SIPLUS ET200S 4DI (1PU=5PCS) -25...+60 DGR C WITH CONFORMAL COATING BASED ON 6ES7131-4BD01-0AA0 . ELECTRONIC MODULE 24V DC WIDTH: 15 MM 5 PCS PER PACKAGING UNIT

Артикул: 6AG1131-4BD01-2AA0
Производитель: Siemens


SIPLUS ET200S 4DI (1PU=5PCS) -25...+60 DGR C WITH CONFORMAL COATING BASED ON 6ES7131-4BD01-0AA0 . ELECTRONIC MODULE 24V DC WIDTH: 15 MM 5 PCS PER PACKAGING UNIT
Supply voltage
24 V DC Yes; From power module
permissible range, lower limit (DC) 20.4 V
permissible range, upper limit (DC) 28.8 V
Reverse polarity protection Yes
Input current
from backplane bus 3.3 V DC, max. 10 mA
from supply voltage L+, max. Dependent on encoder
Encoder supply
Output voltage min. L+ (-0.5 V), under load
Output current, rated value 500 mA
Output current, permissible range 0 to 500 mA
Power losses
Power loss, typ. 0.7 W
Address area
Address space per module
with packing 4 bit
without packing 1 byte
Digital inputs
Number/binary inputs 4
Input characteristic curve acc. to IEC 61131, Type 1 Yes
Input voltage
Type of input voltage DC
Rated value, DC 24 V
for signal "0" -30 to +5 V
for signal "1" 15 to 30 V
Input current
for signal "1", typ. 7 mA; at 24 V
Input delay (for rated value of input voltage)
for standard inputs
Parameterizable No
at "0" to "1", min. 2 ms; typically 3 ms
at "0" to "1", max. 4.5 ms
at "1" to "0", min. 2 ms; typically 3 ms
at "1" to "0", max. 4.5 ms
Cable length
Cable length, shielded, max. 1000 m
Cable length unshielded, max. 600 m
Encoder
Connectable encoders
2-wire sensor Yes
Permissible quiescent current (2-wire sensor), max. 1.5 mA
Interrupts/diagnostics/status information
Diagnostic messages
Diagnostic functions No
Diagnostics indication LED
Group error SF (red) No
Status indicator digital input (green) Yes; per channel
Galvanic isolation
Galvanic isolation digital inputs
between the channels No
between the channels and the backplane bus Yes
Permissible potential difference
between different circuits 75 VDC / 60 VAC
Isolation
Isolation checked with 500 V DC
Ambient conditions
Extended ambient conditions
Relative to ambient temperature-atmospheric pressure-installation altitude Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m)
Relative humidity
with condensation / maximum 100 %; Relative humidity, incl. condensation / frost permitted (no commissioning under condensation conditions)
Resistance
to biologically active substances / conformity with EN 60721-3-3 Yes; , Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation!
to chemically active substances / conformity with EN 60721-3-3 Yes; , Class 3C4 incl. salt spray. The supplied connector covers must remain on the unused interfaces during operation!
to mechanically active substances / conformity with EN 60721-3-3 Yes; , Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation!
Mechanical and climatic conditions during operation
Climatic conditions in operation
Temperature
Min. -25 °C; = Tmin
max. 60 °C; = Tmax
Standards, approvals, certificates
CE mark Yes
Dimensions
Width 15 mm
Height 81 mm
Depth 52 mm
Weight
Weight, approx. 35 g
Status Mar 12, 2012