SIPLUS ET200S EM 2RO DC24V-AC230V/5A -25 ... +70 DEGREES C BASED ON 6ES7132-4HB01-0AB0 5 PIECES PER PACKAGING UNIT . ELECTRON. MODULES FOR ET 200S, 2 DO RELAY 24V DC - 230V AC/5A,15 MM WIDTH FIRST-UP SIGNAL WITH LED SF (GROUP FAULT),

Артикул: 6AG1132-4HB01-2AB0
Производитель: Siemens


Наименование продукта
SIPLUS ET200S EM 2RO DC24V-AC230V/5A -25 ... +70 DEGREES C BASED ON 6ES7132-4HB01-0AB0 5 PIECES PER PACKAGING UNIT . ELECTRON. MODULES FOR ET 200S, 2 DO RELAY 24V DC - 230V AC/5A,15 MM WIDTH FIRST-UP SIGNAL WITH LED SF (GROUP FAULT),
Жизненный цикл продукта
Разрешение на поставку Постепенное снятие продукта с производства Снятие продукта с производства Окончательное снятие продукта с производства
2008-05-01
SIPLUS ET200S EM 2RO DC24V-AC230V/5A -25 ... +70 DEGREES C BASED ON 6ES7132-4HB01-0AB0 5 PIECES PER PACKAGING UNIT . ELECTRON. MODULES FOR ET 200S, 2 DO RELAY 24V DC - 230V AC/5A,15 MM WIDTH FIRST-UP SIGNAL WITH LED SF (GROUP FAULT),
Supply voltage
Load voltage L+
Rated value (DC) 24 V; From power module
Reverse polarity protection Yes
Input current
from load voltage L+ (without load), max. 30 mA
from backplane bus 3.3 V DC, max. 10 mA
Power losses
Power loss, typ. 0.6 W
Address area
Address space per module
with packing 2 bit
without packing 1 byte
Digital outputs
Number/binary outputs 2
Functionality/short-circuit strength No; external fuse, max. 6 A quick-acting
Limitation of inductive shutdown voltage to No
Controlling a digital input Yes
Output current
for signal "1" rated value 5 A
for signal "1" minimum load current 8 mA
Parallel switching of 2 outputs
for increased power No
for redundant control of a load No
Switching frequency
with resistive load, max. 2 Hz
with inductive load, max. 0.5 Hz
on lamp load, max. 2 Hz
Relay outputs
Switching capacity of contacts
Thermal continuous current, max. 5 A
Cable length
Cable length, shielded, max. 1000 m
Cable length unshielded, max. 600 m
Isochronous mode
Isochronous operation (application synchronized up to terminal) No
Interrupts/diagnostics/status information
Substitute values connectable Yes; 0/1
Diagnostic messages
Diagnostic functions No
Diagnostics indication LED
Status indicator digital output (green) Yes
Parameter
Remark 3 bytes
Behavior on CPU/Master STOP, channel-wise Substitute a value/keep last value
Galvanic isolation
Galvanic isolation digital outputs
between the channels Yes
between the channels and the backplane bus Yes
between the channels and the load voltage L+ Yes
Isolation
tested with
Channels against backplane bus and load voltage L+ 1500 V AC
Load voltage L+ against backplane bus 500 V DC
Ambient conditions
Extended ambient conditions
Relative to ambient temperature-atmospheric pressure-installation altitude Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m)
Relative humidity
with condensation / maximum 100 %; , incl. condensation / frost permitted (no commissioning under condensation conditions)
Resistance
to biologically active substances / conformity with EN 60721-3-3 Yes; , Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation in corrosive atmospheres!
to chemically active substances / conformity with EN 60721-3-3 Yes; , Class 3C4 incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation!
to mechanically active substances / conformity with EN 60721-3-3 Yes; , Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation!
Dimensions
Width 15 mm
Height 81 mm
Depth 52 mm
Weight
Weight, approx. 50 g
Status Mar 12, 2012