SIPLUS ET200S PM-E DC 24V WITH DIAGNOSTICS -40 ... +70 DEGREES C WITH CONFORMAL COATING BASED ON 6ES7138-4CA01-0AA0

Артикул: 6AG1138-4CA01-2AA0
Производитель: Siemens


SIPLUS ET200S PM-E DC 24V WITH DIAGNOSTICS -40 ... +70 DEGREES C WITH CONFORMAL COATING BASED ON 6ES7138-4CA01-0AA0
Supply voltage
Load voltage L+
Rated value (DC) 24 V
Short-circuit protection No; external (e.g. automatic circuit breaker), tripping characteristic C
Reverse polarity protection Yes
Input current
from load voltage 1L+ (without load), max. 4 mA
Current carrying capacity
Current carrying capacity up to 60 °C, max. 10 A
Power losses
Power loss, typ. 0.1 W
Interrupts/diagnostics/status information
Diagnostic messages
Diagnostics Yes
Missing load voltage Yes
Diagnostics indication LED
Rated load voltage PWR (green) Yes
Group error SF (red) Yes
Parameter
Remark 3 bytes
Missing load voltage Disable / enable
Galvanic isolation
primary/secondary Yes; between rated load voltage and backplane bus, between power modules
Isolation
Isolation checked with 500 V DC
Ambient conditions
Extended ambient conditions
Relative to ambient temperature-atmospheric pressure-installation altitude Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m)
Relative humidity
with condensation / maximum 100 %; Relative humidity, incl. condensation / frost permitted (no commissioning under condensation conditions)
Resistance
to biologically active substances / conformity with EN 60721-3-3 Yes; , Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation!
to chemically active substances / conformity with EN 60721-3-3 Yes; , Class 3C4 incl. salt spray. The supplied connector covers must remain on the unused interfaces during operation!
to mechanically active substances / conformity with EN 60721-3-3 Yes; , Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation!
Mechanical and climatic conditions during operation
Climatic conditions in operation
Temperature
Min. -40 °C; = Tmin
max. 70 °C; = Tmax
Standards, approvals, certificates
CE mark Yes
UL approval Yes
Dimensions
Width 15 mm
Height 81 mm
Depth 52 mm
Weight
Weight, approx. 35 g
Status Mar 12, 2012