SIPLUS S7-1200 SM1222 16DA FOR MEDIAL STRESS WITH CONFORMAL COATING BASED ON 6ES7222-1BH30-0XB0 . DIGITAL OUTPUT 16 DO, 24V DC, TRANSISTOR 0.5A

Артикул: 6AG1222-1BH30-4XB0
Производитель: Siemens


Наименование продукта
SIPLUS S7-1200 SM1222 16DA FOR MEDIAL STRESS WITH CONFORMAL COATING BASED ON 6ES7222-1BH30-0XB0 . DIGITAL OUTPUT 16 DO, 24V DC, TRANSISTOR 0.5A
Жизненный цикл продукта
Разрешение на поставку Постепенное снятие продукта с производства Снятие продукта с производства Окончательное снятие продукта с производства
2010-04-04
SIPLUS S7-1200 SM1222 16DA FOR MEDIAL STRESS WITH CONFORMAL COATING BASED ON 6ES7222-1BH30-0XB0 . DIGITAL OUTPUT 16 DO, 24V DC, TRANSISTOR 0.5A
Supply voltage
permissible range, lower limit (DC) 20.4 V
permissible range, upper limit (DC) 28.8 V
Input current
from backplane bus 5 V DC, max. 140 mA
Power losses
Power loss, typ. 2.5 W
Digital inputs
Number/binary inputs 0
Digital outputs
Number/binary outputs 16
In groups of 1
Functionality/short-circuit strength No; to be provided externally
Limitation of inductive shutdown voltage to typ. (L+) -48 V
Switching capacity of the outputs
with resistive load, max. 0.5 A
on lamp load, max. 5 W
Output voltage
Rated value (DC) 24 V
for signal "0", max. 0.1 V; with 10 kOhm load
for signal "1", min. 20 V DC
Output current
for signal "1" rated value 0.5 A
for signal "0" residual current, max. 10 µA
Output delay with resistive load
0 to "1", max. 50 µs
1 to "0", max. 200 µs
Aggregate current of outputs (per group)
horizontal installation
up to 50 °C, max. 8 A; Current per mass
Relay outputs
Switching capacity of contacts
with inductive load, max. 0.5 A
on lamp load, max. 5 W
Switching frequency/contacts/at ohmic load/maximum 0.5 A
Cable length
Cable length, shielded, max. 500 m
Cable length unshielded, max. 150 m
Interrupts/diagnostics/status information
Alarms
Alarms Yes
Diagnostic alarm Yes
Diagnostic messages
Diagnostic functions Yes
Diagnostics indication LED
For status of the outputs Yes
for maintenance Yes
Status indicator digital output (green) Yes
Galvanic isolation
Galvanic isolation digital outputs
between the channels, in groups of 1
between the channels and the backplane bus 500 V AC
Ambient conditions
Extended ambient conditions
Relative to ambient temperature-atmospheric pressure-installation altitude Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m)
Relative humidity
with condensation / maximum 100 %; Relative humidity, incl. condensation / frost permitted (no commissioning under condensation conditions)
Resistance
to biologically active substances / conformity with EN 60721-3-3 Yes; , Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation!
to chemically active substances / conformity with EN 60721-3-3 Yes; , Class 3C4 incl. salt spray. The supplied connector covers must remain on the unused interfaces during operation!
to mechanically active substances / conformity with EN 60721-3-3 Yes; , Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation!
Climatic and mechanical conditions for storage and transport
Climatic conditions for storage and transport
Free fall
Drop height, max. (in packaging) 0.3 m; five times, in dispatch package
Temperature
Permissible temperature range -40 °C to +70 °C
Mechanical and climatic conditions during operation
Climatic conditions in operation
Temperature
Min. 0 °C; = Tmin
max. 55 °C; = Tmax
Permissible temperature change 5°C to 55°C, 3°C / minute
Degree and class of protection
IP20 Yes
Standards, approvals, certificates
CE mark Yes
FM approval Yes
Connection method
required front connector Yes
Mechanics/material
Type of housing (front)
Plastic Yes
Dimensions
Width 45 mm
Height 100 mm
Depth 75 mm
Weight
Weight, approx. 220 g
Status Mar 12, 2012

Назад в раздел