SIPLUS S7-1200 SM1223 16DI/16DO -25 ... +70 DEGREES C WITH CONFORMAL COATING BASED ON 6ES7223-1PL30-0XB0 . DIGITALE E/A 16 DI / 16 DO, 16 DI DC 24 V, SINK/SOURCE, 16 DO, RELAYS 2A

Артикул: 6AG1223-1PL30-2XB0
Производитель: Siemens


Наименование продукта
SIPLUS S7-1200 SM1223 16DI/16DO -25 ... +70 DEGREES C WITH CONFORMAL COATING BASED ON 6ES7223-1PL30-0XB0 . DIGITALE E/A 16 DI / 16 DO, 16 DI DC 24 V, SINK/SOURCE, 16 DO, RELAYS 2A
Жизненный цикл продукта
Разрешение на поставку Постепенное снятие продукта с производства Снятие продукта с производства Окончательное снятие продукта с производства
2010-01-06
    Версия от 2012-02-26
 
SIPLUS S7-1200 SM1223 16DI/16DO -25 ... +70 DEGREES C WITH CONFORMAL COATING BASED ON 6ES7223-1PL30-0XB0 . DIGITALE E/A 16 DI / 16 DO, 16 DI DC 24 V, SINK/SOURCE, 16 DO, RELAYS 2A
Supply voltage
24 V DC Yes
permissible range, lower limit (DC) 20.4 V
permissible range, upper limit (DC) 28.8 V
Input current
from backplane bus 5 V DC, max. 180 mA
Digital inputs
from load voltage L+ (without load), max. 4 mA/input 11 mA/relay
Output voltage
Power supply to the transmitters
present Yes
Power losses
Power loss, typ. 10 W
Digital inputs
Number/binary inputs 16
In groups of 2
Input characteristic curve acc. to IEC 61131, Type 1 Yes
Number of simultaneously controllable inputs
all mounting positions
up to 40 °C, max. 16
horizontal installation
up to 40 °C, max. 16
up to 50 °C, max. 16
vertical installation
up to 40 °C, max. 16
Input voltage
Type of input voltage DC
Rated value, DC 24 V
for signal "0" 5 V DC at 1 mA
for signal "1" 15 V DC at 2.5 mA
Input current
for signal "0", max. (permissible quiescent current) 1 mA
for signal "1", min. 2.5 mA
for signal "1", typ. 4 mA; Typical
Input delay (for rated value of input voltage)
for standard inputs
Parameterizable Yes; 0.2, 0.4, 0.8, 1.6, 3.2, 6.4, and 12.8 ms, selectable in groups of four
for interrupt inputs
Parameterizable Yes
Cable length
Cable length, shielded, max. 500 m
Cable length unshielded, max. 300 m
Digital outputs
Number/binary outputs 16
In groups of 4
Functionality/short-circuit strength No; to be provided externally
Switching capacity of the outputs
with resistive load, max. 2 A
on lamp load, max. 30 W DC ; 200 W AC
Output voltage
Rated value (AC) 5 to 250 V AC
Rated value (DC) 5 to 30 V AC
Output current
for signal "1" permissible range, max. 2 A
Output delay with resistive load
0 to "1", max. 10 ms
1 to "0", max. 10 ms
Aggregate current of outputs (per group)
horizontal installation
up to 50 °C, max. 8 A; Current per mass
Relay outputs
Number of relay outputs 16
Rated input voltage of relay coil L+ (DC) 24 V
Number of operating cycles, max. mechanically 10 million, at rated load voltage 100,000
Switching capacity of contacts
with inductive load, max. 2 A
on lamp load, max. 30 W DC ; 200 W AC
Switching frequency/contacts/at ohmic load/maximum 2 A
Cable length
Cable length, shielded, max. 500 m
Cable length unshielded, max. 150 m
Interrupts/diagnostics/status information
Alarms
Alarms Yes
Diagnostic alarm Yes
Diagnostic messages
Diagnostic functions Yes
Diagnostics indication LED
for status of the inputs Yes
For status of the outputs Yes
for maintenance Yes
Status indicator digital output (green) Yes
Status indicator digital input (green) Yes
Galvanic isolation
Galvanic isolation digital inputs
between the channels, in groups of 2
Galvanic isolation digital outputs
between the channels Relay
between the channels, in groups of 4
between the channels and the backplane bus 1500 V AC for 1 minute
Ambient conditions
Extended ambient conditions
Relative to ambient temperature-atmospheric pressure-installation altitude Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m)
Relative humidity
with condensation / maximum 100 %; Relative humidity, incl. condensation / frost permitted (no commissioning under condensation conditions)
Resistance
to biologically active substances / conformity with EN 60721-3-3 Yes; , Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation!
to chemically active substances / conformity with EN 60721-3-3 Yes; , Class 3C4 incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation!
to mechanically active substances / conformity with EN 60721-3-3 Yes; , Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation!
Climatic and mechanical conditions for storage and transport
Climatic conditions for storage and transport
Free fall
Drop height, max. (in packaging) 0.3 m; five times, in dispatch package
Temperature
Permissible temperature range -40 °C to +70 °C
Mechanical and climatic conditions during operation
Climatic conditions in operation
Temperature
Min. -25 °C; = Tmin
max. 70 °C; = Tmax
Degree and class of protection
IP20 Yes
Standards, approvals, certificates
CE mark Yes
cULus Yes
FM approval Yes
Connection method
required front connector Yes
Mechanics/material
Type of housing (front)
Plastic Yes
Dimensions
Width 70 mm
Height 100 mm
Depth 75 mm