SIPLUS S7-1200 SM231 AI 4 12BIT FOR MEDIAL STRESS WITH CONFORMAL COATING BASED ON 6ES7231-4HD30-0XB0 . ANALOG INPUT, 4 AI, +/-10V, +/-5V, +/-2.5V, OR 0-20 MA 12 BIT + SIGN BIT (13 BIT ADC)

Артикул: 6AG1231-4HD30-4XB0
Производитель: Siemens


Наименование продукта
SIPLUS S7-1200 SM231 AI 4 12BIT FOR MEDIAL STRESS WITH CONFORMAL COATING BASED ON 6ES7231-4HD30-0XB0 . ANALOG INPUT, 4 AI, +/-10V, +/-5V, +/-2.5V, OR 0-20 MA 12 BIT + SIGN BIT (13 BIT ADC)
Жизненный цикл продукта
Разрешение на поставку Постепенное снятие продукта с производства Снятие продукта с производства Окончательное снятие продукта с производства
2010-04-04
    Версия от 2012-01-07
 
SIPLUS S7-1200 SM231 AI 4 12BIT FOR MEDIAL STRESS WITH CONFORMAL COATING BASED ON 6ES7231-4HD30-0XB0 . ANALOG INPUT, 4 AI, +/-10V, +/-5V, +/-2.5V, OR 0-20 MA 12 BIT + SIGN BIT (13 BIT ADC)
Supply voltage
24 V DC Yes
Input current
Current consumption, typ. 45 mA
from backplane bus 5 V DC, typ. 80 mA
Power losses
Power loss, typ. 1.5 W
Analog inputs
Number of analog inputs 4; Current or voltage differential inputs
permissible input frequency for current input (destruction limit), max. ± 35 V
permissible input voltage for voltage input (destruction limit), max. 35 V
permissible input current for voltage input (destruction limit), max. 40 mA
Cycle time (all channels) max. 625 µs
permissible input current for current input (destruction limit), max. 40 mA
Input ranges
Voltage Yes; ±10 V, ±5 V, ±2.5 V
Current Yes; 0 to 20 mA
Thermocouple No
Resistance thermometer No
Resistance No
Input ranges (rated values), voltages
-10 V to +10 V Yes
Input resistance (-10 V to +10 V) ?9 MOhm
-2.5 V to +2.5 V Yes
Input resistance (-2.5 V to +2.5 V) ?9 MOhm
-5 V to +5 V Yes
Input resistance (-5 V to +5 V) ?9 MOhm
Input ranges (rated values), currents
0 to 20 mA Yes
Input resistance (0 to 20 mA) 280 ?
Thermocouple (TC)
Temperature compensation
Parameterizable No
Analog outputs
Number of analog outputs 0
Analog value creation
Integrations and conversion time/ resolution per channel
Resolution with overrange (bit including sign), max. 12 bit; + sign
Integration time, parameterizable Yes
Interference voltage suppression for interference frequency f1 in Hz 40 dB, DC to 60 V for interference frequency 50 / 60 Hz
Smoothing of measured values
Parameterizable Yes
Step: None Yes
Step: low Yes
Step: Medium Yes
Step: High Yes
Errors/accuracies
Temperature error (relative to input area) 25 °C ±0.1 % to 55 °C ±0.2 % total measurement range
Basic error limit (operational limit at 25 °C)
Voltage, relative to input area +/- 0,1 %
Current, relative to input area +/- 0,1 %
Interference voltage suppression for f = n x (fl +/- 1%), fl = interference frequency
common mode voltage, max. 12 V
Interrupts/diagnostics/status information
Alarms
Alarms Yes
Diagnostic alarm Yes
Diagnoses
Diagnostic functions Yes
Monitoring the supply voltage to the electronics Yes
Wire break No
Diagnostics indication LED
for status of the inputs Yes
for maintenance Yes
Galvanic isolation
Galvanic isolation analog outputs
between the channels and the power supply of the electronics No
Ambient conditions
Extended ambient conditions
Relative to ambient temperature-atmospheric pressure-installation altitude Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m)
Relative humidity
with condensation / maximum 100 %; Relative humidity, incl. condensation / frost permitted (no commissioning under condensation conditions)
Resistance
to biologically active substances / conformity with EN 60721-3-3 Yes; , Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation!
to chemically active substances / conformity with EN 60721-3-3 Yes
to mechanically active substances / conformity with EN 60721-3-3 Yes; , Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation!
Climatic and mechanical conditions for storage and transport
Climatic conditions for storage and transport
Free fall
Drop height, max. (in packaging) 0.3 m; five times, in dispatch package
Temperature
Permissible temperature range -40 °C to +70 °C
Mechanical and climatic conditions during operation
Climatic conditions in operation
Temperature
Min. 0 °C; = Tmin
max. 55 °C; = Tmax
Degree and class of protection
IP20 Yes
Standards, approvals, certificates
CE mark Yes
FM approval Yes
Connection method
required front connector Yes
Mechanics/material
Type of housing (front)
Plastic Yes
Dimensions
Width 45 mm
Height 100 mm
Depth 75 mm
Weight
Weight, approx. 180 g
Status Dec 19, 2011