SIPLUS S7-1200 SM1231 RTD -25 ... +70 DEGREE C WITH CONFORMAL COATING BASED ON 6ES7231-5PD30-0XB0 . ANALOGINPUT, 4 AI RTD MODUL

Артикул: 6AG1231-5PD30-2XB0
Производитель: Siemens


Наименование продукта
SIPLUS S7-1200 SM1231 RTD -25 ... +70 DEGREE C WITH CONFORMAL COATING BASED ON 6ES7231-5PD30-0XB0 . ANALOGINPUT, 4 AI RTD MODUL
Жизненный цикл продукта
Разрешение на поставку Постепенное снятие продукта с производства Снятие продукта с производства Окончательное снятие продукта с производства
2011-09-03
    Версия от 2012-02-11
 
SIPLUS S7-1200 SM1231 RTD -25 ... +70 DEGREE C WITH CONFORMAL COATING BASED ON 6ES7231-5PD30-0XB0 . ANALOGINPUT, 4 AI RTD MODUL
Supply voltage
24 V DC Yes
Input current
Current consumption, typ. 40 mA
from backplane bus 5 V DC, typ. 80 mA
Power losses
Power loss, typ. 1.5 W
Analog inputs
Number of analog inputs 4; Resistance thermometer
permissible input frequency for current input (destruction limit), max. ± 35 V
Technical unit for temperature measurement adjustable Degrees Celsius/degrees Fahrenheit
Input ranges
Resistance thermometer Yes; Resistance-type transmitter: Pt10, Pt50, Pt100, Pt200, Pt500, Pt1000, Ni100, Ni120, Ni200, Ni500, Ni1000, Cu10, Cu50, Cu100, LG-Ni1000
Resistance Yes; 150 ?, 300 ?, 600 ?
Input ranges (rated values), resistance thermometers
Cu 10 Yes
Input resistance (Cu 10) 10 ?
Ni 100 Yes
Input resistance (Ni 100) 100 ?
Ni 1000 Yes
Input resistance (Ni 1000) 1000 ?
LG-Ni 1000 Yes
Input resistance (LG-Ni 1000) 1000 ?
Ni 120 Yes
Input resistance (Ni 120) 120 ?
Ni 200 Yes
Input resistance (Ni 200) 200 ?
Ni 500 Yes
Input resistance (Ni 500) 500 ?
Pt 100 Yes
Input resistance (Pt 100) 100 ?
Pt 1000 Yes
Input resistance (Pt 1000) 1000 ?
Pt 200 Yes
Input resistance (Pt 200) 200 ?
Pt 500 Yes
Input resistance (Pt 500) 500 ?
Input ranges (rated values), resistors
0 to 150 ohms Yes
0 to 300 ohms Yes
0 to 600 ohms Yes
Thermocouple (TC)
Temperature compensation
Parameterizable No
Analog value creation
Measurement principle integrating
Integrations and conversion time/ resolution per channel
Resolution with overrange (bit including sign), max. 15 bit; + sign
Integration time, parameterizable No
Interference voltage suppression for interference frequency f1 in Hz 85 dB at 50 / 60 / 400 Hz
Errors/accuracies
Temperature error (relative to input area) 25 °C ±0.1%, -25 °C to 70 °C ±0.4 % entire measuring range
Interference voltage suppression for f = n x (fl +/- 1%), fl = interference frequency
Common mode interference, min. 120 dB
Interrupts/diagnostics/status information
Alarms
Alarms Yes
Diagnostic alarm Yes
Diagnostic messages
Diagnostic functions Yes; Can be read out
Monitoring the supply voltage to the electronics Yes
Wire break Yes
Diagnostics indication LED
for status of the inputs Yes
for maintenance Yes
Ambient conditions
Extended ambient conditions
Relative to ambient temperature-atmospheric pressure-installation altitude Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m)
Relative humidity
with condensation / maximum 100 %; Relative humidity, incl. condensation / frost permitted (no commissioning under condensation conditions)
Resistance
to biologically active substances / conformity with EN 60721-3-3 Yes; , Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation!
to chemically active substances / conformity with EN 60721-3-3 Yes; , Class 3C4 incl. salt spray. The supplied connector covers must remain on the unused interfaces during operation!
to mechanically active substances / conformity with EN 60721-3-3 Yes; , Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation!
Climatic and mechanical conditions for storage and transport
Climatic conditions for storage and transport
Free fall
Drop height, max. (in packaging) 0.3 m; five times, in dispatch package
Temperature
Permissible temperature range -40 °C to +70 °C
Mechanical and climatic conditions during operation
Climatic conditions in operation
Temperature
Min. -25 °C; = Tmin
max. 70 °C; = Tmax
Degree and class of protection
IP20 Yes
Standards, approvals, certificates
CE mark Yes
Connection method
required front connector Yes
Mechanics/material
Type of housing (front)
Plastic Yes
Dimensions
Width 45 mm
Height 100 mm
Depth 75 mm
Weight
Weight, approx. 220 g
Status Feb 6, 2012