SIPLUS S7-400 SM431 BEG AI6X14 FOR MEDIAL STRESS AND MODIFIED INOUT CIRCUIT BASED ON 6ES7431-1KF20-0AB0

Артикул: 6AG1431-1KF20-4AY0
Производитель: Siemens


Наименование продукта
SIPLUS S7-400 SM431 BEG AI6X14 FOR MEDIAL STRESS AND MODIFIED INOUT CIRCUIT BASED ON 6ES7431-1KF20-0AB0
Жизненный цикл продукта
Разрешение на поставку Постепенное снятие продукта с производства Снятие продукта с производства Окончательное снятие продукта с производства
2007-03-22
SIPLUS S7-400 SM431 BEG AI6X14 FOR MEDIAL STRESS AND MODIFIED INOUT CIRCUIT BASED ON 6ES7431-1KF20-0AB0
Supply voltage
Load voltage L+
Rated value (DC) 24 V; Only required for supplying 2-wire transmitters
Reverse polarity protection Yes
Input current
from load voltage L+ (without load), max. 200 mA; for 8 connected, fully controlled 2-wire transmitters
from backplane bus 5 V DC, max. 1000 mA
Power losses
Power loss, typ. 4.9 W
Analog inputs
Number of analog inputs 8
Number of analog inputs for voltage/current measurement 8
Number of analog inputs for resistance measurement 4
permissible input voltage for voltage input (destruction limit), max. 18 V; 18 V continuous, 75 V for 1 ms (mark to space ratio 1:20)
permissible input current for current input (destruction limit), max. 40 mA; Permanent
Input ranges
Voltage Yes
Current Yes
Resistance Yes
Input ranges (rated values), voltages
1 to 5 V Yes
Input resistance (1 to 5 V) 10 MΩ
-1 V to +1 V Yes
Input resistance (-1 V to +1 V) 10 MΩ
-10 V to +10 V Yes
Input resistance (-10 V to +10 V) 100 kΩ
Input ranges (rated values), currents
-20 to +20 mA Yes
Input resistance (-20 to +20 mA) 50 Ω
4 to 20 mA Yes
Input resistance (4 to 20 mA) 50 kΩ
Input ranges (rated values), resistors
0 to 600 ohms Yes
Cable length
Cable length, shielded, max. 200 m
Analog value creation
Integrations and conversion time/ resolution per channel
Resolution with overrange (bit including sign), max. 14 bit; 14 / 14 / 14
Integration time, parameterizable Yes
Basic conversion time, ms 52 µs
Interference voltage suppression for interference frequency f1 in Hz none / 400 / 60 / 50 Hz
Encoder
Connection of signal encoders
for current measurement as 2-wire transducer Yes
for current measurement as 4-wire transducer Yes
for resistance measurement with 2-conductor connection Yes; Line resistances are also measured
for resistance measurement with 3-conductor connection Yes; Line resistances are also measured
for resistance measurement with 4-conductor connection Yes
Errors/accuracies
Operational limit in overall temperature range
Voltage, relative to input area +/- 0,7 %; +/-0.7% at +/-1 V; +/-0.9% at +/-10 V, 1 to 5 V
Current, relative to input area +/- 0,8 %; at +/-20 mA, 4 to 20 mA
Impedance, relative to input area +/- 1 %
Basic error limit (operational limit at 25 °C)
Voltage, relative to input area +/- 0,6 %; 0.6% at +/-1 V; 0.75% at +/-10 V, 1 to 5 V
Current, relative to input area +/- 0,7 %; at +/-20 mA, 4 to 20 mA
Impedance, relative to input area +/- 0,7 %; 0 to 600 ohms
Galvanic isolation
Galvanic isolation analog inputs
Galvanic isolation analog inputs Yes; internal/external
between the channels No
Permissible potential difference
between the inputs (UCM) 8 V AC
Isolation
Isolation checked with 2120 V DC between bus and analog part; 500 V DC between bus and local ground; 707 V DC between analog part and L+/M; 2120 V DC between analog part and local ground; 2120 V DC between L+/M and local ground
Ambient conditions
Extended ambient conditions
Relative to ambient temperature-atmospheric pressure-installation altitude Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m)
Relative humidity
with condensation / maximum 100 %; Relative humidity, incl. condensation / frost permitted (no commissioning under condensation conditions)
Resistance
to biologically active substances / conformity with EN 60721-3-3 Yes; , Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation!
to chemically active substances / conformity with EN 60721-3-3 Yes; , Class 3C4 incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation!
to mechanically active substances / conformity with EN 60721-3-3 Yes; , Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation!
Dimensions
Width 25 mm
Height 290 mm
Depth 210 mm
Required slots 1
Weight
Weight, approx. 500 g
Status Mar 12, 2012