| SIMOTION D435 mit PROFINET Board, Abb. ähnlich | | SIMOTION DRIVE-BASED CONTROL UNIT D435; PROGRAMMABLE MOTION CONTROLLER; STANDARD PERFORMANCE; INTERFACES: 8 DI, 8 DI/DO, 4 DRIVE-CLIQ, 2 PROFIBUS, 2 ETHERNET, 2 USB, 1 OPTION SLOT |
PLC- und Motion Control Performance | |
Number of axes / maximum | 32 |
Bus clock cycle / acc. to PROFIBUS / remark | 1 ms |
Send clock cycle / acc. to PROFINET / minimum | 0,5 ms |
Interpolator clock cycle / minimum | 1 ms |
Servo clock cycle / minimum | 1 ms |
Integrierte Antriebsregelung | |
Number of axes | |
- for servo control / maximum
| 6 |
- for U/f control / maximum
| 8 |
- for vector control / maximum
| 4 |
Speicher | |
Memory capacity | |
| 48 Mbyte |
- on RAM / for Java applications
| 20 Mbyte |
| 23 Mbyte |
| 364 kbyte |
- of the user memory / as persistent memory
| 300 Mbyte |
Kommunikation | |
Number of interfaces | |
| 4 |
| 2 |
- согласно Industrial Ethernet
| 2 |
| 2 |
| 0 |
Allgemeine technische Daten | |
Напряжение питания / при пост.токе / [nicht versorgt - Nennwert] | 24 V |
Напряжение питания | 20,4 V… 28,8 V |
own current drawn / typical | 600 mA |
Inrush current / typical | 6 A |
Мощность потерь / типично | 15 W |
Температура окружающей среды | |
| -40 °C… 70 °C |
| -40 °C… 70 °C |
| 0 °C… 55 °C |
Относительная влажность воздуха / без конденсации | |
| 5 %… 95 % |
Air pressure | 700 hPa… 1060 hPa |
Вид защиты IP | IP20 |
Высота | 380 mm |
Ширина | 50 mm |
Глубина | 270 mm |
Чистый вес | 2600 g |
Количиство цифровых выходов | 8 |
Входное напряжение / на цифровом выходе | |
| 24 V |
- начальный параметр для распознавания сигнала <1>
| 15 V |
- [nicht versorgt - Endwert für Signal<1>-Erkennung]
| 30 V |
- [nicht versorgt - Anfangswert für Signal<0>-Erkennung]
| -3 V |
- конечный параметр для распознавания сигнала <0>
| 5 V |
Electrical isolation / at the digital input | Да |
Current drawn / at the digital input/output for digital input signals / for signal <1> | 10 mA |
Input delay time / at the digital input | |
- for signal <0> to <1> / typical
| 50 µs |
- for signal <1> to <0> / typical
| 150 µs |
Number of digital inputs/outputs | 8 |
Bei Verwendung als Eingang | |
Input voltage / at the digital input/output for digital input signals | |
| 24 V |
- initial value for <1> signal detection
| 15 V |
- final value for <1> signal detection
| 30 V |
- initial value for <0> signal detection
| -3 V |
- final value for <0> signal detection
| 5 V |
Electrical isolation / at the digital input/output for the digital inputs signals / between the channels and electronics power suppl
y | Нет |
Current drawn / at the digital input / for signal <1> / typical | 10 mA |
Input delay time | |
- at the digital input/output for digital input signals / for signal <0> to <1> / typical
| 5 µs |
Reproducibility of the edge detection / at the digital input/output for digital input signals as probe input | 5 µs |
Bei Verwendung als Ausgang | |
Output voltage / at the digital input/output for digital output signals / for signal <1> / for DC / rated value
| 24 V |
Output voltage / at the digital input/output for digital output signals | |
| 20,4 V… 28,8 V |
Electrical isolation / at the digital input/output for digital output signals / between the channels and electronics power supply | Нет |
Current load capability / at the digital input/output for digital output signals / maximum | 500 mA |
Leakage current / at the digital input /output for digital output signals / maximum | 2 mA |
Delay time for the signal change / at the digital input/output for digital output signals / for ohmic load | |
| 150 µs… 400 µs |