SIMATIC S7, ANALOG OUTPUT SM 332, OPTICALLY ISOLATED, 4 AO, 0/4 UP TO 20 MA, 20 PIN, FOR SIGNALS FROM HAZARDOUSAREAS CAPABLE OF DIANOST., PTB-TESTED

Артикул: 6ES7332-5RD00-0AB0
Производитель: Siemens


Наименование продукта
SIMATIC S7, ANALOG OUTPUT SM 332, OPTICALLY ISOLATED, 4 AO, 0/4 UP TO 20 MA, 20 PIN, FOR SIGNALS FROM HAZARDOUSAREAS CAPABLE OF DIANOST., PTB-TESTED
Жизненный цикл продукта
Разрешение на поставку Постепенное снятие продукта с производства Снятие продукта с производства Окончательное снятие продукта с производства
1996-09-30
Manuals weitere>>
Principles of explosion protection  2006-04-05
SIMATIC S7, ANALOG OUTPUT SM 332, OPTICALLY ISOLATED, 4 AO, 0/4 UP TO 20 MA, 20 PIN, FOR SIGNALS FROM HAZARDOUSAREAS CAPABLE OF DIANOST., PTB-TESTED
Supply voltage
Load voltage L+
Rated value (DC) 24 V
Input current
from load voltage L+ (without load), max. 180 mA
from backplane bus 5 V DC, max. 80 mA
Power losses
Power loss, typ. 4 W
Analog outputs
Number of analog outputs 4
Voltage output, short-circuit protection Yes
Voltage output, short-circuit current, max. 70 mA
Current output, no-load voltage, max. 14 V
Output ranges, current
0 to 20 mA Yes
4 to 20 mA Yes
Connection of actuators
for current output 2-conductor connection Yes
Load impedance (in rated range of output)
with current outputs, max. 500 Ω
Cable length
Cable length, shielded, max. 200 m
Analog value creation
Integrations and conversion time/ resolution per channel
Resolution with overrange (bit including sign), max. 15 bit
Basic conversion time, ms 2.5 ms
Errors/accuracies
Operational limit in overall temperature range
Current, relative to output area +/- 0,55 %
Basic error limit (operational limit at 25 °C)
Current, relative to output area +/- 0,2 %
Interrupts/diagnostics/status information
Diagnostic messages
Diagnostic functions Yes
Diagnostic information readable Yes
Overrange Yes
Wire break in actuator cable Yes
Group error Yes
Diagnostics indication LED
Short circuit per channel (red) Yes
Short-circuit group error (red) Yes
Ex(i) characteristics
Module for Ex(i) protection Yes
Galvanic isolation
Galvanic isolation analog outputs
Galvanic isolation analog outputs Yes
Permissible potential difference
between outputs and MANA (UCM) 60 V DC/30 V AC when used in the hazardous area; 400 V DC/250 V AC when used in NON-hazardous area
between the outputs (UCM) 60 V DC/30 V AC when used in the hazardous area; 400 V DC/250 V AC when used in NON-hazardous area
Ambient conditions
Operating temperature
max. 60 °C
Standards, approvals, certificates
Use in hazardous areas
Type of protection acc. to EN 50020 (CENELEC) [EEx ib] IIC
Type of protection acc. to FM Class I, Division 2, Group A, B, C, D T4
Test number PTB Ex-96.D.2026X
Connection method
required front connector 20-pin
Weight
Weight, approx. 280 g
Status Mar 12, 2012