KOMMUNIKATIONSPROZESSOR CP343-1 ERPC FOR CONNECTING SIMATIC S7-300 CPU TO INDUSTRIAL ETHERNET AND TO VARIOUS DATABASES. FUNCTIONS: TCP/UDP, S7-COMM, OPEN COMM. WITH AND WITHOUT RFC 1006, MULTICAST, WEBSERVER, TIME VIA SIMATIC PROCESS OR NTP, ACCESS PROTEC

Артикул: 6GK7343-1FX00-0XE0
Производитель: Siemens


Наименование продукта
KOMMUNIKATIONSPROZESSOR CP343-1 ERPC FOR CONNECTING SIMATIC S7-300 CPU TO INDUSTRIAL ETHERNET AND TO VARIOUS DATABASES. FUNCTIONS: TCP/UDP, S7-COMM, OPEN COMM. WITH AND WITHOUT RFC 1006, MULTICAST, WEBSERVER, TIME VIA SIMATIC PROCESS OR NTP, ACCESS PROTECTION VIA IP-ACCESS LIST, SNMP, DHCP, C-PLUG, GIGABIT-SS 1X RJ45 (10/100/1000 MBIT);
Жизненный цикл продукта
Разрешение на поставку Постепенное снятие продукта с производства Снятие продукта с производства Окончательное снятие продукта с производства
2010-04-19
KOMMUNIKATIONSPROZESSOR CP343-1 ERPC FOR CONNECTING SIMATIC S7-300 CPU TO INDUSTRIAL ETHERNET AND TO VARIOUS DATABASES. FUNCTIONS: TCP/UDP, S7-COMM, OPEN COMM. WITH AND WITHOUT RFC 1006, MULTICAST, WEBSERVER, TIME VIA SIMATIC PROCESS OR NTP, ACCESS PROTECTION VIA IP-ACCESS LIST, SNMP, DHCP, C-PLUG, GIGABIT-SS 1X RJ45 (10/100/1000 MBIT);
Transmission rate  
Transfer rate / at the interface 1 10 1000 Mbit/s
Interfaces  
Number of electrical connections  
  • at interface 1 / in accordance with Industrial Ethernet
1
  • for power supply
1
design of the removable storage / C-PLUG Yes
Supply voltage, current consumption, power loss  
Type of voltage / of supply voltage DC
Supply voltage  
  • 1 / from backplane bus
5 V
  • external
24 V
Relative positive tolerance / at 24 V / with DC 20 %
Relative negative tolerance / at 24 V / with DC 15 %
Consumed current  
  • from backplane bus / at 5 V / for DC / [nicht versorgt - typisch]
0.3 A
  • [nicht versorgt - aus externer Versorgungsspannung] / [nicht versorgt - bei 24 V] / [nicht versorgt - bei DC]
 
  • [nicht versorgt - typisch]
0.16 A
  • maximum
0.6 A
Resistive loss 14.7 W
Permitted ambient conditions  
Ambient temperature  
  • during storage
-40 +70 °C
  • during transport
-40 +70 °C
Relative humidity / at 25 °C / without condensation / during operating / maximum 95 %
Protection class IP IP20
Design, dimensions and weight  
Width 80 mm
Height 125 mm
Depth 120 mm
Net weight 0.8 kg
Performance data / open communication  
Number of possible connections / for open communication / by means of SEND/RECEIVE blocks / maximum 8
Data volume  
  • as user data per ISO on TCP connection / for open communication / by means of SEND/RECEIVE blocks / maximum
8 Kibyte
  • as user data per TCP connection / for open communication / by means of SEND/RECEIVE blocks / maximum
8 Kibyte
  • as user data per UDP connection / for open IE communication / by means of SEND/RECEIVE blocks / maximum
2 Kibyte
Number of Multicast stations 8
Performance data / S7 communication  
Number of possible connections / [nicht versorgt - für S7-Kommunikation]  
  • [nicht versorgt - maximal]
8
Performance data / multi-protocol mode  
Number of active connections / [nicht versorgt - bei Multiprotokollbetrieb] 32
Performance data / ERPC functions  
Number of possible connections / for communication with ERP or MES stations / maximum 8
Number of possible logical triggers / per CP / maximum 8
Number of configurable ERPC symbols for database access  
  • per CPU / maximum
2000
  • per logical trigger / maximum
255
Data volume / as user data and header information per logical trigger 8 Kibyte
Product functions / management, configuration  
Product function / MIB support Yes
Protocol / is supported  
  • SNMP v1
Yes
  • DCP
Yes
  • LLDP
Yes
Identification & maintenance  
  • I&M0 - device-specific information
Yes
  • I&M1 - plant identification/location name
Yes
Product functions / Diagnosis  
Product function / Web-based diagnostics Yes
Product functions / Redundancy  
Product function / Ring redundancy No
Product functions / Security  
Product function  
  • ACL - IP-based
Yes
  • switchoff of non-required services
Yes
  • blocking of communication via physical ports
Yes
  • log file for unauthorized access
No
Product functions / Time  
Product function  
  • SICLOCK support
Yes
  • pass on time synchronization
Yes
Protocol / is supported / NTP Yes
 