SIEMENS BUILDING TECHNOLOGIES COMMUNICATIONS PROCESSOR CP343-1 BACNET FOR CONNECTING SIMATIC S7-300 TO BACNET. ADDITIONAL RUNTIME LICENSE FOR USING BAC NET PROTOCOL ON CP IS NECESSARY. ANNOUNCEMENT LIMITATION OF SALES CHANNELS OF CP343-1 BACNET: SALES WIL

Артикул: 6FL4343-1CX10-0XE0
Производитель: Siemens


Наименование продукта
PLEASE NOTE: SALES WILL BE RESTRICTED AS OF APR.30TH 2012 HTTP://SUPPORT.AUTOMATION.SIEME NS.COM/WW/VIEW/EN/58567948 SIEMENS BUILDING TECHNOLOGIES COMMUNICATIONS PROCESSOR CP 343-1 BACNET FOR CONNECTION OF SIMATIC S7-300 TO BACNET. ADDITIONAL RUNTIME LICENSE REQUIRED FOR USE OF BAC NET PROTOCOL ON CP
Жизненный цикл продукта
Разрешение на поставку Постепенное снятие продукта с производства Снятие продукта с производства Окончательное снятие продукта с производства
2010-02-22
    Версия от 2012-03-10
 
SIEMENS BUILDING TECHNOLOGIES COMMUNICATIONS PROCESSOR CP343-1 BACNET FOR CONNECTING SIMATIC S7-300 TO BACNET. ADDITIONAL RUNTIME LICENSE FOR USING BAC NET PROTOCOL ON CP IS NECESSARY. ANNOUNCEMENT LIMITATION OF SALES CHANNELS OF CP343-1 BACNET: SALES WILL BE LIMITED AS OF APRIL 30TH 2012 DETAILED INFORMATION SEE HTTP://SUPPORT.AUTOMATION.SIEME NS.COM/WW/VIEW/DE/32989864 NECESSARY TO SEE CATALOG!
Transmission rate  
Transfer rate / at the interface 1 10 100 Mbit/s
Interfaces  
Number of electrical connections  
  • at interface 1 / in accordance with Industrial Ethernet
1
  • for power supply
1
Supply voltage, current consumption, power loss  
Type of voltage / of supply voltage DC
Supply voltage  
  • 1 / from backplane bus
5 V
  • external
24 V
Relative positive tolerance / at 24 V / with DC 20 %
Relative negative tolerance / at 24 V / with DC 15 %
Consumed current  
  • from backplane bus / at 5 V / for DC / [nicht versorgt - typisch]
0.2 A
  • [nicht versorgt - aus externer Versorgungsspannung] / [nicht versorgt - bei 24 V] / [nicht versorgt - bei DC]
 
  • maximum
0.2 A
Resistive loss 5.8 W
Permitted ambient conditions  
Ambient temperature  
  • during operating
0 60 °C
  • during storage
-40 +70 °C
  • during transport
-40 +70 °C
Relative humidity / at 25 °C / without condensation / during operating / maximum 95 %
Protection class IP IP20
Design, dimensions and weight  
Width 40 mm
Height 125 mm
Depth 120 mm
Net weight 0.22 kg
Product properties, functions, components / general  
Number of modules  
  • per CPU / maximum
1
Performance data / open communication  
Number of possible connections / for open communication / by means of SEND/RECEIVE blocks / maximum 8
Data volume  
  • as user data per TCP connection / for open communication / by means of SEND/RECEIVE blocks / maximum
8 Kibyte
  • as user data per UDP connection / for open IE communication / by means of SEND/RECEIVE blocks / maximum
2 Kibyte
Number of Multicast stations 8
Performance data / S7 communication  
Number of possible connections / [nicht versorgt - f?r S7-Kommunikation]  
  • [nicht versorgt - maximal]
4
  • with PG connections / maximum
2
  • with PG/OP connections / maximum
2
Performance data / multi-protocol mode  
Number of active connections / [nicht versorgt - bei Multiprotokollbetrieb] 12
Performance data / BACnet  
Protocol / is supported / BACnet/IP Yes
Product function  
  • BACnet device type AAC (Advanced Application Controller)
Yes
  • peer-to-peer between BACnet automation stations
Yes
  • BBMD (BACnet Broadcast Management Device)
Yes
Number of BACnet I/O objects / maximum 800
Total number of BACnet objects / maximum 1500
Memory capacity / [nicht versorgt - des Arbeitsspeichers der S7-CPU] / [nicht versorgt - erforderlich] 4 Kibyte
Product functions / management, configuration  
Product function / MIB support Yes
Protocol / is supported  
  • SNMP v1
Yes
  • DCP
Yes
  • LLDP
Yes
Product functions / Diagnosis  
Product function / Web-based diagnostics No
Product functions / switch  
Product feature / switch Yes
Product function  
  • switch-managed
No
  • Configuration with STEP 7
Yes
Product functions / Time  
Product function  
  • SICLOCK support
Yes
  • pass on time synchronization
Yes
Protocol / is supported / NTP Yes
 
letzte ?nderung:
Feb 28, 2012

Назад в раздел