SIPLUS S7-1200 CPU 1214C AC/DC/RLY -25 ... +55 DEGREES C WITH CONFORMAL COATING SIGNAL BOARD USEABLE BASED ON 6ES7214-1BE30-0XB0 . COMPACT CPU, AC/DC/RELAY, ONBOARD I/O: 14 DI 24V DC; 10 DO RELAY 0.5A; 2 AI 0 - 10V DC, POWER SUPPLY: AC 85 - 264 V AC @ 47

Артикул: 6AG1214-1BE30-5XB0
Производитель: Siemens


Наименование продукта
SIPLUS S7-1200 CPU 1214C AC/DC/RLY -25 ... +55 DEGREES C WITH CONFORMAL COATING SIGNAL BOARD USEABLE BASED ON 6ES7214-1BE30-0XB0 . COMPACT CPU, AC/DC/RELAY, ONBOARD I/O: 14 DI 24V DC; 10 DO RELAY 0.5A; 2 AI 0 - 10V DC, POWER SUPPLY: AC 85 - 264 V AC @ 47 - 63 HZ, PROGRAM/DATA MEMORY: 50 KB
Жизненный цикл продукта
Разрешение на поставку Постепенное снятие продукта с производства Снятие продукта с производства Окончательное снятие продукта с производства
2010-01-06
    Версия от 2012-02-19
 
SIPLUS S7-1200 CPU 1214C AC/DC/RLY -25 ... +55 DEGREES C WITH CONFORMAL COATING SIGNAL BOARD USEABLE BASED ON 6ES7214-1BE30-0XB0 . COMPACT CPU, AC/DC/RELAY, ONBOARD I/O: 14 DI 24V DC; 10 DO RELAY 0.5A; 2 AI 0 - 10V DC, POWER SUPPLY: AC 85 - 264 V AC @ 47 - 63 HZ, PROGRAM/DATA MEMORY: 50 KB
General information
Engineering with
Programming package STEP 7 Basic V10.5
Display
integrated No
Supply voltage
120 V AC Yes
230 V AC Yes
permissible range, lower limit (AC) 85 V
permissible range, upper limit (AC) 264 V
Line frequency
Frequency of the supply voltage 47 Hz
Frequency of the supply voltage 63 Hz
Load voltage L+
Rated value (DC) 24 V
permissible range, lower limit (DC) 5 V
permissible range, upper limit (DC) 250 V
Input current
Current consumption (rated value) 100 mA @ 120 VAC 50 mA @ 240 VAC
Current consumption, max. 300 mA @ 120 VAC 150 mA @ 240 VAC
Inrush current, max. 20 A; at 264 V
Encoder supply
24 V encoder supply
24 V Permissible range: 20.4 to 28.8 V
Output current
Current output to backplane bus (DC 5 V), max. 1600 mA; 5 VDC max. for SM and CM
Power losses
Power loss, typ. 14 W
Memory
Usable memory for user data 50 kbyte
Work memory
integrated 50 kbyte
expandable No
Load memory
integrated 2 Mbyte
expandable, max. 24 Mbyte; with SIEMENS Memory Card
Backup
present Yes; Entire project maintenance-free in the integral EEPROM
without battery Yes
CPU processing times
for bit operations, min. 0.1 µs; / Operation
for word operations, min. 12 µs; / Operation
for floating point arithmetic, min. 18 µs; / Operation
CPU-blocks
Number of blocks (total) DBs, FCs, FBs, counters and timers. The maximum number of addressable blocks ranges from 1 to 65535. There is no restriction, the entire working memory can be used
OB
Number, max. Limited only by RAM for code
Data areas and their retentivity
retentive data area in total (incl. times, counters, flags), max. 2048 byte
Flag
Number, max. 8 kbyte; Size of bit memory address area
Address area
I/O address area
I/O address area, overall 1024 bytes for inputs / 1024 bytes for outputs
Inputs 1024 byte
Outputs 1024 byte
Process image
Inputs, adjustable 1 kbyte
Outputs, adjustable 1 kbyte
Hardware configuration
Number of modules per system, max. 3 comm. modules, 1 signal board, 8 signal modules
Time of day
Clock
Hardware clock (real-time clock) Yes
Deviation per day, max. +/- 60 s/month at 25 °C
Backup time 240 h; Typical
Digital inputs
Number/binary inputs 14; integrated
of which, inputs usable for technological functions 6; HSC (High Speed Counting)
integrated channels (DI) 14
m/p-reading Yes
Input voltage
Rated value, DC 24 V
for signal "0" 5 V DC at 1 mA.
for signal "1" 15 VDC at 2.5 mA.
Input current
for signal "1", typ. 1 mA
Input delay (for rated value of input voltage)
for standard inputs
Parameterizable 0.2, 0.4, 0.8, 1.6, 3.2, 6.4, and 12.8 ms, selectable in groups of four
at "0" to "1", min. 0.2 ms
at "0" to "1", max. 12.8 ms
for interrupt inputs
Parameterizable Yes
for counter/technological functions
Parameterizable Single phase: 3 @ 100 kHz & 3 @ 30 kHz differential: 3 @ 80 kHz & 3 @ 30 kHz
Cable length
Cable length, shielded, max. 500 m; 50 m for technological functions
Cable length unshielded, max. 300 m; For technological functions: No
Digital outputs
Number/binary outputs 10; Relay
integrated channels (DO) 10
Functionality/short-circuit strength No; to be provided externally
Switching capacity of the outputs
with resistive load, max. 2 A
on lamp load, max. 30 W DC; 200 W AC
Output delay with resistive load
0 to "1", max. 10 ms; max.
1 to "0", max. 10 ms; max.
Switching frequency
of the pulse outputs, with resistive load, max. 1 Hz
Relay outputs
Number of relay outputs 10
Number of operating cycles, max. mechanically 10 million, at rated load voltage 100,000
Cable length
Cable length, shielded, max. 500 m
Cable length unshielded, max. 150 m
Analog inputs
Integrated channels (AI) 2
Number of analog inputs 2
Input ranges
Voltage Yes
Input ranges (rated values), voltages
0 to +10 V Yes
Input resistance (0 to 10 V) ?100k ohms
Cable length
Cable length, shielded, max. 100 m; Назад в раздел