| DECOUPLING MODULE (DCM) FOR DECOUPLING THE CONTROL BUS OF HEATING SYSTEM CONTROL SIPLUS HCS300I. |
Product brand name | | SIPLUS |
product designation | | Heating control HCS300I |
Design of the product | | Decoupling module |
|
General technical data: |
Item designation / according to DIN 40719 extendable after IEC 204-2 / according to IEC 750 | | F |
Item designation / according to DIN EN 61346-2 | | F |
Number of status displays | | 1 |
Type of display / as status display by LED | | Continuously illuminated: ready |
|
Communication: |
Design of the interface | | system interface |
|
Supply voltage: |
Design of the power supply | | Supply via base unit |
|
Ambient conditions: | | |
Protection class IP | | IP20 |
Resistance against shock / according to IEC 60068-2-27 | | 15g / 11 ms |
Resistance against vibration / according to IEC 60068-2-6 | | 5 ... 500 Hz, 3.5 mm ampl., 1g, 10 cycles, 1 octave/min |
Conductor-bound parasitic coupling BURST / according to IEC 61000-4-4 | | 2 kV (power ports) / 1 kV (signal ports) |
Conductor-bound parasitic coupling SURGE / according to IEC 61000-4-5 | | on power supply lines: 1 kV symmetric, 2 kV asymmetric; on signal lines > 30 m unshielded: 1 kV symmetric, 2 kV asymmetric, > 30 m shielded: 2 kV asymmetric |
Conducted interference as high-frequency radiation / according to IEC 61000-4-6 | | 10 V |
Conductor-bound parasitic coupling conductor-earth SURGE / according to IEC 61000-4-5 | | 2 kV |
Conductor-bound parasitic coupling conductor-conductor SURGE / according to IEC 61000-4-5 | | 1 kV |
Electrostatic discharge / according to IEC 61000-4-2 | | 6 kV contact discharge / 8 kV air discharge |
Field-bound parasitic coupling / according to IEC 61000-4-3 | | 10 V/m |
EMC emitted interference | | IEC61131: Class A; conducted and radiated: DIN EN 55011/CISPR11 (corresponds to degree of severity A) |
Installation altitude / at a height over sea level / maximum | m | 2,000 |
Ambient temperature | | |
| °C | -40… 80 |
| °C | -25… 60 |
| °C | -40… 80 |
Air pressure | | |
| hPa | 795… 1,080 |
| hPa | 660… 1,080 |
|
Connections: |
|
terminals |
Design of the electrical connection / for auxiliary and control current circuit | | screw-type terminals |
Product function / removable terminal for auxiliary and control circuit | | Yes |
Type of the connectable conductor cross-section | | |
| | |
| | 1x (0.5 ... 4 mm2), 2x (0.5 ... 2.5 mm2) |
- for AWG conductors / for auxiliary contacts
| | 1x (0.5 ... 2.5 mm2), 2x (0.5 ... 1.5 mm2) |
|
Installation/mounting/dimensions: |
Built in orientation | | any |
Type of mounting | | snap-on fastening on 35 mm standard mounting rail or screw fastening using an additional push-in lug |
Width | mm | 22.5 |
Height | mm | 92 |
Depth | mm | 115 |
|
Certificates/approvals: |
Verification of suitability | | CE / C-TICK |
|
|
Further information: |
Information- and Downloadcenter (Catalogs, Brochures,…) http://www.automation.siemens.com/mcms/topics/en/siplus/industrial-heating-control/Pages/home.aspx |
Industry Mall (Online ordering system) http://www.siemens.com/industrial-controls/mall |
CAx-Online-Generator http://www.siemens.com/cax |
Service&Support (Manuals, Certificates, Characteristics, FAQs,...) http://support.automation.siemens.com/WW/view/en/6BK1700-4BA40-0AA0/all |
Image database (product images, 2D dimension drawings, 3D models, device circuit diagrams, ...) http://www.automation.siemens.com/bilddb/cax_en.aspx?mlfb=6BK1700-4BA40-0AA0 |
|
|
| |
|
last change: | Aug 25, 2011 |