SINVERT PVS351 UL INVERTER FOR PV, GRID CONNECT. LV, UL 60HZ, 3P, STANDARD MPP, UMAX 600VDC, 3 DC-INPUTS, NEMA1, AIR COOLING, PV FIELD GROUNDING POS. POLE, VOLTAGE MEASUREMENT DC INPUTS, SYMMETRY MONITORING, CABINET HEATING

Артикул: 6AG3101-4PD00-0AA0-ZD30D70M10S10
Производитель: Siemens


Наименование продукта
SINVERT PVS351 UL INVERTER FOR PV, GRID CONNECT. LV, UL 60HZ, 3P, STANDARD MPP, UMAX 600VDC, 3 DC-INPUTS, NEMA1, AIR COOLING, PV FIELD GROUNDING POS. POLE, VOLTAGE MEASUREMENT DC INPUTS, SYMMETRY MONITORING, CABINET HEATING
Жизненный цикл продукта
Разрешение на поставку Постепенное снятие продукта с производства Снятие продукта с производства Окончательное снятие продукта с производства
2011-12-05
SINVERT PVS351 UL INVERTER FOR PV, GRID CONNECT. LV, UL 60HZ, 3P, STANDARD MPP, UMAX 600VDC, 3 DC-INPUTS, NEMA1, AIR COOLING, PV FIELD GROUNDING POS. POLE, VOLTAGE MEASUREMENT DC INPUTS, SYMMETRY MONITORING, CABINET HEATING
 
General technical data:
product brand name   SINVERT
Product-type designation   SINVERT PVS351 UL
product designation   photovoltaic inverter
Output class for PV inverters   350
Efficiency / maximum possible % 97.2
Efficiency    
  • according to CEC
  96.6
Design of PV inverter unit   single device
Number of PV inverter sub-units   1
Type of installation   indoor installation
Protection class IP   IP21
Operating resource protection class   I
Design of the interface / for communication   Ethernet
A-rated sound power level / maximum dB 78
Design of the display   LCD-TFT
National language / at the indicator of the display / selectable   English
Connection method for PV inverters   with transformer
 
Output (AC side):
   
Phase number   3
Output voltage / on the AC side / for infeed operation / nominal value V 480
Output voltage / on the AC side    
  • for infeed operation
V 422 528
Power factor / at nominal value of active power supplied / nominal value   1
Active power supplied / on the AC side    
  • in permanent operation / nominal value
W 350,000
  • maximum
W 385,000
Current supplied / on the AC side / maximum A 424
Line frequency / suitable for infeed operation / nominal value Hz 60
Line frequency    
  • suitable for infeed operation
Hz 59.3 60.5
Relative residual ripple / of AC current / at nominal value of the AC active power / on unloaded line / maximum % 2.5
Grounding concept / on the AC side   TN-C
Design of the overvoltage protection / on the AC side   type 2
 
Input (DC side):
   
MPP voltage V 330 480
Consumed active power / on the DC side / nominal value W 364,000
Input voltage / on the DC side    
  • for the start of the infeed operation
V 330
  • for possible infeed operation
V 330 600
  • nominal value
V 400
  • maximum permissible
V 600
Number of inputs / on the DC side   3
Input current / per DC input / maximum A 368
Total power used / on the DC side / maximum A 1,103
Overcurrent strength / per DC input / nominal value A 400
Design of the overvoltage protection / on the DC side   type 2
 
External auxiliary voltage supply:
   
Auxiliary voltage / nominal value V 480
Auxiliary voltage frequency / nominal value Hz 60
 
Ambient conditions:
   
Installation altitude m 0 2,000
  • for nominal active power
m 0 1,000
Incoming air temperature / at nominal value of active power supplied / maximum °C 30
Ambient temperature    
  • during operating
°C 0 50
  • during storage
/ °C 70
  • during transport
/ °C 70
Relative humidity / without condensation    
  • during operating phase
% 0 95
Relative humidity    
  • during storage
% 95
  • during transport
% 95
Climatic class   3K3
Type of cooling   forced-air cooling via fan
Cooling air flow m³/h 5,300
Nature of the ventilation   air intake cabinet front/air outlet cabinet top
 
Mechanical data:
   
Built in orientation   vertical
Width / of PV inverter subunits mm 2,804
Height / of PV inverter subunits mm 2,200
Depth / of PV inverter subunits mm 745
Weight / of the single device kg 3,256
Type of mounting   Floor mounting installation
 
Certificates/approvals:
Verification of suitability / CE mark   Yes
Verification of suitability   UL / CSA
Product quality    
  • for security
   
  • UL 1741
  Yes
  • for harmonics
   
  • UL 1741
  Yes
 
Connections:
   
Design of the electrical connection / at the DC input   ring cable lug
Design of the thread / of the connection screw / at DC input   M12
Tightening torque    
  • at DC input
N·m 70 70
Design of the electrical connection / at AC output   ring cable lug
Design

Назад в раздел