SINVERT PVM17 INVERTER FOR PV, GRID CONNECT. LV, IEC 50/60HZ, 3P, 400VAC, STANDARD MPP, UMAX 1000VDC, 4 DC-INPUTS, IP65, AIR COOLING, SINVERT PVM WARRANTY - 5 YEARS

Артикул: 6AG3120-3JJ02-0AC0
Производитель: Siemens


Наименование продукта
SINVERT PVM17 INVERTER FOR PV, GRID CONNECT. LV, IEC 50/60HZ, 3P, 400VAC, STANDARD MPP, UMAX 1000VDC, 4 DC-INPUTS, IP65, AIR COOLING, SINVERT PVM WARRANTY - 5 YEARS
Жизненный цикл продукта
Разрешение на поставку Постепенное снятие продукта с производства Снятие продукта с производства Окончательное снятие продукта с производства
2009-11-23 2010-08-09 2010-08-12
SINVERT PVM17 INVERTER FOR PV, GRID CONNECT. LV, IEC 50/60HZ, 3P, 400VAC, STANDARD MPP, UMAX 1000VDC, 4 DC-INPUTS, IP65, AIR COOLING, SINVERT PVM WARRANTY - 5 YEARS
 
General technical data:
product brand name   SINVERT
Product-type designation   SINVERT PVM17
product designation   photovoltaic inverter
Output class for PV inverters   17
Design of PV inverter unit   single device
Number of PV inverter sub-units   1
Type of installation   indoor installation / outdoor installation
Protection class IP   IP65
Operating resource protection class   I
Installation altitude / at rated value of power / at a height above sea level / maximum m 2,000
Incoming air temperature / at nominal value of active power supplied / maximum °C 45
Ambient temperature    
  • during operating
°C -25 +55
  • during storage
°C -25 +70
  • during transport
°C -25 +70
Relative humidity / without condensation    
  • during operating phase
% 4 100
Climatic class   4K4H
Type of cooling   natural convection
A-rated sound power level / maximum dB 45
RAL color number   RAL 7035
Design of the display   graphical (with backlight)
Horizontal image resolution   128
Vertical screen resolution   64
Number of colors / of the display   2
Design of the display / touchscreen   No
Design of the control elements   8 membrane keys
National language / at the indicator of the display / selectable   English, French, German, Italian, Spanish, Czech
Design of the interface / for communication   Ethernet, RS485
Product feature / functional earth   No
Connection method for PV inverters   without transformer
Product function / galvanic isolation   No
Product component    
  • input for radiation sensor
  Yes
  • relay output for fault message
  Yes
 
Inputs:
   
MPP voltage V 525 850
Input voltage / on the DC side    
  • for the start of the infeed operation
V 350
  • for possible infeed operation
V 350 950
  • nominal value
V 600
  • maximum permissible
V 1,000
Consumed active power / on the DC side / nominal value W 16,800
Total power used / on the DC side / maximum A 32
Number of inputs / on the DC side   4
Input current / per DC input / maximum A 25
Product component / on the DC side    
  • circuit breaker
  Yes
  • overvoltage protection
  Yes
Design of the overvoltage protection / on the DC side   type 3
 
Outputs:
   
Phase number   3
Output voltage / on the AC side / for infeed operation / nominal value V 400
Output voltage / on the AC side    
  • for infeed operation
V 320 480
Line frequency    
  • 1
   
  • for infeed operation / nominal value
Hz 50
  • 2
   
  • for infeed operation / nominal value
Hz 60
Active power supplied / on the AC side    
  • in permanent operation / nominal value
W 16,500
  • maximum
W 16,500
Current supplied / on the AC side / maximum A 25
Power factor / at nominal value of active power supplied / nominal value   1
Power factor inductive / minimum   0.9
Power factor capacitive / minimum   0.9
Relative residual ripple / of AC current / at nominal value of the AC active power / on unloaded line / maximum % 2.5
Grounding concept / on the AC side   TN-S
Design of protection / on the AC side / required   32 (type B)
Product component / on the AC side / overvoltage protection   Yes
Design of the overvoltage protection / on the AC side   type 3
 
Efficiency / heat loss:
   
Efficiency / maximum possible % 98
Euro efficiency % 97.7
Apparent power consumed    
  • in night-time operating mode
V·A 0.5
  • in standby operating mode
V·A 0.5
Input power / on the DC side / for possible infeed operation / minimum W 60
 
Connections:
   
Design of the electrical connection    
  • at the DC input
  MC4
  • at AC output
  connector
Conductor cross-section that can be connected / at the AC- output / stranded wire    
  • with conductor end processing
mm² 4 6
Lockable cable diameter  

Назад в раздел