SINVERT PVM CONTROL BOX

Артикул: 6AG3600-3AB10-0AA0
Производитель: Siemens


Наименование продукта
SINVERT PVM CONTROL BOX
Жизненный цикл продукта
Разрешение на поставку Постепенное снятие продукта с производства Снятие продукта с производства Окончательное снятие продукта с производства
2010-09-16
SINVERT PVM CONTROL BOX
 
General technical data:
product brand name   SINVERT
Product-type designation   SINVERT PVM ControlBox
product designation   Photovoltaik park controller
Type of installation   indoor installation
Protection class IP   IP20
Installation altitude / at a height over sea level / maximum m 2,000
Ambient temperature    
  • during operating
°C -25 +55
  • during storage
°C -25 +55
  • during transport
°C -25 +55
Relative humidity / without condensation    
  • during operating phase
% 5 99
Climatic class / according to EN 60721   3K3
Type of cooling   natural convection
Design of the interface / for communication   Ethernet, RS485
 
Supply voltage:
   
Type of voltage / of the supply voltage / for power supply   AC
Supply voltage    
  • at 50 Hz / for AC
   
  • rated value
V 115 230
  • at 60 Hz / for AC
   
  • rated value
V 115 230
Type of voltage / of the outputs   DC
Output voltage / for DC V 24
Output voltage    
  • for DC
V 21 27
Active power loss / total / typical W 18
Cable length m 1.5
Type of voltage / of the supply voltage / for basic unit   DC
Supply voltage / for DC V 24
  • rated value
V 21 27
Active power loss / at 24 V / for DC W 12
Consumed current / for rated value of supply voltage mA 500
 
Control circuit:
   
Number of digital inputs   4
Design of the electrical connection / at the digital inputs   X17 terminal strip
Galvanic isolation / at the digital inputs / between the channels and voltage supply of the electronic   Yes
Signal voltage    
  • for signal <0> / for DC / nominal value
V 0
  • for signal <0>
   
  • for DC
V -1 +5
  • for signal <1> / for DC / nominal value
V 24
  • for signal <1>
   
  • for DC
V 13 33
 
Communication:
   
Input current / at the digital input / for signal <1> / minimum mA 8
Number of interfaces    
  • according to Ethernet
  1
  • according to RS 485
  2
Design of the electrical connection    
  • the Industrial Ethernet Interface
  X13 RJ45-bushing
  • the RS 485-interface
  X77, X15 terminal strip (at X15 ext. overvoltage protection EN type D1 is required)
 
Installation/mounting/dimensions:
Built in orientation / recommended   vertical
Type of mounting   only with wall bracket (accessories kit)
Width mm 267
Depth mm 103
Height mm 267
Weight kg 1.6
 
Certificates/approvals:
Verification of suitability   CE
Product quality / EMC emitted interference industry according to IEC 61000-6-4   Yes
Product quality / EMC interference resistance industry according to IEC 61000-6-2   Yes
Declaration of Conformity
 
 
Further information:
Information- and Downloadcenter (Catalogs, Brochures,…)
http://www.siemens.com/sinvert-infocenter
Industry Mall (Online ordering system)
http://www.siemens.com/sinvert-mall
CAx-Online-Generator
http://www.siemens.com/cax
Service&Support (Manuals, Certificates, Characteristics, FAQs,...)
http://support.automation.siemens.com/WW/view/en/6AG3600-3AB10-0AA0/all
Image database (product images, 2D dimension drawings, 3D models, device circuit diagrams, ...)
http://www.automation.siemens.com/bilddb/cax_en.aspx?mlfb=6AG3600-3AB10-0AA0
 
 
 