6ES7 138-4DD01-0AB0 |
Supply voltages |
|
Load voltage L+ |
|
|
24 V; From power module |
|
Yes |
Current consumption |
|
from load voltage L+ (without load), max. |
40 mA |
from backplane bus 3.3 V DC, max. |
10 mA |
Power losses |
|
Power loss, typ. |
1.8 W |
Digital inputs |
|
Number of digital inputs |
2 |
Input characteristic curve acc. to IEC 1131, Type 2 |
Yes |
Input voltage |
|
|
24 V |
|
-30 to +5 V |
|
11 to 30 V |
Input current |
|
|
9 mA |
Input delay (for rated value of input voltage) |
|
|
20 kHz |
|
100 µs |
Cable length |
|
|
100 m |
Digital outputs |
|
Number of digital outputs |
2 |
Short-circuit protection |
Yes |
|
10 A |
Limitation of inductive shutdown voltage to |
L+ (-50 to -65 V) |
Lamp load, max. |
10 W |
Accuracy of pulse duration |
+/- (time period x 100 ppm), +/-100 µs with a load <= 50 ohms |
minimum pulse duration |
100 µs |
Controlling a digital input |
Yes |
Output voltage |
|
|
L+ (-1 V) |
Output current |
|
|
2 A |
|
7 mA |
|
2 A |
|
0.5 mA |
Output delay with resistive load |
|
|
100 µs |
|
200 µs |
Switching frequency |
|
|
5 kHz |
|
2 Hz |
|
10 Hz |
Cable length |
|
|
1 000 m |
|
600 m |
Encoder supply |
|
Output voltage |
L+ (-0.8 V) |
Output current, rated value |
500 mA |
Short-circuit protection |
Yes |
Encoder |
|
Connectable encoders |
|
|
Yes |
|
2 mA |
Pulse generator |
|
Number of channels |
2; 1 digital input and 1 digital output per channel |
Interrupts/diagnostics/status information |
|
Diagnostics indication LED |
|
|
Yes |
|
Yes |
|
Yes |
Isolation |
|
Isolation checked with |
500 VDC |
Galvanic isolation |
|
Galvanic isolation digital inputs |
|
|
No |
|
Yes |
Galvanic isolation digital outputs |
|
|
No |
|
Yes |
Permissible potential difference |
|
between different circuits |
75 VDC / 60 VAC |
Dimensions and weight |
|
Dimensions |
|
|
15 mm |
|
81 mm |
|
52 mm |
Weight |
|
|
40 g |