6ES7 131-1BH01-0XB0 |
6ES7 131-1BL01-0XB0 |
Supply voltages |
|
|
Rated value |
|
|
|
Yes |
Yes |
|
Yes |
Yes |
Hardware configuration |
|
|
Rack |
|
|
|
TB 16L |
TB 32L |
Connection method |
|
|
Inputs/outputs |
Screw-type and spring-loaded terminals, permanent wiring; standard: 2-wire connection, optional: 3 and 4-wire connection |
Screw-type and spring-loaded terminals, permanent wiring; standard: 2-wire connection, optional: 3 and 4-wire connection |
PROFIBUS DP |
|
|
Transmission rate, max. |
1.5 Mbit/s |
1.5 Mbit/s |
Direct data exchange (slave-to-slave communication) |
Yes; Transmitter (for digital outputs and hybrid modules ET 200L: not for L-SC or IM-SC) |
Yes; Transmitter (for digital outputs and hybrid modules ET 200L: not for L-SC or IM-SC) |
Digital inputs |
|
|
Number of digital inputs |
16 |
32 |
Input voltage |
|
|
|
24 V |
24 V |
|
-30 to +5 V |
-30 to +5 V |
|
13 to 30 V |
13 to 30 V |
Input current |
|
|
|
5 mA |
5 mA |
Input delay (for rated value of input voltage) |
|
|
|
|
|
|
2 ms |
2 ms |
|
4.5 ms |
4.5 ms |
Cable length |
|
|
|
1 000 m |
1 000 m |
Galvanic isolation |
|
|
between PROFIBUS DP and all other circuit components |
Yes |
Yes |
Galvanic isolation digital inputs |
|
|
|
No |
No |
|
Yes |
Yes |
Environmental requirements |
|
|
Operating temperature |
|
|
|
0 °C |
0 °C |
|
60 °C; 40°C for other mountings |
60 °C; 40°C for other mountings |
Air pressure |
|
|
|
795 hPa |
795 hPa |
|
1 080 hPa |
1 080 hPa |
Relative humidity |
|
|
|
5 % |
5 % |
|
95 %; RH class 2 in accordance with IEC 1131-2 |
95 %; RH class 2 in accordance with IEC 1131-2 |
Vibrations |
|
|
|
Yes; IEC 68, Part 2-6; 10 to 57 Hz; (constant amplitude 0.075 mm); 57 to 150 Hz; (constant acceleration 1 g) |
Yes; IEC 68, Part 2-6; 10 to 57 Hz; (constant amplitude 0.075 mm); 57 to 150 Hz; (constant acceleration 1 g) |
Shock test |
|
|
|
Yes; IEC 68, Part 2-27; half-sine, 15 g, 11 ms |
Yes; IEC 68, Part 2-27; half-sine, 15 g, 11 ms |
Degree of protection |
|
|
IP20 |
Yes |
Yes |
Dimensions and weight |
|
|
Dimensions |
|
|
|
145 mm |
145 mm |
|
60 mm |
60 mm |
|
60.5 mm |
60.5 mm |
|
6ES7 132-1BH00-0XB0 |
6ES7 132-1BL00-0XB0 |
Supply voltages |
|
|
Rated value |
|
|
|
Yes |
Yes |
|
Yes |
Yes |
Mains buffering, min. |
20 ms |
20 ms |
Load voltage 2L+ |
|
|
|
24 V; 1L+, 2L+, 3L+ |
24 V; 1L+, 2L+, 3L+ |
Current consumption |
|
|
from load voltage L1 (without load), max. |
50 mA; per load group (L1+ or L2+ / L3+) |
100 mA; per load group (L1+ or L2+ / L3+) |
from supply voltage L+, max. |
70 mA; L4+ / L5+ |
70 mA; L4+ / L5+ |
Power losses |
|
|
Power loss, typ. |
5 W |
7 W |
Hardware configuration |
|
|
Rack |
|
|
|
TB 16L |
TB 32L |
Communication functions |
|
|
Bus protocol/transmission protocol |
PROFIBUS DP |
PROFIBUS DP |
Connection method |
|
|
Inputs/outputs |
Screw-type and spring-loaded terminals, permanent wiring; standard: 2-wire connection, optional: 3 and 4-wire connection |
Screw-type and spring-loaded terminals, permanent wiring; standard: 2-wire connection, optional: 3 and 4-wire connection |
PROFIBUS DP |
|
|
Transmission rate, max. |
1.5 Mbit/s |
1.5 Mbit/s |
SYNC capability |
Yes |
Yes |
Direct data exchange (slave-to-slave communication) |
Yes; Transmitter (for digital outputs and hybrid modules ET 200L: not for L-SC or IM-SC) |
Yes; Transmitter (for digital outputs and hybrid modules ET 200L: not for L-SC or IM-SC) |
Digital outputs |
|
|
Number of digital outputs |
16 |
32 |
Short-circuit protection |
Yes; Electronic |
Yes; Electronic |
Response threshold, typ. |
0.7 A |
0.7 A |
Limitation of inductive shutdown voltage to |
typ. (L1+ or L2+ / L3+) -55 V |
typ. (L1+ or L2+ / L3+) -55 V |
Lamp load, max. |
5 W |
5 W |
Controlling a digital input |
Yes |
Yes |
Output voltage |
|
|
|
24 V |
24 V |
|
Ua - 3 V |
Ua - 3 V |
Output current |
|
|
|
0.5 A |
0.5 A |
|
0.5 A |
0.5 A |
|
1 mA |
1 mA |
Output delay with resistive load |
|
|
|
50 ms |
50 ms |
|
200 ms |
200 ms |
Parallel switching of 2 outputs |
|
|
|
No |
No |
|
Yes; only outputs of the same group |
Yes; only outputs of the same group |
Switching frequency |
|
|
|
100 Hz |
100 Hz |
|
0.5 Hz |
0.5 Hz |
|
8 Hz |
8 Hz |
Aggregate current of outputs (per group) |
|
|
|
|
|
|
2 A |
2 A |
|
4 A |
4 A |
|
3 000 mA |
3 000 mA |
|
2 000 mA |
2 000 mA |
Load resistance range |
|
|
|
41 Ω |
41 Ω |
|
28 000 Ω |
28 000 Ω |
Cable length |
|
|
|
1 000 m |
1 000 m |
|
600 m |
600 m |
Interrupts/diagnostics/status information |
|
|
Alarms |
|
|
|
No |
No |
Diagnoses |
|
|
|
Yes |
Yes |
Diagnostics indication LED |
|
|
|
Yes |
Yes |
|
Yes |
Yes |
|
Yes |
Yes |
|
Yes |
Yes |
Isolation |
|
|
Isolation checked with |
500 VDC |
500 VDC |
Galvanic isolation |
|
|
between PROFIBUS DP and all other circuit components |
Yes |
Yes |
Galvanic isolation digital outputs |
|
|
|
No |
No |
|
Yes; Optocoupler |
Yes |
Environmental requirements |
|
|
Operating temperature |
|
|
|
0 °C |
0 °C |
|
60 °C; 40°C for other mountings |
60 °C; 40°C for other mountings |
Air pressure |
|
|
|
795 hPa |
795 hPa |
|
1 080 hPa |
1 080 hPa |
Relative humidity |
|
|
|
5 % |
5 % |
|
95 %; RH class 2 in accordance with IEC 1131-2 |
95 %; RH class 2 in accordance with IEC 1131-2 |
Vibrations |
|
|
|
Yes; IEC 68, Part 2-6; 10 to 57 Hz; (constant amplitude 0.075 mm); 57 to 150 Hz; (constant acceleration 1 g) |
Yes; IEC 68, Part 2-6; 10 to 57 Hz; (constant amplitude 0.075 mm); 57 to 150 Hz; (constant acceleration 1 g) |
Shock test |
|
|
|
Yes; IEC 68, Part 2-27; half-sine, 15 g, 11 ms |
Yes; IEC 68, Part 2-27; half-sine, 15 g, 11 ms |
Degree of protection |
|
|
IP20 |
Yes |
Yes |
General information |
|
|
Vendor identification (VendorID) |
0016h |
0011h |
Dimensions and weight |
|
|
Dimensions |
|
|
|
145 mm |
145 mm |
|
60 mm |
60 mm |
|
60.5 mm |
60.5 mm |
Weight |
|
|
|
130 g |
150 g |
|
6ES7 133-1BL01-0XB0 |
Supply voltages |
|
Rated value |
|
|
Yes |
|
Yes |
Hardware configuration |
|
Rack |
|
|
TB 32L |
Connection method |
|
Inputs/outputs |
Screw-type and spring-loaded terminals, permanent wiring; standard: 2-wire connection, optional: 3 and 4-wire connection |
PROFIBUS DP |
|
Transmission rate, max. |
1.5 Mbit/s |
Direct data exchange (slave-to-slave communication) |
Yes; Transmitter (for digital outputs and hybrid modules ET 200L: not for L-SC or IM-SC) |
Digital inputs |
|
Number of digital inputs |
16 |
Input voltage |
|
|
24 V |
|
-30 to +5 V |
|
13 to 30 V |
Input current |
|
|
5 mA |
Input delay (for rated value of input voltage) |
|
|
|
|
2 ms |
|
4.5 ms |
Cable length |
|
|
1 000 m |
Digital outputs |
|
Number of digital outputs |
16 |
Short-circuit protection |
Yes; Electronic |
Output voltage |
|
|
24 V |
|
Ua - 3 V |
Output current |
|
|
0.5 mA |
|
1 mA |
Switching frequency |
|
|
100 Hz |
|
0.5 Hz |
|
8 Hz |
Aggregate current of outputs (per group) |
|
|
4 A |
Cable length |
|
|
1 000 m |
Galvanic isolation |
|
between PROFIBUS DP and all other circuit components |
Yes |
Galvanic isolation digital inputs |
|
|
No |
|
Yes |
Environmental requirements |
|
Operating temperature |
|
|
0 °C |
|
60 °C; 40°C for other mountings |
Air pressure |
|
|
795 hPa |
|
1 080 hPa |
Relative humidity |
|
|
5 % |
|
95 %; RH class 2 in accordance with IEC 1131-2 |
Vibrations |
|
|
Yes; IEC 68, Part 2-6; 10 to 57 Hz; (constant amplitude 0.075 mm); 57 to 150 Hz; (constant acceleration 1 g) |
Shock test |
|
|
Yes; IEC 68, Part 2-27; half-sine, 15 g, 11 ms |
Degree of protection |
|
IP20 |
Yes |
Dimensions and weight |
|
Dimensions |
|
|
145 mm |
|
60 mm |
|
60.5 mm |
|
6ES7 193-1CH00-0XA0 |
6ES7 193-1CH10-0XA0 |
6ES7 193-1CH20-0XA0 |
6ES7 193-1CL00-0XA0 |
6ES7 193-1CL10-0XA0 |
Dimensions and weight |
|
|
|
|
|
Dimensions |
|
|
|
|
|
|
145 mm |
145 mm |
191 mm |
191 mm |
191 mm |
|
100 mm; Height with electronics block from top edge of DIN rail (with bus connector 6ES7 972-0CA30-0XA0): 82 mm |
100 mm; Height with electronics block from top edge of DIN rail (with bus connector 6ES7 972-0CA30-0XA0): 82 mm |
100 mm; Height with electronics block from top edge (with bus connector ): 98.5 mm |
100 mm; Height with electronics block from top edge of DIN rail (with bus connector 6ES7 972-0CA30-0XA0): 82 mm |
100 mm; Height with electronics block from top edge of DIN rail (with bus connector 6ES7 972-0CA30-0XA0): 82 mm |
|
40.5 mm |
40.5 mm |
40.5 mm |
40.5 mm |
40.5 mm |
Weight |
|
|
|
|
|
|
230 g |
230 g |
283 g |
350 g |
350 g |