6ES7 331-7TB00-0AB0

Supply voltages

 

Load voltage L+

 

  • Rated value (DC)

24 V

  • Reverse polarity protection

Yes

Power supply to the transmitters

 

  • present

Yes

  • Rated value (DC)

15 V; at 22 mA

  • short-circuit proof

Yes; approx. 30 mA

  • No-load voltage (DC)

29.6 V

Current consumption

 

from backplane bus 5 V DC, max.

100 mA

from supply voltage L+, max.

180 mA

Power losses

 

Power loss, typ.

4.5 W

Analog inputs

 

Number of analog inputs

2

Cable length, shielded, max.

400 m

  • Current

Yes

Input ranges (rated values), currents

 

  • 0 to 20 mA

Yes

  • Input resistance (0 to 20 mA)

50 Ω

  • 4 to 20 mA

Yes

  • Input resistance (4 to 20 mA)

50 Ω

Current input

 

  • permissible input current for current input (destruction limit), max.

40 mA

Analog value creation

 

Measurement principle

Sigma Delta

Integrations and conversion time/ resolution per channel

 

  • Resolution with overrange (bit including sign), max.

16 bit; 10 to 15 bits + sign

  • Integration time, parameterizable

Yes

  • Integration time, ms

2.5 / 16.67 / 20 / 100 ms

  • Basic conversion time, including integration time, ms

2.5 / 16.67 / 20 / 100 (1 channel enabled); 7.5 / 50 / 60 / 300 (2 channels enabled)

  • Interference voltage suppression for interference frequency f1 in Hz

10 / 50 / 60 / 400 Hz

Encoder

 

Connection of signal encoders

 

  • for current measurement as 2-wire transducer

Yes

  • for current measurement as 4-wire transducer

Yes

Ex(i) characteristics

 

Module for Ex(i) protection

Yes

Max. values of input circuits (per channel)

 

  • Co (permissible external capacity), max.

62 nF

  • Io (short-circuit current), max.

96.1 mA

  • Lo (permissible external inductivity), max.

3 mH

  • Po (power of load), max.

511 mW

  • Uo (output no-load voltage), max.

26 V

  • Um (fault voltage), max.

250 V; DC

  • Ta (permissible ambient temperature), max.

0.6 °C

Errors/accuracies

 

Linearity error (relative to input area)

+/- 0.01 %

Temperature error (relative to input area)

+/- 0.01 %

Crosstalk between the inputs, min.

130 dB

Repeat accuracy in settled status at 25 °C (relative to input area)

+/- 0.05 %

Operational limit in overall temperature range

 

  • Current, relative to input area

+/- 0,45 %; from 0/4 to 20 mA

Basic error limit (operational limit at 25 °C)

 

  • Current, relative to input area

+/- 0,1 %; From 0/4 to 20 mA

Interference voltage suppression for f = n x (fl +/- 1%), fl = interference frequency

 

  • Series mode interference (peak value of interference < rated value of input range), min.

60 dB

  • Common mode interference, min.

130 dB

Interrupts/diagnostics/status information

 

Alarms

 

  • Diagnostic alarm

Yes; Parameterizable

  • Limit value alarm

Yes; Parameterizable, channels 0 and 1

Diagnoses

 

  • Diagnostic functions

Yes; can be set in parameters, red LED, alarm message

  • Diagnostic information readable

Yes

  • Overrange

Yes; red LED, signal

  • Wire break in signal transmitter cable

Yes; red LED, signal

  • Short circuit of the signal encoder cable

Yes; red LED, signal

  • HART communication active

Yes; green LED (H)

Diagnostics indication LED

 

  • Group error SF (red)

Yes

  • Channel error indicator F (red)

Yes

Isolation

 

tested with

 

  • Channels against backplane bus and load voltage L+

1500 V AC

  • Channels among one another

1500 V AC

  • Load voltage L+ against backplane bus

500 V DC

Galvanic isolation

 

between the channels and backplane bus

Yes

Galvanic isolation analog inputs

 

  • Galvanic isolation analog inputs

Yes

Galvanic isolation analog outputs

 

  • between the channels

Yes

  • between the channels and the load voltage L+

Yes

Permissible potential difference

 

between the inputs (UCM)

60 V DC / 30 V AC

Environmental requirements

 

Operating temperature

 

  • max.

60 °C

Standards, approvals, certificates

 

FM approval

Available soon

Type of protection acc. to EN 50020 (CENELEC)

[EEx ib] IIC

Type of protection acc. to FM

Class I, Division 2, Group A, B, C, D T4; Class I, Zone 2, Group IIC T4

Test number KEMA

KEMA 97; ATEX3039 X

Type of protection acc. to KEMA

II3 (2) G Eex nA [ib] IIC T4

Dimensions and weight

 

Dimensions

 

  • Width

40 mm

  • Height

125 mm

  • Depth

120 mm

Weight

 

  • Weight, approx.

260 g