6ES7 332-5TB00-0AB0

Supply voltages

 

Load voltage L+

 

  • Rated value (DC)

24 V

  • Reverse polarity protection

Yes

Current consumption

 

from backplane bus 5 V DC, max.

100 mA

from supply voltage L+, max.

150 mA

Power losses

 

Power loss, typ.

3.5 W

Analog outputs

 

Number of analog outputs

2

Cable length, shielded, max.

400 m

Voltage output, short-circuit protection

Yes

Current output, no-load voltage, max.

19 V

Cycle time (all channels) max.

5 ms

Output ranges, current

 

  • 0 to 20 mA

Yes

  • 4 to 20 mA

Yes

Connection of actuators

 

  • for current output 2-conductor connection

Yes

Load impedance (in rated range of output)

 

  • with current outputs, max.

650 Ω

  • with current outputs, inductive load, max.

7.5 mH

Destruction limits against externally applied voltages and currents

 

  • Voltages at the outputs towards MANA

max. 17 V / -0.5 V

  • Current, max.

60 mA / -1 A

Analog value creation

 

Integrations and conversion time/ resolution per channel

 

  • Resolution with overrange (bit including sign), max.

12 bit; Output value; 8 bit (+ sign) read back value

  • Conversion time (per channel)

40 ms

Settling time

 

  • for resistive load

2.5 ms

  • for capacitive load

4 ms

  • for inductive load

2.5 ms

Ex(i) characteristics

 

Module for Ex(i) protection

Yes

Max. values of output circuits (per channel)

 

  • Co (permissible external capacity), max.

230 nF

  • Io (short-circuit current), max.

66 mA

  • Lo (permissible external inductivity), max.

7.5 mH

  • Po (power of load), max.

506 mW

  • Uo (output no-load voltage), max.

19 V

  • Um (fault voltage), max.

60 V; DC

  • Ta (permissible ambient temperature), max.

60 °C

Errors/accuracies

 

Output ripple (based on output area, bandwidth 0 to 50 kHz)

+/- 0.02 %

Linearity error (relative to output area)

+/- 0.03 %

Temperature error (relative to output area)

+/- 0.01 %

Crosstalk between the outputs, min.

130 dB

Repeat accuracy in settled status at 25 °C (relative to output area)

+/- 0.005 %

Operational limit in overall temperature range

 

  • Current, relative to output area

+/- 0,55 %

Basic error limit (operational limit at 25 °C)

 

  • Current, relative to output area

+/- 0,15 %

Interrupts/diagnostics/status information

 

Substitute values connectable

Yes; Parameterizable

Alarms

 

  • Diagnostic alarm

Yes; Parameterizable

Diagnoses

 

  • Diagnostic functions

Yes; Parameterizable

  • Diagnostic information readable

Yes

  • Diagnostics

Yes

  • Overrange

Yes

  • Wire break

Yes; as of output value > 0.5 mA

  • Wire break in actuator cable

Yes

  • HART communication active

Yes; green LED (H)

Diagnostics indication LED

 

  • Group error SF (red)

Yes; Additional group message per channel

  • Channel error indicator F (red)

Yes; per channel

Isolation

 

tested with

 

  • Channels against backplane bus and load voltage L+

1500 V AC

  • Channels among one another

1500 V AC

  • Load voltage L+ against backplane bus

500 V DC

Galvanic isolation

 

between the channels and backplane bus

Yes

Galvanic isolation analog outputs

 

  • Galvanic isolation analog outputs

Yes

  • between the channels

Yes

  • between the channels and the load voltage L+

Yes

Permissible potential difference

 

between the outputs (UCM)

60 V DC/30 V AC

between M internally and the outputs

60 V DC / 30 V AC

Standards, approvals, certificates

 

FM approval

Available soon

Type of protection acc. to EN 50020 (CENELEC)

[EEx ib] IIC

Type of protection acc. to FM

Class I, Division 2, Group A, B, C, D T4; Class I, Zone 2, Group IIC T4

Test number KEMA

97 ATEX 2359 X

Type of protection acc. to KEMA

II3 (2) G Eex nA [ib] IIC T4

Dimensions and weight

 

Dimensions

 

  • Width

40 mm

  • Height

125 mm

  • Depth

120 mm

Weight

 

  • Weight, approx.

280 g