6ES7 332-5TB00-0AB0 |
Supply voltages |
|
Load voltage L+ |
|
|
24 V |
|
Yes |
Current consumption |
|
from backplane bus 5 V DC, max. |
100 mA |
from supply voltage L+, max. |
150 mA |
Power losses |
|
Power loss, typ. |
3.5 W |
Analog outputs |
|
Number of analog outputs |
2 |
Cable length, shielded, max. |
400 m |
Voltage output, short-circuit protection |
Yes |
Current output, no-load voltage, max. |
19 V |
Cycle time (all channels) max. |
5 ms |
Output ranges, current |
|
|
Yes |
|
Yes |
Connection of actuators |
|
|
Yes |
Load impedance (in rated range of output) |
|
|
650 Ω |
|
7.5 mH |
Destruction limits against externally applied voltages and currents |
|
|
max. 17 V / -0.5 V |
|
60 mA / -1 A |
Analog value creation |
|
Integrations and conversion time/ resolution per channel |
|
|
12 bit; Output value; 8 bit (+ sign) read back value |
|
40 ms |
Settling time |
|
|
2.5 ms |
|
4 ms |
|
2.5 ms |
Ex(i) characteristics |
|
Module for Ex(i) protection |
Yes |
Max. values of output circuits (per channel) |
|
|
230 nF |
|
66 mA |
|
7.5 mH |
|
506 mW |
|
19 V |
|
60 V; DC |
|
60 °C |
Errors/accuracies |
|
Output ripple (based on output area, bandwidth 0 to 50 kHz) |
+/- 0.02 % |
Linearity error (relative to output area) |
+/- 0.03 % |
Temperature error (relative to output area) |
+/- 0.01 % |
Crosstalk between the outputs, min. |
130 dB |
Repeat accuracy in settled status at 25 °C (relative to output area) |
+/- 0.005 % |
Operational limit in overall temperature range |
|
|
+/- 0,55 % |
Basic error limit (operational limit at 25 °C) |
|
|
+/- 0,15 % |
Interrupts/diagnostics/status information |
|
Substitute values connectable |
Yes; Parameterizable |
Alarms |
|
|
Yes; Parameterizable |
Diagnoses |
|
|
Yes; Parameterizable |
|
Yes |
|
Yes |
|
Yes |
|
Yes; as of output value > 0.5 mA |
|
Yes |
|
Yes; green LED (H) |
Diagnostics indication LED |
|
|
Yes; Additional group message per channel |
|
Yes; per channel |
Isolation |
|
tested with |
|
|
1500 V AC |
|
1500 V AC |
|
500 V DC |
Galvanic isolation |
|
between the channels and backplane bus |
Yes |
Galvanic isolation analog outputs |
|
|
Yes |
|
Yes |
|
Yes |
Permissible potential difference |
|
between the outputs (UCM) |
60 V DC/30 V AC |
between M internally and the outputs |
60 V DC / 30 V AC |
Standards, approvals, certificates |
|
FM approval |
Available soon |
Type of protection acc. to EN 50020 (CENELEC) |
[EEx ib] IIC |
Type of protection acc. to FM |
Class I, Division 2, Group A, B, C, D T4; Class I, Zone 2, Group IIC T4 |
Test number KEMA |
97 ATEX 2359 X |
Type of protection acc. to KEMA |
II3 (2) G Eex nA [ib] IIC T4 |
Dimensions and weight |
|
Dimensions |
|
|
40 mm |
|
125 mm |
|
120 mm |
Weight |
|
|
280 g |