6ES7 972-0CB20-0XA0

Supply voltages

 

Rated value

 

  • 24 V DC

Yes

Current consumption

 

Current consumption, typ.

100 mA

Power consumption, typ.

max. 2.5 W

EMC

 

Interference immunity against discharge of static electricity

 

  • Interference immunity against discharge of static electricity acc. to IEC 61000-4-2

Yes; 6 kV, contact discharge (to IEC 61000-4-2); 8 kV, air discharge (to IEC 61000-4-2)

Interference immunity to cable-borne interference

 

  • on the supply lines acc. to IEC 61000-4-4

Yes; 2 kV (to IEC 61000-4-4, Burst)

  • Interference immunity on signal lines acc. to IEC 61000-4-4

Yes; 1 kV (to IEC 61000-4-4; burst; length < 3 m); 2 kV (to IEC 61000-4-4; burst; length > 3 m)

Surge immunity

 

  • on the supply lines acc. to IEC 61000-4-5

Yes; 1 kV (to IEC 61000-4-5; surge symm.); 2 kV (to IEC 61000-4-5; surge asymm.)

Immunity against high-frequency electromagnetic fields

 

  • Interference immunity against high-frequency radiation acc. to IEC 61000-4-3

Yes; 10 V/m, 80 to 1000 MHz (to IEC 61000-4-3); 10 V/m, 900 MHz, 1.89 GHz, 50% ED (to IEC 61000-4-3)

Immunity against conducted interference induced by high-frequency fields

 

  • Interference immunity against high frequency current feed acc. to IEC 61000-4-6

Yes; 10 V, 9 kHz to 80 MHz (to IEC 61000-4-6)

Immunity to magnetic field interference

 

  • Interference immunity to magnetic fields at 50 Hz

30 A/m; to IEC 61000-4-8

Emission of radio interference acc. to EN 55 022

 

  • Interference emission acc. to EN 55022, class B

Yes

Environmental requirements

 

Operating temperature

 

  • Min.

5 °C

  • max.

40 °C

  • permissible temperature change

10 °C/h; Operation: 10 K/h; storage/transport: 20 K/h

Storage/transport temperature

 

  • Min.

-20 °C

  • max.

60 °C

Relative humidity

 

  • Operation, min.

5 %

  • Operation, max.

80 %; at 25 °C  (no condensation)

  • Storage/transport, min.

5 %

  • Storage/transport, max.

95 %; at 25 °C  (no condensation)

Vibrations

 

  • Operation, checked according to IEC 60068-2-6

Yes; 10 to 58 Hz: amplitude 0.075 mm; 58 to 500 Hz: acceleration 9.8 m/s2

  • Transport tested checked to IEC 60068-2-6

Yes; (packed) 5 to 9 Hz, amplitude 3.5 mm; 9 to 500 Hz, acceleration 9.8 m/s2

Shock test

 

  • Shock test

Tested to DIN IEC 60068-2-2; Operation: 950 m/s2 (10 g), 30 ms, 100 Shocks; Transport (packaged): 250 m/s2 (25 g), 6 ms, 1000 shocks

Dimensions and weight

 

Dimensions

 

  • Width

105 mm

  • Height

58 mm

  • Depth

26 mm

Weight

 

  • Weight, approx.

100 g