Order No.

6GK7 342-5DA02-0XE0

Product type designation

CP 342-5

Transmission rate

 

Transmission rate at interface 1 in accordance with PROFIBUS

9.6 Kbit/s … 12 Mbit/s

Interfaces

 

Number of electrical connections

 

  • at interface 1 in accordance with PROFIBUS

1

  • for power supply

1

Design of electrical connection

 

  • at interface 1 in accordance with PROFIBUS

9-pin D-sub socket (RS485)

  • for power supply

4-pin terminal strip

Supply voltage, current consumption, power loss

 

Type of power supply

DC

Power supply

 

  • 1 from backplane bus

5 V

  • External

24 V

Relative positive tolerance at 24 V DC

20 %

Relative negative tolerance at 24 V DC

15 %

Current consumed

 

  • from backplane bus at 5 V DC, typical

0.15 A

  • from external power supply with 24 V DC

 

    • Typical

0.25 A

    • Maximum

-

Effective power loss

6.75 W

Permitted ambient conditions

 

Ambient temperature

 

  • During operating phase

0 … 60 °C

  • During storage

-40 … +70 °C

  • During transport

-40 … +70 °C

Relative humidity at 25 °C without condensation during operating phase, maximum

95 %

IP degree of protection

IP 20

Design, dimensions and weights

 

Module format

S7-300 compact module, single-width

Width

40 mm

Height

125 mm

Depth

120 mm

Net weight

0.3 kg

Type of mounting: S7-300 DIN rail mounting

 

Product properties, functions, componentsGeneral

 

Maximum number of modules per CPU

4

Number of modules - Note

-

Performance data

 

Performance dataOpen communication

 

Number of possible connections for open communication by means of SEND/RECEIVE blocks, maximum

16

Data volume as user data per connection for open communication by means of SEND/RECEIVE blocks, maximum

240 byte

Performance dataPROFIBUS  DP

 

Service as DP master DPV0

Yes

Number of DP slaves operable on DP master

124

Data volume

 

  • of address area of inputs as DP master, total

2 160 byte

  • of address area of outputs as DP master, total

2 160 byte

  • of address area of inputs per DP slave

244 byte

  • of address area of outputs per DP slave

244 byte

  • of address area of diagnostics data per DP slave

240 byte

Service as DP slave DPV0

Yes

Data volume

 

  • of address area of inputs as DP slave, total

240 byte

  • of address area of outputs as DP slave, total

240 byte

Performance dataS7 communication

 

Maximum number of possible connections for S7 communication

16

Number of possible connections for S7 communication - Note

-

Performance dataMultiprotocol operation

 

Number of active connections in multiprotocol mode

 

  • Maximum without DP

32

  • Maximum with DP

28

Product functionsManagement, configuration, programming

 

Configuration software required