Order No.

6GK7 443-5FX02-0XE0

Product type designation

CP 443-5 Basic

Transmission rate

 

Transmission rate at interface 1 in accordance with PROFIBUS

9.6 Kbit/s … 12 Mbit/s

Interfaces

 

Number of electrical connections at interface 1 in accordance with PROFIBUS

1

Design of electrical connection at interface 1 in accordance with PROFIBUS

9-pin D-sub socket (RS485)

Supply voltage, current consumption, power loss

 

Type of power supply

DC

Power supply 1 from backplane bus

5 V

Relative symmetrical tolerance at 5 V DC

5 %

Current input from backplane bus with 5 V DC, typical

1.2 A

Effective power loss

6.5 W

Permitted ambient conditions

 

Ambient temperature

 

  • During operating phase

0 … 60 °C

  • During storage

-40 … +70 °C

  • During transport

-40 … +70 °C

Relative humidity at 25 °C without condensation during operating phase, maximum

95 %

IP degree of protection

IP 20

Design, dimensions and weights

 

Module format

S7-400 compact module, single-width

Width

25 mm

Height

290 mm

Depth

210 mm

Net weight

0.7 kg

Product properties, functions, componentsGeneral

 

Maximum number of modules per CPU

14

Number of modules - Note

-

Performance data

 

Performance dataOpen communication

 

Number of possible connections for open communication by means of SEND/RECEIVE blocks, maximum

32

Data volume as user data per connection for open communication by means of SEND/RECEIVE blocks, maximum

240 byte

Performance dataFMS functions

 

Number of possible connections with FMS connection, maximum

48

Data volume of variables

 

  • Maximum with READ request

237 byte

  • Maximum with WRITE request

233 byte

Number of variables

 

  • Configurable from server to FMS partner

512

  • Loadable from server onto FMS partner

2 640

Performance dataS7 communication

 

Maximum number of possible connections for S7 communication

48

Number of possible connections for S7 communication - Note

-

Performance dataMultiprotocol operation

 

Number of possible connections, of which 2 reserved for PG/OP communication in multiprotocol mode, maximum

59

Product functionsManagement, configuration, programming

 

Configuration software required

STEP 7 V5.2 SP1 and higher and NCM S7 for PROFIBUS