Order No.

6GK7 342-5DF00-0XE0

Product type designation

CP 342-5 FO

Transmission rate

 

Transmission rate at interface 1 in accordance with PROFIBUS

9.6 Kbit/s … 12 Mbit/s

Interfaces

 

Number of optical connections at interface 1 in accordance with PROFIBUS

2

Number of electrical connections for power supply

1

Design of optical connection at interface 1 in accordance with PROFIBUS

Duplex socket

Design of electrical connection for power supply

4-pin terminal strip

Supply voltage, current consumption, power loss

 

Type of power supply

DC

Power supply

 

  • 1 from backplane bus

5 V

  • External

24 V

Relative positive tolerance at 24 V DC

20 %

Relative negative tolerance at 24 V DC

15 %

Current consumed

 

  • from backplane bus at 5 V DC, typical

0.15 A

  • from external power supply with 24 V DC

 

    • Typical

0.25 A

    • Maximum

-

Effective power loss

6.75 W

Permitted ambient conditions

 

Ambient temperature

 

  • During operating phase

0 … 60 °C

  • During storage

-40 … +70 °C

  • During transport

-40 … +70 °C

Relative humidity at 25 °C without condensation during operating phase, maximum

95 %

IP degree of protection

IP 20

Design, dimensions and weights

 

Module format

Compact module

Width

40 mm

Height

125 mm

Depth

120 mm

Net weight

0.3 kg

Product properties, functions, componentsGeneral

 

Maximum number of modules per CPU

4

Number of modules - Note

-

Cable length

 

  • With polymer cladded fiber cable, maximum

300 m

  • With plastic optical fiber cable, maximum

50 m

Performance data

 

Performance dataOpen communication

 

Number of possible connections for open communication by means of SEND/RECEIVE blocks, maximum

16

Data volume as user data per connection for open communication by means of SEND/RECEIVE blocks, maximum

240 byte

Performance dataPROFIBUS  DP

 

Service as DP master DPV0

Yes

Number of DP slaves operable on DP master

124

Data volume

 

  • of address area of inputs as DP master, total

2 160 byte

  • of address area of outputs as DP master, total

2 160 byte

  • of address area of inputs per DP slave

244 byte

  • of address area of outputs per DP slave

244 byte

  • of address area of diagnostics data per DP slave

240 byte

Service as DP slave DPV0

Yes

Data volume

 

  • of address area of inputs as DP slave, total

240 byte

  • of address area of outputs as DP slave, total

240 byte

Performance dataS7 communication

 

Maximum number of possible connections for S7 communication

16

Number of possible connections for S7 communication - Note

-

Performance dataMultiprotocol operation

 

Number of active connections in multiprotocol mode

 

  • Maximum without DP

32

  • Maximum with DP

28

Product functionsManagement, configuration, programming

 

Configuration software required

STEP 7 V5.1 SP2 or higher