6ES7 322-1BH01-0AA0

6ES7 322-1BH10-0AA0

6ES7 322-1BL00-0AA0

6ES7 322-1BP00-0AA0

6ES7 322-1BP50-0AA0

6ES7 322-8BF00-0AB0

Supply voltages

 

 

 

 

 

 

Load voltage L+

 

 

 

 

 

 

  • Rated value (DC)

24 V

24 V

24 V

24 V

24 V

24 V

Current consumption

 

 

 

 

 

 

from load voltage L+ (without load), max.

80 mA

110 mA

160 mA

75 mA

75 mA

90 mA

from backplane bus 5 V DC, max.

80 mA

70 mA

110 mA

100 mA

100 mA

70 mA

Power losses

 

 

 

 

 

 

Power loss, typ.

4.9 W

5 W

6.6 W

6 W

6 W

5 W

Connection method

 

 

 

 

 

 

required front connector

20-pin

20-pin

40-pin

Cable: 6ES7 392-4Bxx0-0AA0 terminal block: 6ES7 392-1xN00-0AA0

Cable: 6ES7 392-4Bxx0-0AA0 terminal block: 6ES7 392-1xN00-0AA0

20-pin

Digital outputs

 

 

 

 

 

 

Number of digital outputs

16

16

32

64

64

8

Short-circuit protection

Yes; Electronic

Yes; Electronic

Yes; Electronic

Yes; Electronic

Yes; Electronic

Yes; Electronic

Limitation of inductive shutdown voltage to

L+ (-53 V)

L+ (-53 V)

L+ (-53 V)

L+ (-53 V)

M+ (45 V)

L+ (-45 V)

Lamp load, max.

5 W

5 W

5 W

5 W

5 W

5 W

Output voltage

 

 

 

 

 

 

  • for signal "1", min.

L+ (-0.8 V)

L+ (-0.8 V)

L+ (-0.8 V)

L+ (-0.5 V)

M+ (0.5 V)

L+ (-0.8 to -1.6 V)

Output current

 

 

 

 

 

 

  • for signal "1" rated value

0.5 A

0.5 A

0.5 A

0.3 A

0.3 A

0.5 A

  • for signal "1" permissible range, min.

 

 

 

2.4 mA

2.4 mA

 

  • for signal "1" permissible range, max.

 

 

 

0.36 A

0.36 A

 

  • for signal "1" permissible range for 0 to 40 °C, min.

5 mA

5 mA

5 mA

 

 

10 mA

  • for signal "1" permissible range for 0 to 40 °C, max.

0.6 A

0.6 A

0.6 A

 

 

0.6 A

  • for signal "1" permissible range for 40 to 60 °C, min.

5 mA

5 mA

5 mA

 

 

10 mA

  • for signal "1" permissible range for 40 to 60 °C, max.

0.6 A

0.6 A

0.6 A

 

 

0.6 A

  • for signal "1" minimum load current

5 mA

5 mA

5 mA

 

 

10 mA

  • for signal "0" residual current, max.

0.5 mA

0.5 mA

0.5 mA

0.1 mA

 

0.5 mA

Switching frequency

 

 

 

 

 

 

  • with resistive load, max.

100 Hz

1 000 Hz

100 Hz

100 Hz

100 Hz

100 Hz

  • with inductive load, max.

0.5 Hz

0.5 Hz

 

0.5 Hz

0.5 Hz

2 Hz

  • on lamp load, max.

10 Hz

10 Hz

10 Hz

10 Hz

10 Hz

10 Hz

Aggregate current of outputs (per group)

 

 

 

 

 

 

  • horizontal installation

 

 

 

 

 

 

    • up to 40 °C, max.

4 A

4 A

4 A

1.6 A

1.6 A

4 A

    • up to 60 °C, max.

3 A

3 A

3 A

1.2 A

1.2 A

3 A

  • vertical installation

 

 

 

 

 

 

    • up to 40 °C, max.

2 A

2 A

2 A

1.6 A

1.6 A

4 A

Cable length

 

 

 

 

 

 

  • Cable length, shielded, max.

1 000 m

1 000 m

1 000 m

1 000 m

1 000 m

1 000 m

  • Cable length unshielded, max.

600 m

600 m

600 m

600 m

600 m

600 m

Interrupts/diagnostics/status information

 

 

 

 

 

 

Alarms

 

 

 

 

 

 

  • Diagnostic alarm

No

No

No

No

No

Yes; Parameterizable

Diagnoses

 

 

 

 

 

 

  • Diagnostics

No

No

No

No

No

Yes

Isolation

 

 

 

 

 

 

Isolation checked with

500 VDC

500 VDC

500 VDC

500 VDC

500 VDC

500 VDC

Galvanic isolation

 

 

 

 

 

 

Galvanic isolation digital outputs

 

 

 

 

 

 

  • between the channels, in groups of

8

8

8

16

16

8

  • between the channels and the backplane bus

Yes; Optocoupler

Yes; Optocoupler

Yes; Optocoupler

Yes; Optocoupler

Yes; Optocoupler

Yes; Optocoupler

Dimensions and weight

 

 

 

 

 

 

Dimensions

 

 

 

 

 

 

  • Width

40 mm

40 mm

40 mm

40 mm

40 mm

40 mm

  • Height

125 mm

125 mm

125 mm

125 mm

125 mm

125 mm

  • Depth

120 mm

120 mm

120 mm

112 mm

112 mm

120 mm

Weight

 

 

 

 

 

 

  • Weight, approx.

190 g

200 g

260 g

230 g

230 g

210 g


 

6ES7 322-5GH00-0AB0

6ES7 322-1CF00-0AA0

6ES7 322-1BF01-0AA0

6ES7 322-1FF01-0AA0

6ES7 322-5FF00-0AB0

6ES7 322-1FH00-0AA0

Supply voltages

 

 

 

 

 

 

Load voltage L+

 

 

 

 

 

 

  • Rated value (DC)

24 V; 24 / 48

48 V; 48 to 125 V DC

24 V

 

 

 

Load voltage L1

 

 

 

 

 

 

  • Rated value (AC)

 

 

 

230 V; 120 / 230 VAC

230 V; 120 / 230 VAC

230 V; 120 / 230 VAC

Current consumption

 

 

 

 

 

 

from load voltage L+ (without load), max.

200 mA

2 mA

60 mA

 

 

2 mA

from load voltage L1 (without load), max.

 

 

 

2 mA

2 mA

3 mA

from backplane bus 5 V DC, max.

100 mA

100 mA

40 mA

100 mA

100 mA

200 mA

Power losses

 

 

 

 

 

 

Power loss, typ.

2.8 W

7.2 W

6.8 W

8.6 W

8.6 W

8.6 W

Connection method

 

 

 

 

 

 

required front connector

40-pin

20-pin

20-pin

20-pin

40-pin

20-pin

Digital outputs

 

 

 

 

 

 

Number of digital outputs

16

8

8

8

8

16

Short-circuit protection

No; to be provided externally

Yes; Electronic

Yes; Electronic

Yes; Fuse 8 A, 250 V; per group

Yes; to be provided externally; fuse 3.15 A / 250 V, quick response

Yes; Fuse 8 A, 250 V; per group

Limitation of inductive shutdown voltage to

 

M (-1 V)

L+ (-48 V)

 

 

 

Lamp load, max.

2.5 W

15 W; 15 W (48 V) or 40 W (125 V)

10 W

50 W

50 W

50 W

Output voltage

 

 

 

 

 

 

  • for signal "1", min.

L+ (-0.25 V)

L+ (-1.2 V)

L+ (-0.8 V)

L1 (-1.5 V)

L1 (-8.5 V)

 

Output current

 

 

 

 

 

 

  • for signal "1" rated value

0.5 A

1.5 A

2 A

2 A

2 A

1 A

  • for signal "1" permissible range for 0 to 40 °C, min.

 

10 mA

5 mA

10 mA

10 mA

10 mA

  • for signal "1" permissible range for 0 to 40 °C, max.

 

1.5 A

2.4 A

2 A

2 A

1 A

  • for signal "1" permissible range for 40 to 60 °C, min.

 

10 mA

5 mA

10 mA

10 mA

10 mA

  • for signal "1" permissible range for 40 to 60 °C, max.

 

1.5 A

2.4 A

1 A

1 A

0.5 A

  • for signal "1" minimum load current

 

10 mA

5 mA

10 mA

10 mA

10 mA

  • for signal "1" permissible surge current, max.

1.5 A; for 50 ms, 1 A 2 s one-time

3 A; for 10 ms

 

20 A; max. 1 AC cycle

20 A; with 2 half waves

20 A; with 2 half waves

  • for signal "0" residual current, max.

10 µA

0.5 mA

0.5 mA

2 mA

2 mA

2 mA

Switching frequency

 

 

 

 

 

 

  • with resistive load, max.

10 Hz

25 Hz

100 Hz

10 Hz

10 Hz

10 Hz

  • with inductive load, max.

 

0.5 Hz

0.5 Hz

0.5 Hz

0.5 Hz

0.5 Hz

  • on lamp load, max.

0.5 Hz

10 Hz

10 Hz

1 Hz

1 Hz

1 Hz

Aggregate current of outputs (per group)

 

 

 

 

 

 

  • horizontal installation

 

 

 

 

 

 

    • up to 40 °C, max.

 

6 A

 

4 A

8 A

4 A

    • up to 50 °C, max.

 

4 A

 

 

 

 

    • up to 60 °C, max.

0.5 A; (8 A per module)

3 A

4 A

2 A

4 A

2 A

  • vertical installation

 

 

 

 

 

 

    • up to 40 °C, max.

 

4 A

4 A

2 A

4 A

2 A

  • all other mounting positions

 

 

 

 

 

 

    • up to 40 °C, max.

0.5 A; (8 A per module)

 

 

 

 

 

Cable length

 

 

 

 

 

 

  • Cable length, shielded, max.

1 000 m

1 000 m

1 000 m

1 000 m

1 000 m

1 000 m

  • Cable length unshielded, max.

600 m

600 m

600 m

600 m

600 m

600 m

Interrupts/diagnostics/status information

 

 

 

 

 

 

Alarms

 

 

 

 

 

 

  • Diagnostic alarm

Yes; Parameterizable

No

No

No

Yes; Parameterizable

No

Diagnoses

 

 

 

 

 

 

  • Diagnostics

Yes; Parameters can be assigned

No

No

Yes

Yes

Yes

Isolation

 

 

 

 

 

 

Isolation checked with

1500 VAC

1500 VAC

500 VDC

1500 VAC

1500 VAC

4000 VDC

Galvanic isolation

 

 

 

 

 

 

Galvanic isolation digital outputs

 

 

 

 

 

 

  • between the channels, in groups of

1

4

4

4

1

8

  • between the channels and the backplane bus

Yes; Optocoupler

Yes; Optocoupler

Yes; Optocoupler

Yes; Optocoupler

Yes; Optocoupler

Yes; Optocoupler

Dimensions and weight

 

 

 

 

 

 

Dimensions

 

 

 

 

 

 

  • Width

40 mm

40 mm

40 mm

40 mm

40 mm

40 mm

  • Height

125 mm

125 mm

125 mm

125 mm

125 mm

125 mm

  • Depth

120 mm

120 mm

120 mm

120 mm

120 mm

120 mm

Weight

 

 

 

 

 

 

  • Weight, approx.

260 g

250 g

190 g

275 g

275 g

275 g


 

6ES7 322-1FL00-0AA0

6ES7 322-1HF01-0AA0

6ES7 322-1HF10-0AA0

6ES7 322-5HF00-0AB0

6ES7 322-1HH01-0AA0

Supply voltages

 

 

 

 

 

Load voltage L+

 

 

 

 

 

  • Rated value (DC)

 

24 V

120 V

24 V

120 V

Load voltage L1

 

 

 

 

 

  • Rated value (AC)

120 V; 120 / 230 VAC

 

230 V

230 V

230 V

Current consumption

 

 

 

 

 

from load voltage L+ (without load), max.

 

110 mA; Current consumption of relay

 

 

 

from load voltage L1 (without load), max.

10 mA

110 mA

 

 

 

from backplane bus 5 V DC, max.

190 mA

40 mA

40 mA

100 mA

100 mA

Power losses

 

 

 

 

 

Power loss, typ.

25 W

3.2 W

4.2 W

3.5 W

4.5 W

Connection method

 

 

 

 

 

required front connector

20-pin

20-pin

40-pin

40-pin

20-pin

Digital outputs

 

 

 

 

 

Number of digital outputs

32

8; Relay

8; Relay

8; Relay

16; Relay

Short-circuit protection

No

 

No; to be provided externally

No; to be provided externally

 

Lamp load, max.

50 W

50 W

1 500 W; AC 230 V

1 500 W; AC 230 V

50 W; AC 230 V

Output voltage

 

 

 

 

 

  • for signal "1", min.

L1 (-0.8 V)

 

 

 

 

Output current

 

 

 

 

 

  • for signal "1" rated value

1 A

2 A

5 A

5 A

2 A

  • for signal "1" permissible range for 0 to 40 °C, min.

10 mA

 

 

 

 

  • for signal "1" permissible range for 0 to 40 °C, max.

1 A

 

 

 

 

  • for signal "1" permissible range for 40 to 60 °C, min.

10 mA

 

 

 

 

  • for signal "1" permissible range for 40 to 60 °C, max.

1 A

 

 

 

 

  • for signal "1" minimum load current

10 mA

5 mA

5 mA

10 mA

10 mA

  • for signal "1" permissible surge current, max.

10 A; per group (for 2 AC cycles)

 

 

 

 

  • for signal "0" residual current, max.

2 mA

 

 

 

 

Switching frequency

 

 

 

 

 

  • with resistive load, max.

10 Hz

2 Hz

2 Hz

2 Hz

1 Hz

  • with inductive load, max.

0.5 Hz

0.5 Hz

0.5 Hz

0.5 Hz

0.5 Hz

  • on lamp load, max.

1 Hz

2 Hz

2 Hz

2 Hz

1 Hz

  • mechanical, max.

 

10 Hz

10 Hz

10 Hz

10 Hz

Aggregate current of outputs (per group)

 

 

 

 

 

  • horizontal installation

 

 

 

 

 

    • up to 40 °C, max.

4 A

 

 

 

 

    • up to 60 °C, max.

3 A

 

5 A

5 A

8 A

  • vertical installation

 

 

 

 

 

    • up to 40 °C, max.

4 A

 

5 A

5 A

8 A

Cable length

 

 

 

 

 

  • Cable length, shielded, max.

1 000 m

1 000 m

1 000 m

1 000 m

1 000 m

  • Cable length unshielded, max.

600 m

600 m

600 m

600 m

600 m

Relay outputs

 

 

 

 

 

Rated input voltage of relay L+ (DC)

 

24 V; 110 mA

24 V

 

24 V

Number of operating cycles

 

300 000; 230 V AC: 100000; 120 V AC: 200000; 24 V DC: 300000 (at 2 A)

300 000; 300000 (24 V DC, at 2 A); 200000 (120 V AC, at 3 A); 100000 (230 V AC, at 3 A)

100 000; 100,000 (DC 24 V, at 5 A), 100,000 (AC 230 V, at 5 A)

100 000; 50000 (24 V DC, at 2 A); 700000 (120 V AC, at 2 A); 100000 (230 V AC, at 2 A)

Switching capacity of contacts

 

 

 

 

 

  • with inductive load, max.

 

2 A; 2 A (230 V AC), 2 A (24 V DC)

3 A; 3 A (230 V DC); 2 A (24 V AC)

5 A; 5 A (230 V DC); 5 A (24 V AC)

2 A; 2 A (230 V AC), 2 A (24 V DC)

  • with resistive load, max.

 

2 A

8 A; 8 A (230 V DC); 5 A (24 V AC)

5 A; 5 A (230 V DC); 5 A (24 V AC)

2 A; 2 A (230 V AC), 2 A (24 V DC)

Interrupts/diagnostics/status information

 

 

 

 

 

Alarms

 

 

 

 

 

  • Diagnostic alarm

No

No

No

Yes; Parameterizable

No

Diagnoses

 

 

 

 

 

  • Diagnostics

Yes

No

No

Yes

No

Isolation

 

 

 

 

 

Isolation checked with

4000 VDC

1500 VAC

2000 V AC

1500 VAC

1500 VAC

Galvanic isolation

 

 

 

 

 

Galvanic isolation digital outputs

 

 

 

 

 

  • between the channels, in groups of

8

2

1

1

8

  • between the channels and the backplane bus

Yes; Optocoupler

Yes; Optocoupler

Yes; Optocoupler

Yes; Optocoupler

Yes; Optocoupler

Dimensions and weight

 

 

 

 

 

Dimensions

 

 

 

 

 

  • Width

80 mm

40 mm

40 mm

40 mm

40 mm

  • Height

125 mm

125 mm

125 mm

125 mm

125 mm

  • Depth

117 mm

120 mm

120 mm

120 mm

120 mm

Weight

 

 

 

 

 

  • Weight, approx.

500 g

190 g

320 g

320 g

250 g