6ES7 323-1BH01-0AA0

6ES7 323-1BL00-0AA0

6ES7 327-1BH00-0AB0

Supply voltages

 

 

 

Load voltage L+

 

 

 

  • Rated value (DC)

24 V

24 V

24 V

Current consumption

 

 

 

from load voltage L+ (without load), max.

40 mA

80 mA

20 mA

from backplane bus 5 V DC, max.

40 mA

80 mA

60 mA

Power losses

 

 

 

Power loss, typ.

3.5 W

6.5 W

3 W

Connection method

 

 

 

required front connector

20-pin

40-pin

20-pin

Isochronous mode

 

 

 

Isochronous mode

No

No

No

Digital inputs

 

 

 

Number of digital inputs

8

16

8; 8 hard-wired, 8 others individually parameterizable

Number of simultaneously controllable inputs

 

 

 

  • all mounting positions

 

 

 

    • Concurrently controllable inputs, up to 40 °C

8

16

16

    • Concurrently controllable inputs, up to 60 °C

8

8

16

Input characteristic curve acc. to IEC 1131, Type 1

Yes

Yes

Yes

Input voltage

 

 

 

  • Rated value, DC

24 V

24 V

24 V

  • for signal "0"

-30 to +5 V

-30 to +5 V

-30 to +5 V

  • for signal "1"

13 to 30 V

13 to 30 V

15 to 30 V

Input current

 

 

 

  • for signal "1", typ.

7 mA

7 mA

6 mA

Input delay (for rated value of input voltage)

 

 

 

  • for standard inputs

 

 

 

    • at "0" to "1", min.

1.2 ms

1.2 ms

1.2 ms

    • at "0" to "1", max.

4.8 ms

4.8 ms

4.8 ms

    • at "1" to "0", min.

1.2 ms

1.2 ms

1.2 ms

    • at "1" to "0", max.

4.8 ms

4.8 ms

4.8 ms

Cable length

 

 

 

  • Cable length, shielded, max.

1 000 m

1 000 m

1 000 m

  • Cable length unshielded, max.

600 m

600 m

600 m

Digital outputs

 

 

 

Number of digital outputs

8

16

8; can also be parameterized individually as DI

Short-circuit protection

Yes; Electronic

Yes; Electronic

Yes; Electronic

  • Response threshold, typ.

1 A

1 A

1 A

Limitation of inductive shutdown voltage to

L+ (-53 V)

L+ (-48 V)

L+ (-54 V)

Lamp load, max.

5 W

5 W

5 W

Controlling a digital input

Yes

Yes

Yes

Output voltage

 

 

 

  • for signal "1", min.

L+ (-0.8 V)

L+ (-0.8 V)

L+ (-1.5 V)

Output current

 

 

 

  • for signal "1" rated value

0.5 A

0.5 A

0.5 A

  • for signal "1" permissible range for 0 to 60 °C, min.

 

 

5 mA

  • for signal "1" permissible range for 0 to 60 °C, max.

 

 

0.6 A

  • for signal "1" minimum load current

5 mA

5 mA

 

  • for signal "0" residual current, max.

0.5 mA

0.5 mA

0.5 mA

Output delay with resistive load

 

 

 

  • 0 to "1", max.

100 µs

100 µs

350 µs

  • 1 to "0", max.

500 µs

500 µs

500 µs

Parallel switching of 2 outputs

 

 

 

  • for increased power

No

No

No

  • for redundant control of a load

Yes; outputs of the same group only

Yes; outputs of the same group only

Yes; outputs of the same group only

Switching frequency

 

 

 

  • with resistive load, max.

100 Hz

100 Hz

100 Hz

  • with inductive load, max.

0.5 Hz

0.5 Hz

0.5 Hz

  • on lamp load, max.

10 Hz

100 Hz

10 Hz

Aggregate current of outputs (per group)

 

 

 

  • horizontal installation

 

 

 

    • up to 40 °C, max.

 

4 A

4 A

    • up to 60 °C, max.

4 A

3 A

3 A

  • vertical installation

 

 

 

    • up to 40 °C, max.

4 A

2 A

2 A

Load resistance range

 

 

 

  • lower limit

48 Ω

48 Ω

48 Ω

  • upper limit

4 kΩ

4 kΩ

4 kΩ

Cable length

 

 

 

  • Cable length, shielded, max.

1 000 m

1 000 m

1 000 m

  • Cable length unshielded, max.

600 m

600 m

600 m

Encoder

 

 

 

Connectable encoders

 

 

 

  • 2-wire BEROS

Yes

Yes

Yes

    • permissible quiescent current (2-wire BEROS), max.

2 mA

1.5 mA

1.5 mA

Interrupts/diagnostics/status information

 

 

 

Alarms

 

 

 

  • Alarms

No

No

No

Diagnoses

 

 

 

  • Diagnostic functions

No

No

No

Diagnostics indication LED

 

 

 

  • Status indicator digital output (green)

Yes

Yes

Yes

  • Status indicator digital input (green)

Yes

Yes

Yes

Isolation

 

 

 

Isolation checked with

500 VDC

500 VDC

500 VDC

Galvanic isolation

 

 

 

Galvanic isolation digital inputs

 

 

 

  • between the channels

Yes

Yes

No

  • between the channels, in groups of

8

16

 

  • between the channels and the backplane bus

Yes; Optocoupler

Yes; Optocoupler

Yes; Optocoupler

Galvanic isolation digital outputs

 

 

 

  • between the channels

Yes

Yes

No

  • between the channels, in groups of

8

8

 

  • between the channels and the backplane bus

Yes; Optocoupler

Yes; Optocoupler

Yes; Optocoupler

Permissible potential difference

 

 

 

between different circuits

75 VDC / 60 VAC

75 VDC / 60 VAC

75 VDC / 60 VAC

Dimensions and weight

 

 

 

Dimensions

 

 

 

  • Width

40 mm

40 mm

40 mm

  • Height

125 mm

125 mm

125 mm

  • Depth

120 mm

120 mm

120 mm

Weight

 

 

 

  • Weight, approx.

220 g

260 g

200 g