6ES7 326-1RF00-0AB0

6ES7 326-1BK02-0AB0

Supply voltages

 

 

Supply voltage of electronics and encoders 1L+/2L+

 

 

  • Rated value (DC)

24 V

24 V

Current consumption

 

 

from load voltage L+ (without load), max.

160 mA

450 mA

from backplane bus 5 V DC, max.

90 mA

100 mA

Power losses

 

 

Power loss, typ.

4.5 W

10 W

Connection method

 

 

required front connector

40-pin

40-pin

Digital inputs

 

 

Number of digital inputs

8; 8 (one-channel); 4 (two-channel)

24

Number of simultaneously controllable inputs

 

 

  • all mounting positions

 

 

    • Concurrently controllable inputs, up to 40 °C

8; vertical setup

24

    • Concurrently controllable inputs, up to 60 °C

8; horizontal set up

24; (at 24 V) or 18 (at 28.8 V)

Input voltage

 

 

  • Rated value, DC

in accordance with DIN 19234 or NAMUR

24 V

  • for signal "0"

 

-30 to +5 V

  • for signal "1"

 

11 to 30 V

Input current

 

 

  • for signal "0", max. (permissible quiescent current)

0.35 to 1.2 mA

2 mA

  • for signal "1", typ.

2.1 to 7 mA

10 mA

Input delay (for rated value of input voltage)

 

 

  • for standard inputs

 

 

    • at "0" to "1", max.

 

3.4 ms

    • at "1" to "0", max.

 

3.4 ms

  • for NAMUR inputs

 

 

    • at "0" to "1", max.

1.2 to 3 ms

 

    • at "1" to "0", max.

1.2 to 3 ms

 

Cable length

 

 

  • Cable length, shielded, max.

200 m

200 m

  • Cable length unshielded, max.

100 m

100 m

Encoder supply

 

 

Number of outputs

8

4; Isolated

Output voltage

8.2 V DC

 

Output current, rated value

 

400 mA

Encoder

 

 

Connectable encoders

 

 

  • 2-wire BEROS

 

Yes; if short-circuit test is deactivated

    • permissible quiescent current (2-wire BEROS), max.

 

2 mA

Ex(i) characteristics

 

 

Module for Ex(i) protection

Yes

 

Max. values of input circuits (per channel)

 

 

  • Co (permissible external capacity), max.

3 µF

 

  • Io (short-circuit current), max.

13.9 mA

 

  • Lo (permissible external inductivity), max.

80 mH

 

  • Po (power of load), max.

33.1 mW

 

  • Uo (output no-load voltage), max.

10 V

 

  • Um (fault voltage), max.

60 V DC/ 30 V AC

 

  • Ta (permissible ambient temperature), max.

60 °C

60 °C

Interrupts/diagnostics/status information

 

 

Alarms

 

 

  • Diagnostic alarm

Yes

Yes

Diagnoses

 

 

  • Diagnostic information readable

Yes

Yes

Isolation

 

 

Isolation checked with

500 VDC

500 V DC / 350 V AC

Galvanic isolation

 

 

Galvanic isolation digital inputs

 

 

  • between the channels

Yes

Yes

  • between the channels, in groups of

 

12

  • between the channels and the backplane bus

Yes

Yes

Standards, approvals, certificates

 

 

Test number KEMA

99 ATEX 2671 X

 

Highest safety class achievable in safety mode

 

 

  • to DIN VDE 0801

AK 4 (one channel), AK 5 und 6 (two channel)

AK 6

  • acc. to EN 954

Cat. 3 (single-channel), Cat. 4 (two-channel)

Cat. 4

  • acc. to IEC 61508

SIL 2 (single-channel), SIL 3 (two-channel)

SIL 3

Dimensions and weight

 

 

Dimensions

 

 

  • Width

80 mm

80 mm

  • Height

125 mm

125 mm

  • Depth

120 mm

120 mm

Weight

 

 

  • Weight, approx.

482 g

442 g