6ES7 350-1AH03-0AE0 |
Supply voltages |
|
Aux. voltage 1L+, load voltage 2 L+ |
|
|
24 V |
|
|
|
18.5 V |
|
30.2 V |
|
20.4 V |
|
28.8 V |
|
|
|
500 ms |
|
50 s |
|
35 V |
Current consumption |
|
from load voltage 1L+ (without load), max. |
40 mA |
from backplane bus 5 V DC, max. |
160 mA |
Power losses |
|
Power loss, typ. |
4.5 W |
Connection method |
|
required front connector |
1x 20-pin |
Digital inputs |
|
Number of digital inputs |
3 |
Functions |
1 for gate start, 1 for gate stop, 1 for setting the counter |
Input voltage |
|
|
-28.8 to +5 V |
|
+11 to +28.8 V |
Input current |
|
|
9 mA |
Digital outputs |
|
Number of digital outputs |
2 |
Short-circuit protection |
Yes; Clocked electronically |
Limitation of inductive shutdown voltage to |
2L+ (-39 V) |
Output voltage |
|
|
3 V |
|
2L+ (-1.5 V) |
Output current |
|
|
0.5 A |
|
5 mA |
|
0.6 A |
Output delay with resistive load |
|
|
300 µs |
Encoder supply |
|
5 V encoder supply |
|
|
Yes; 5.2 V +/-2% |
|
300 mA |
24 V encoder supply |
|
|
Yes; 1L+ (-3 V) |
|
400 mA |
Encoder |
|
Connectable encoders |
|
|
Yes; With 2 pulse trains offset by 90° |
|
Yes |
|
Yes |
|
Yes; 1 pulse train, 1 direction level |
Counter |
|
Number of counter inputs |
1 |
Counting range, description |
32 bit or +/-31 bit |
Minimum pulse width, adjustable |
Yes; 2.5 or 25 µs |
Counter input 5 V |
|
|
RS 422 |
|
220 Ω |
|
1.3 V |
|
500 kHz |
Counter input 24 V |
|
|
-28.8 to +5 V |
|
+11 to +28.8 V |
|
9 mA |
|
200 kHz |
|
2.5 µs |
Isolation |
|
Isolation checked with |
500 V |
Galvanic isolation |
|
Galvanic isolation digital inputs |
|
|
Yes; Optocoupler |
Galvanic isolation digital outputs |
|
|
Yes; Optocoupler |
Galvanic isolation counter |
|
|
Yes; Optocoupler |
Permissible potential difference |
|
between different circuits |
75 VDC / 60 VAC |
Dimensions and weight |
|
Dimensions |
|
|
40 mm |
|
125 mm |
|
120 mm |
Weight |
|
|
250 g |