6ES7 414-2XK05-0AB0

6ES7 414-3XM05-0AB0

6ES7 414-3EM06-0AB0

Product type designation

CPU 414-2

CPU 414-3

CPU414-3 PN/DP

Product version

 

 

 

Hardware product version

03

03

01

Firmware version

V5.3

V5.3

V6.0

associated programming package

STEP7 V 5.3 SP2 or higher with HW update

STEP7 V 5.3 SP2 or higher with HW update

STEP7 V5.5 or higher/iMap V3.0 + iMap STEP7 Add-on V3.0 SP5 or higher

Supply voltages

 

 

 

Rated value

 

 

 

  • 24 V DC

No; Power supply via system power supply

No; Power supply via system power supply

No; Power supply via system power supply

Feeding of external backup voltage to CPU

5 to 15 VDC

5 to 15 VDC

5 to 15 VDC

Current consumption

 

 

 

from backplane bus 5 V DC, max.

1.1 A

1.3 A

1.5 A

from interface 5 V DC, max.

90 mA; At each DP interface

90 mA; At each DP interface

90 mA; At each DP interface

Power losses

 

 

 

Power loss, typ.

4.5 W

5.5 W

6.5 W

Power loss, max.

5 W

6 W

7.5 W

Backup battery

 

 

 

Battery operation

not relevant

not relevant

not relevant

  • Backup current, typ.

125 µA; (up to 40 °C)

125 µA

125 µA; (up to 40 °C)

  • Backup current, max.

550 µA

550 µA

450 µA

Memory

 

 

 

Work memory

 

 

 

  • integrated (for program)

0.5 Mbyte

1.4 Mbyte

2 Mbyte

  • integrated (for data)

0.5 Mbyte

1.4 Mbyte

2 Mbyte

  • expandable

No

No

No

Load memory

 

 

 

  • expandable FEPROM

Yes; with Memory Card (FLASH)

Yes; with Memory Card (FLASH)

Yes; with Memory Card (FLASH)

  • expandable FEPROM, max.

64 Mbyte

64 Mbyte

64 Mbyte

  • integrated RAM, max.

512 Kibyte

512 Kibyte

512 Kibyte

  • expandable RAM

Yes; with Memory Card (RAM)

Yes; with Memory Card (RAM)

Yes; with Memory Card (RAM)

  • expandable RAM, max.

64 Mbyte

64 Mbyte

64 Mbyte

Backup

 

 

 

  • present

Yes

Yes

Yes

  • with battery

Yes; All data

Yes; All data

Yes; All data

  • without battery

No

No

No

CPU/ blocks

 

 

 

DB

 

 

 

  • Number, max.

6 000; Number range: 1 to 16,000

6 000; Number range: 1 to 16,000

6 000; Number range: 1 to 16,000

  • Size, max.

64 Kibyte

64 Kibyte

64 Kibyte

FB

 

 

 

  • Number, max.

3 000; Number range: 0 to 7999

3 000; Number range: 0 to 7999

3 000; Number range: 0 to 7999

  • Size, max.

64 Kibyte

64 Kibyte

64 Kibyte

FC

 

 

 

  • Number, max.

3 000; Number range: 0 to 7999

3 000; Number range: 0 to 7999

3 000; Number range: 0 to 7999

  • Size, max.

64 Kibyte

64 Kibyte

64 Kibyte

OB

 

 

 

  • Size, max.

64 Kibyte

64 Kibyte

64 Kibyte

Nesting depth

 

 

 

  • per priority class

24

24

24

  • additional within an error OB

1

1

1

CPU processing times

 

 

 

for bit operations, min.

45 ns

45 ns

45 ns

for word operations, min.

45 ns

45 ns

45 ns

for fixed point arithmetic, min.

45 ns

45 ns

45 ns

for floating point arithmetic, min.

135 ns

135 ns

135 ns

Counters, timers and their retentivity

 

 

 

S7 counter

 

 

 

  • Number

2 048

2 048

2 048

  • Retentivity

 

 

 

    • can be set

Yes

Yes

Yes

    • lower limit

0

0

0

    • upper limit

2 047

2 047

2 047

    • preset

Z 0 to Z 7

Z 0 to Z 7

Z 0 to Z 7

  • Counting range

 

 

 

    • lower limit

0

0

0

    • upper limit

999

999

999

IEC counter

 

 

 

  • present

Yes

Yes

Yes

  • Type

SFB

SFB

SFB

  • Number

Unlimited (limited only by RAM capacity)

Unlimited (limited only by RAM capacity)

Unlimited (limited only by RAM capacity)

S7 times

 

 

 

  • Number

2 048

2 048

2 048

  • Retentivity

 

 

 

    • can be set

Yes

Yes

Yes

    • lower limit

0

0

0

    • upper limit

2 047

2 047

2 047

    • preset

No times retentive

No times retentive

No times retentive

  • Time range

 

 

 

    • lower limit

10 ms

10 ms

10 ms

    • upper limit

9 990 s

9 990 s

9 990 s

IEC timer

 

 

 

  • present

Yes

Yes

Yes

  • Type

SFB

SFB

SFB

  • Number

Unlimited (limited only by RAM capacity)

Unlimited (limited only by RAM capacity)

Unlimited (limited only by RAM capacity)

Data areas and their retentivity

 

 

 

retentive data area, total

Total working and load memory (with backup battery)

Total working and load memory (with backup battery)

Total working and load memory (with backup battery)

Flag

 

 

 

  • Number, max.

8 Kibyte; Size of bit memory address area

8 Kibyte; Size of bit memory address area

8 Kibyte; Size of bit memory address area

  • Retentivity available

Yes

Yes

Yes

  • Number of clock memories

8; (in 1 memory byte)

8; (in 1 memory byte)

8; (in 1 memory byte)

Data blocks

 

 

 

  • Number, max.

6 000; Number range: 1 to 16,000

6 000; Number range: 1 to 16,000

6 000; Number range: 1 to 16,000

  • Size, max.

64 Kibyte

64 Kibyte

64 Kibyte

Local data

 

 

 

  • adjustable, max.

16 Kibyte

16 Kibyte

16 Kibyte

  • preset

8 Kibyte

8 Kibyte

8 Kibyte

Address area

 

 

 

I/O address area

 

 

 

  • overall

8 Kibyte

8 Kibyte

8 Kibyte

  • Outputs

8 Kibyte

8 Kibyte

8 Kibyte

  • of which, distributed

 

 

 

    • MPI/DP interface, inputs

2 Kibyte

2 Kibyte

2 Kibyte

    • MPI/DP interface, outputs

2 Kibyte

2 Kibyte

2 Kibyte

    • DP interface, inputs

6 Kibyte

6 Kibyte

6 Kibyte

    • DP interface, outputs

6 Kibyte

6 Kibyte

6 Kibyte

    • PN interface, inputs

 

 

8 Kibyte

    • PN interface, outputs

 

 

8 Kibyte

Process image

 

 

 

  • Inputs, adjustable

8 Kibyte

8 Kibyte

8 Kibyte

  • Outputs, adjustable

8 Kibyte

8 Kibyte

8 Kibyte

  • Inputs, default

256 byte

256 byte

256 byte

  • Outputs, default

256 byte

256 byte

256 byte

  • consistent data, max.

244 byte

244 byte

244 byte

  • Access to consistent data in process image

Yes

Yes

Yes

Subprocess images

 

 

 

  • Number of subprocess images, max.

15

15

15

Digital channels

 

 

 

  • Inputs

65 536

65 536

65 536

  • Outputs

65 536

65 536

65 536

  • Inputs, of which central

65 536

65 536

65 536

  • Outputs, of which central

65 536

65 536

65 536

Analog channels

 

 

 

  • Inputs

4 096

4 096

4 096

  • Outputs

4 096

4 096

4 096

  • Inputs, of which central

4 096

4 096

4 096

  • Outputs, of which central

4 096

4 096

4 096

Hardware configuration

 

 

 

connectable OPs

31

31

63

Central devices, max.

1

1

1

Expansion devices, max.

21

21

21

Multicomputing

Yes; 4 CPUs max. (with UR1 or UR2)

Yes; 4 CPUs max. (with UR1 or UR2)

Yes; 4 CPUs max. (with UR1 or UR2)

Interface modules

 

 

 

  • Number of connectable IMs (total), max.

6

6

6

  • Number of connectable IM 460s, max.

6

6

6

  • Number of connectable IM 463s, max.

4; IM 463-2

4; IM 463-2

4; IM 463-2

Number of DP masters

 

 

 

  • integrated

2

2

1

  • via IM 467

4

4

4

  • via CP

10; CP 443-5 Extended

10; CP 443-5 Extended

10; CP 443-5 Extended

  • Mixed mode IM + CP permitted

No; IM 467 not suitable for use with CP 443-5 Ext. and CP443-1 EX4x, EX20, GX20 (in PNIO mode)

No; IM 467 not suitable for use with CP 443-5 Ext. and CP443-1 EX4x, EX20, GX20 (in PNIO mode)

No; IM 467 not suitable for use with CP 443-5 Ext. and CP443-1 EX4x, EX20, GX20 (in PNIO mode)

  • via interface module

0

1

1; IF 964-DP

  • Number of pluggable S5 modules (via adapter capsule in central device), max.

6

6

6

Number of IO Controllers

 

 

 

  • integrated

0

0

1

  • via CP

4; No mixed operation of CP443-1 EX40 and CP443-1 EX 41/EX20/GX20, max. 4 in central controller

4; No mixed operation of CP443-1 EX40 and CP443-1 EX 41/EX20/GX20, max. 4 in central controller

4; No mixed operation of CP443-1 EX40 and CP443-1 EX 41/EX20/GX20, max. 4 in central controller

Number of operable FMs and CPs (recommended)

 

 

 

  • FM

Limited by number of slots and number of connections

Limited by number of slots and number of connections

Limited by number of slots and number of connections

  • CP, point-to-point

CP 440: limited by number of slots; CP 441: limited by number of connections

CP 440: limited by number of slots; CP 441: limited by number of connections

CP 440: Limited by number of slots; CP 441: Limited by number of slots and number of connections

  • PROFIBUS and Ethernet CPs

14; Of which 10 CPs max. or IMs as DP master, 4 PN controller maximum

14; Of which 10 CPs max. or IMs as DP master, 4 PN controller maximum

14; In total max. 10 CPs as DP master and PN controller, of which up to 10 IMs or CPs as DP master and up to 4 CPs as PN controller

Time of day

 

 

 

Clock

 

 

 

  • Hardware clock (real-time clock)

Yes

Yes

Yes

  • battery-backed and synchronizable

Yes

Yes

Yes

  • Resolution

1 ms

1 ms

1 ms

Runtime meter

 

 

 

  • Number

16

16

16

Clock synchronization

 

 

 

  • supported

Yes

Yes

Yes

  • to MPI, master

Yes

Yes

Yes

  • to MPI, slave

Yes

Yes

Yes

  • to DP, master

Yes

Yes

Yes

  • to DP, slave

Yes

Yes

Yes

  • in AS, master

Yes

Yes

Yes

  • in AS, slave

Yes

Yes

Yes

  • on Ethernet via NTP

No; Via CP

No; Via CP

Yes; as client

  • to IF 964 DP

No

Yes

Yes

S7 message functions

 

 

 

Number of login stations for message functions, max.

31; Max. 31 with alarm_S and alarm_D (OP's); max. 8 with alarm_8 and alarm_P (e.g. WinCC)

31; Max. 31 with alarm_S and alarm_D (OP's); max. 8 with alarm_8 and alarm_P (e.g. WinCC)

63

Symbol-related messages

Yes

Yes

Yes

SCAN procedure

Yes

Yes

Yes

Number of messages

 

 

 

  • overall, max.

512

512

512

Block related messages

Yes

Yes

Yes

Process diagnostic messages

Yes

Yes

Yes

Alarm 8-blocks

Yes

Yes

Yes

Process control messages

Yes

Yes

Yes

Test commissioning functions

 

 

 

Status/control

 

 

 

  • Status/control variable

Yes; Up to 16 variable tables

Yes; Up to 16 variable tables

Yes; Up to 16 variable tables

Forcing

 

 

 

  • Forcing

Yes

Yes

Yes

Status block

Yes; Up to 2 simultaneously

Yes; Up to 2 simultaneously

Yes

Single step

Yes

Yes

Yes

Number of breakpoints

4

4

16

Diagnostic buffer

 

 

 

  • present

Yes

Yes

Yes

  • Number of entries, max.

400

3 200

3 200

    • can be set

Yes

Yes

Yes

    • preset

120

120

120

Service data

 

 

 

  • can be read out

 

 

Yes

Communication functions

 

 

 

PG/OP communication

Yes

Yes

Yes

Data record routing

Yes

Yes

Yes

Routing

Yes; S7 routing

Yes; S7 routing

Yes; S7 routing

Global data communication

 

 

 

  • supported

Yes

Yes

Yes

  • Size of GD packets, max.

54 byte

54 byte

54 byte

S7 basic communication

 

 

 

  • supported

Yes

Yes

Yes

  • User data per job, max.

76 byte

76 byte

76 byte

S7 communication

 

 

 

  • supported

Yes

Yes

Yes

  • as server

Yes

Yes

Yes

  • as client

Yes

Yes

Yes

  • User data per job, max.

64 Kibyte

64 Kibyte

64 Kibyte

S5-compatible communication

 

 

 

  • supported

Yes; Via FC AG_SEND and AG_RECV, max. via 10 CP 443-1 or 443-5

Yes; Via FC AG_SEND and AG_RECV, max. via 10 CP 443-1 or 443-5

Yes; Via FC AG_SEND and AG_RECV, max. via 10 CP 443-1 or 443-5

  • User data per job, max.

8 Kibyte

8 Kibyte

8 Kibyte

Standard communication (FMS)

 

 

 

  • supported

Yes; Via CP and loadable FB

Yes; Via CP and loadable FB

Yes; Via CP and loadable FB

Web server

 

 

 

  • supported

No

No

Yes

  • Number of HTTP clients

 

 

5

  • User-defined websites

 

 

Yes

Open IE communication

 

 

 

  • TCP/IP

 

 

Yes; Via integrated PROFINET interface and loadable FBs

    • Number of connections, max.

 

 

62

    • Data length, max.

 

 

32 Kibyte

    • Several passive connections per port, supported

 

 

Yes

  • ISO-on-TCP (RFC1006)

Via CP 443-1 and loadable FB

Via CP 443-1 and loadable FB

Yes; Via integrated PROFINET interface or CP 443-1 Adv. and loadable FBs

    • Number of connections, max.

 

 

62

    • Data length, max.

1452 bytes via CP 443-1 Adv.

1452 bytes via CP 443-1 Adv.

32 Kibyte; 1452 bytes via CP 443-1 Adv.

  • UDP

 

 

Yes; Via integrated PROFINET interface and loadable FBs

    • Number of connections, max.

 

 

62

    • Data length, max.

 

 

1 472 byte

Number of connections

 

 

 

  • overall

32

32

64

PROFINET CBA (at set setpoint communication load)

 

 

 

  • Number of remote interconnection partners

 

 

32

  • Number of functions, master/slave

 

 

150

  • Total of all Master/Slave connections

 

 

4 500

  • Data length of all incoming connections master/slave, max.

 

 

45 000 byte

  • Data length of all outgoing connections master/slave, max.

 

 

45 000 byte

  • Number of device-internal and PROFIBUS interconnections

 

 

1 000

  • Data length of device-internal und PROFIBUS interconnections, max.

 

 

16 000 byte

  • Data length per connection, max.

 

 

2 000 byte

  • Remote interconnections with acyclic transmission

 

 

 

    • Sampling frequency: Sampling time, min.

 

 

200 ms; Depending on preset communcation load, number of interconnections and data length used

    • Number of incoming interconnections

 

 

250

    • Number of outgoing interconnections

 

 

250

    • Data length of all incoming interconnections, max.

 

 

8 000 byte

    • Data length of all outgoing interconnections, max.

 

 

8 000 byte

    • Data length per connection, max.

 

 

2 000 byte

  • Remote interconnections with cyclic transmission

 

 

 

    • Transmission frequency: Transmission interval, min.

 

 

1 ms; Depending on preset communication load, number of interconnections and data length used

    • Number of incoming interconnections

 

 

300

    • Number of outgoing interconnections

 

 

300

    • Data length of all incoming interconnections, max.

 

 

4 800 byte

    • Data length of all outgoing interconnections, max.

 

 

4 800 byte

    • Data length per connection, max.

 

 

450 byte

  • HMI variables via PROFINET (acyclic)

 

 

 

    • Number of stations that can log on for HMI variables (PN OPC/iMap)

 

 

2x PN OPC/1x iMap

    • HMI variable updating

 

 

500 ms

    • Number of HMI variables

 

 

1 000

    • Data length of all HMI variables, max.

 

 

32 000 byte

  • PROFIBUS proxy functionality

 

 

 

    • supported

 

 

Yes; 32 PROFIBUS slaves max. connectable

    • Data length per connection, max.

 

 

240 byte; Slave-dependent

1st interface

 

 

 

Type of interface

Integrated

Integrated

Integrated

Physics

RS 485 / PROFIBUS + MPI

RS 485 / PROFIBUS + MPI

RS 485 / PROFIBUS + MPI

Isolated

Yes

Yes

Yes

Power supply to interface (15 to 30 V DC), max.

150 mA

150 mA

150 mA

Number of connection resources

MPI: 32, DP: 16

MPI: 32, DP: 16

MPI: 32, DP: 16

Functionality

 

 

 

  • MPI

Yes

Yes

Yes

  • DP master

Yes

Yes

Yes

  • DP slave

Yes

Yes

Yes

MPI

 

 

 

  • Number of connections

32; if a diagnostic repeater is used on the line, the number of connection resources on the line is reduced by 1

32; if a diagnostic repeater is used on the line, the number of connection resources on the line is reduced by 1

32; if a diagnostic repeater is used on the line, the number of connection resources on the line is reduced by 1

  • Services

 

 

 

    • PG/OP communication

Yes

Yes

Yes

    • Routing

Yes

Yes

Yes

    • Global data communication

Yes

Yes

Yes

    • S7 basic communication

Yes

Yes

Yes

    • S7 communication

Yes

Yes

Yes

    • S7 communication, as client

Yes

Yes

Yes

    • S7 communication, as server

Yes

Yes

Yes

  • Transmission rate, max.

12 Mbit/s

12 Mbit/s

12 Mbit/s

DP master

 

 

 

  • Number of connections, max.

16; if a diagnostic repeater is used on the line, the number of connection resources on the line is reduced by 1

16; if a diagnostic repeater is used on the line, the number of connection resources on the line is reduced by 1

16; if a diagnostic repeater is used on the line, the number of connection resources on the line is reduced by 1

  • Services

 

 

 

    • PG/OP communication

Yes

Yes

Yes

    • Routing

Yes

Yes

Yes

    • Global data communication

No

No

No

    • S7 basic communication

Yes

Yes

Yes

    • S7 communication

Yes

Yes

Yes

    • S7 communication, as client

Yes

Yes

Yes

    • S7 communication, as server

Yes

Yes

Yes

    • Equidistance mode support

Yes

Yes

Yes

    • Isochronous mode

Yes

Yes

Yes

    • SYNC/FREEZE

Yes

Yes

Yes

    • Activation/deactivation of DP slaves

Yes

Yes

Yes

    • Direct data exchange (slave-to-slave communication)

Yes

Yes

Yes

    • DPV1

Yes

Yes

Yes

  • Transmission rate, max.

12 Mbit/s

12 Mbit/s

12 Mbit/s

  • Number of DP slaves, max.

32

32

32

  • Address area

 

 

 

    • Inputs, max.

2 Kibyte

2 Kibyte

2 Kibyte

    • Outputs, max.

2 Kibyte

2 Kibyte

2 Kibyte

  • User data per DP slave

 

 

 

    • User data per DP slave, max.

244 byte

244 byte

244 byte

    • Inputs, max.

244 byte

244 byte

244 byte

    • Outputs, max.

244 byte

244 byte

244 byte

    • Slots, max.

244

244

244

    • per slot, max.

128 byte

128 byte

128 byte

DP slave

 

 

 

  • Number of connections

16

16

16

  • Services

 

 

 

    • PG/OP communication

Yes; with interface active

Yes; with interface active

Yes; with interface active

    • S7 routing

Yes; With interface active

Yes; With interface active

Yes; With interface active

    • Global data communication

No

No

No

    • S7 basic communication

No

No

No

    • S7 communication

Yes

Yes

Yes

    • S7 communication, as client

Yes

Yes

Yes

    • S7 communication, as server

Yes

Yes

Yes

    • Direct data exchange (slave-to-slave communication)

No

No

No

    • DPV1

No

No

No

  • GSD file

http://support.automation.siemens.com/WW/view/de/113652

http://support.automation.siemens.com/WW/view/de/113652

http://support.automation.siemens.com/WW/view/de/113652

  • Transmission rate, max.

12 Mbit/s

12 Mbit/s

12 Mbit/s

  • Automatic baud rate search

No

No

No

  • Transfer memory

 

 

 

    • Inputs

244 byte

244 byte

244 byte

    • Outputs

244 byte

244 byte

244 byte

  • Address area, max.

32; Virtual slots

32; Virtual slots

32; Virtual slots

  • User data per address area, max.

32 byte

32 byte

32 byte

  • User data per address area, of which consistent, max.

32 byte

32 byte

32 byte

2nd interface

 

 

 

Type of interface

Integrated

Integrated

PROFINET

Physics

RS 485 / PROFIBUS

RS 485 / PROFIBUS

Ethernet RJ45

Isolated

Yes

Yes

Yes

Integrated switch

 

 

Yes

Number of ports

 

 

2

Power supply to interface (15 to 30 V DC), max.

150 mA

150 mA

 

automatic detection of transmission speed

 

 

Yes

Autonegotiation

 

 

Yes

Autocrossing

 

 

Yes

Media redundancy

 

 

 

  • supported

 

 

Yes

  • Switchover time on line break, typically

 

 

200 ms

  • Number of stations in the ring, max.

 

 

50

Change of IP address at runtime, supported

 

 

Yes; Assignment by higher-level IO Controller or by the user program with SFB104 "IP_CONF"

Number of connection resources

16

16

64

Functionality

 

 

 

  • DP master

Yes

Yes

No

  • DP slave

Yes

Yes

No

  • PROFINET IO Controller

 

 

Yes

  • PROFINET IO Device

 

 

Yes

  • PROFINET CBA

 

 

Yes

  • Open IE communication

 

 

Yes

  • Web server

 

 

Yes

    • Number of HTTP clients

 

 

5

  • Point-to-point connection

 

 

No

DP master

 

 

 

  • Number of connections, max.

16

16

 

  • Services

 

 

 

    • PG/OP communication

Yes

Yes

 

    • Routing

Yes

Yes

 

    • Global data communication

No

No

 

    • S7 basic communication

Yes

Yes

 

    • S7 communication

Yes

Yes

 

    • S7 communication, as client

Yes

Yes

 

    • S7 communication, as server

Yes

Yes

 

    • Equidistance mode support

Yes

Yes

 

    • Isochronous mode

Yes

Yes

 

    • SYNC/FREEZE

Yes

Yes

 

    • Activation/deactivation of DP slaves

Yes

Yes

 

    • Direct data exchange (slave-to-slave communication)

Yes

Yes

 

    • DPV1

Yes

Yes

 

  • Transmission speeds, max.

12 Mbit/s

12 Mbit/s

 

  • Number of DP slaves, max.

96

96

 

  • Address area

 

 

 

    • Inputs, max.

6 Kibyte

6 Kibyte

 

    • Outputs, max.

6 Kibyte

6 Kibyte

 

  • User data per DP slave

 

 

 

    • User data per DP slave, max.

244 byte

244 byte

 

    • Inputs, max.

244 byte

244 byte

 

    • Outputs, max.

244 byte

244 byte

 

    • Slots, max.

244

244

 

    • per slot, max.

128 byte

128 byte

 

DP slave

 

 

 

  • Number of connections

16

16

 

  • Services

 

 

 

    • Routing

Yes

Yes

 

    • Programming

Yes

Yes

 

  • GSD file

http://support.automation.siemens.com/WW/view/de/113652

http://support.automation.siemens.com/WW/view/de/113652

 

  • Transmission rate, max.

12 Mbit/s

12 Mbit/s

 

  • Transfer memory

 

 

 

    • Inputs

244 byte

244 byte

 

    • Outputs

244 byte

244 byte

 

  • Address area, max.

32

32

 

  • User data per address area, max.

32 byte

32 byte

 

  • User data per address area, of which consistent, max.

32 byte

32 byte

 

PROFINET IO Controller

 

 

 

  • Services

 

 

 

    • PG/OP communication

 

 

Yes

    • S7 routing

 

 

Yes

    • S7 communication

 

 

Yes

    • Isochronous mode

 

 

Yes; Only with IRT and the High Performance option

    • Open IE communication

 

 

Yes

  • Transmission rate, min.

 

 

10 Mbit/s

  • Transmission rate, max.

 

 

100 Mbit/s

  • Number of connectable IO devices, max.

 

 

256

  • Max. number of connectable IO devices for RT

 

 

256

    • of which in line, max.

 

 

256

  • Number of IO Devices with IRT and the option "high flexibility"

 

 

256

    • of which in line, max.

 

 

61

  • Number of IO Devices with IRT and the option "high performance", max.

 

 

64

    • of which in line, max.

 

 

64

  • IRT, supported

 

 

Yes

  • Shared device, supported

 

 

Yes

  • Prioritized startup supported

 

 

Yes

    • Number of IO Devices, max.

 

 

32

  • Activation/deactivation of IO Devices

 

 

Yes

    • Number of IO Devices that can be simultaneously activated/deactivated, max.

 

 

8

  • IO Devices changing during operation (partner ports), supported

 

 

Yes

    • Max. number of IO devices per tool

 

 

8; 8 parallel calls of the SFC 12 "D_ACT_DP" possible per line. Max. 32 IO Devices changing during operation (partner ports) are supported.

  • Device replacement without swap medium

 

 

Yes

  • Send clock times

 

 

250 μs, 500 μs, 1 ms, 2 ms, 4 ms additionally with IRT with high performance: 250 µs to 4 ms in 125 µs frame

  • Address area

 

 

 

    • Inputs, max.

 

 

8 Kibyte

    • Outputs, max.

 

 

8 Kibyte

  • User data per address area, max.

 

 

 

    • User data consistency, max.

 

 

1 024 byte

PROFINET IO device

 

 

 

  • Services

 

 

 

    • [Fehlender Merkmalstext TAK_ABT616_001_000]

 

 

Yes

    • S7 routing

 

 

Yes

    • S7 communication

 

 

Yes

    • Isochronous mode

 

 

No

    • Open IE communication

 

 

Yes

    • IRT, supported

 

 

Yes

    • Prioritized startup supported

 

 

Yes

    • Shared device, supported

 

 

Yes

    • Number of IO controllers with shared device, max.

 

 

2

  • Transfer memory

 

 

 

    • Inputs, max.

 

 

1 440 byte

    • Outputs, max.

 

 

1 440 byte

  • Submodules

 

 

 

    • Number, max.

 

 

64

    • User data per submodule, max.

 

 

1 024 byte

PROFINET CBA

 

 

 

  • acyclic transmission

 

 

Yes

  • cyclic transmission

 

 

Yes

Open IE communication

 

 

 

  • Open IE communication, supported

 

 

Yes

  • Number of connections, max.

 

 

62

  • Local port numbers used at the system end

 

 

0, 20, 21, 25, 80, 102, 135, 161, 34962, 34963, 34964, 65532, 65533, 65534, 65535

  • Keep-alive function, supported

 

 

Yes

3rd interface

 

 

 

Type of interface

 

Pluggable interface module (IF), technical specifications as for 2nd interface

Pluggable interface module (IF)

Plug-in interface modules

 

IF 964-DP (MLFB: 6ES7964-2AA04-0AB0)

IF 964-DP (MLFB: 6ES7964-2AA04-0AB0)

Physics

 

RS 485 / PROFIBUS

RS 485 / PROFIBUS

Isolated

 

Yes

Yes

Power supply to interface (15 to 30 V DC), max.

 

150 mA

150 mA

automatic detection of transmission speed

 

No

No

Number of connection resources

 

16

16

Functionality

 

 

 

  • MPI

 

No

No

  • DP master

 

Yes

Yes

  • DP slave

 

Yes

Yes

DP master

 

 

 

  • Number of connections, max.

 

16

16

  • Services

 

 

 

    • PG/OP communication

 

Yes

Yes

    • Routing

 

Yes; S7 routing

Yes; S7 routing

    • Global data communication

 

No

No

    • S7 basic communication

 

No

Yes

    • S7 communication

 

Yes

Yes

    • S7 communication, as client

 

Yes

Yes

    • S7 communication, as server

 

Yes

Yes

    • Equidistance mode support

 

Yes

Yes

    • Isochronous mode

 

Yes

Yes

    • SYNC/FREEZE

 

Yes

Yes

    • Activation/deactivation of DP slaves

 

Yes

Yes

    • Direct data exchange (slave-to-slave communication)

 

Yes

Yes

    • DPV0

 

Yes

Yes

    • DPV1

 

Yes

Yes

  • Transmission rate, max.

 

12 Mbit/s

12 Mbit/s

  • Transmission rate, min.

 

9.6 kbit/s

9.6 kbit/s

  • Number of DP slaves, max.

 

96

96

  • Address area

 

 

 

    • Inputs, max.

 

6 Kibyte

6 Kibyte

    • Outputs, max.

 

6 Kibyte

6 Kibyte

  • User data per DP slave

 

 

 

    • User data per DP slave, max.

 

244 byte

244 byte

    • Inputs, max.

 

244 byte

244 byte

    • Outputs, max.

 

244 byte

244 byte

    • Slots, max.

 

244

244

    • per slot, max.

 

128 byte

128 byte

DP slave

 

 

 

  • Number of connections

 

16

16

  • Services

 

 

 

    • PG/OP communication

 

Yes

Yes

    • S7 routing

 

Yes; With active interface

Yes; With active interface

    • Global data communication

 

No

No

    • S7 basic communication

 

No

No

    • S7 communication

 

Yes

Yes

    • S7 communication, as client

 

Yes

Yes

    • S7 communication, as server

 

Yes

Yes

    • SYNC/FREEZE

 

No

No

    • Direct data exchange (slave-to-slave communication)

 

No

No

    • DPV1

 

No

No

    • Status/control

 

Yes; When interface active

Yes; When interface active

  • GSD file

 

http://support.automation.siemens.com/WW/view/de/113652

http://support.automation.siemens.com/WW/view/de/113652

  • Transmission rate, min.

 

9.6 kbit/s

9.6 kbit/s

  • Transmission rate, max.

 

12 Mbit/s

12 Mbit/s

  • Automatic baud rate search

 

No

No

  • Transfer memory

 

 

 

    • Inputs

 

244 byte

244 byte

    • Outputs

 

244 byte

244 byte

  • Address areas, max.

 

32

32

  • User data per address area, max.

 

32 byte

32 byte

  • User data per address area, of which consistent, max.

 

32 byte

32 byte

Isochronous mode

 

 

 

Isochronous mode

Yes; For PROFIBUS only

Yes; For PROFIBUS only

Yes; Via PROFIBUS DP or PROFINET interface

Number of DP masters with isochronous mode

2

3

2

User data per isochronous slave, max.

244 byte

244 byte

244 byte

equidistance

Yes

Yes

Yes

shortest clock pulse

1 ms; 0.5 ms without use of SFC 126, 127

1 ms; 0.5 ms without use of SFC 126, 127

1 ms; 0.5 ms without use of SFC 126, 127

max. cycle

32 ms

32 ms

32 ms

CiR - Configuration in RUN

 

 

 

CiR synchronization time, basic load

100 ms

100 ms

100 ms

CiR synchronization time, time per I/O slave

15 µs; Time per I/O byte

15 µs

15 µs; Time per I/O byte

CPU/ programming

 

 

 

Configuration software

 

 

 

  • STEP 7

Yes

Yes

Yes

Programming language

 

 

 

  • STEP 7

Yes

Yes

Yes

  • LAD

Yes

Yes

Yes

  • FBD

Yes

Yes

Yes

  • STL

Yes

Yes

Yes

  • SCL

Yes

Yes

Yes

  • CFC

Yes

Yes

Yes

  • GRAPH

Yes

Yes

Yes

  • HiGraph®

Yes

Yes

Yes

Nesting levels

7

7

7

Know-how protection

 

 

 

  • User program protection/password protection

Yes

Yes

Yes

  • Block encryption

 

 

Yes

EMC

 

 

 

Emission of radio interference acc. to EN 55 011

 

 

 

  • Limit class A, for use in industrial areas

 

 

Yes

  • Limit class B, for use in residential areas

 

 

No

Dimensions

 

 

 

Required slots

1

2

2

Dimensions and weight

 

 

 

Dimensions

 

 

 

  • Width

25 mm

50 mm

50 mm

  • Height

290 mm

290 mm

290 mm

  • Depth

219 mm

219 mm

219 mm

Weight

 

 

 

  • Weight, approx.

0.7 kg

0.9 kg

900 g