6ES7 422-1FH00-0AA0 |
6ES7 422-1HH00-0AA0 |
6ES7 422-1BH11-0AA0 |
6ES7 422-1BL00-0AA0 |
6ES7 422-7BL00-0AB0 |
Supply voltages |
|
|
|
|
|
Load voltage L+ |
|
|
|
|
|
|
|
60 V |
24 V |
24 V |
24 V |
|
|
1 V |
20.4 V |
20.4 V |
20.4 V |
|
|
60 V |
28.8 V |
28.8 V |
28.8 V |
Load voltage L1 |
|
|
|
|
|
|
230 V; 120 / 230 VAC |
230 V |
|
|
|
|
79 V |
2 V |
|
|
20.4 V |
|
264 V |
264 V |
|
|
28.8 V |
Current consumption |
|
|
|
|
|
from load voltage L+ (without load), max. |
1.5 mA |
|
30 mA |
30 mA |
120 mA |
from load voltage L1 (without load), max. |
6 mA |
|
|
|
|
from backplane bus 5 V DC, max. |
400 mA |
1 A |
160 mA |
200 mA |
200 mA |
Power losses |
|
|
|
|
|
Power loss, max. |
16 W |
25 W |
7 W |
4 W |
8 W |
Digital outputs |
|
|
|
|
|
Number of digital outputs |
16 |
16; Relay |
16 |
32 |
32 |
Short-circuit protection |
Yes; Fuse 8 A, 250 V; per group |
|
Yes; Clocked electronically |
Yes; Clocked electronically |
Yes; Clocked electronically |
Limitation of inductive shutdown voltage to |
|
|
-30 V |
-27 V |
L+ (-45 V) |
Lamp load, max. |
50 W |
60 W |
10 W |
5 W |
5 W |
Output voltage |
|
|
|
|
|
|
L1 (-18.1 V) |
|
L+ (-0.5 V) |
L+ (-0.3 V) |
L+ (-0.8 V) |
Output current |
|
|
|
|
|
|
2 A |
5 A |
2 A |
0.5 A |
0.5 A |
|
10 mA |
|
5 mA |
5 mA |
5 mA |
|
|
|
2.4 A |
0.6 A |
0.6 A |
|
2.6 mA |
|
0.5 mA |
0.3 mA |
0.5 mA |
Switching frequency |
|
|
|
|
|
|
10 Hz |
10 Hz |
100 Hz |
100 Hz |
100 Hz |
|
0.5 Hz |
|
0.1 Hz |
0.5 Hz |
2 Hz |
Aggregate current of outputs (per group) |
|
|
|
|
|
|
2 A; 5 A with fan subassembly; per 4 adjacent outputs |
5 mA; 10 A with fan subassembly |
2 A; 2 adjacent outputs each |
2 A; 8 adjacent outputs each |
2 A |
Cable length |
|
|
|
|
|
|
1 000 m |
1 000 m |
1 000 m |
1 000 m |
1 000 m |
|
600 m |
600 m |
600 m |
600 m |
600 m |
Relay outputs |
|
|
|
|
|
Number of operating cycles |
|
100 000; 100,000 (AC 15 / DC 13); 3,000,000 mechanical |
|
|
|
Switching capacity of contacts |
|
|
|
|
|
|
|
5 A; 5 A (30 V DC); 5 A (230 V AC) |
|
|
|
|
|
5 A; 5 A (30 V DC); 5 A (230 V AC); 1.2 A (60 V DC); 0.2 A (125 V DC) |
|
|
|
Interrupts/diagnostics/status information |
|
|
|
|
|
Alarms |
|
|
|
|
|
|
|
|
|
|
Yes; Parameterizable |
Diagnoses |
|
|
|
|
|
|
|
|
|
|
Yes; internal/ external fault |
Isolation |
|
|
|
|
|
Isolation checked with |
1500 VAC |
1500 VAC |
500 VDC |
500 VDC |
500 VDC |
Galvanic isolation |
|
|
|
|
|
Galvanic isolation digital outputs |
|
|
|
|
|
|
4 |
2 |
8 |
32 |
8 |
|
Yes |
Yes |
Yes |
Yes |
Yes |
Dimensions and weight |
|
|
|
|
|
Dimensions |
|
|
|
|
|
|
25 mm |
25 mm |
25 mm |
25 mm |
25 mm |
|
290 mm |
290 mm |
290 mm |
290 mm |
290 mm |
|
210 mm |
210 mm |
210 mm |
210 mm |
210 mm |
Weight |
|
|
|
|
|
|
800 g |
700 g |
600 g |
600 g |
600 g |