6ES7 422-1FH00-0AA0

6ES7 422-1HH00-0AA0

6ES7 422-1BH11-0AA0

6ES7 422-1BL00-0AA0

6ES7 422-7BL00-0AB0

Supply voltages

 

 

 

 

 

Load voltage L+

 

 

 

 

 

  • Rated value (DC)

 

60 V

24 V

24 V

24 V

  • permissible range, lower limit (DC)

 

1 V

20.4 V

20.4 V

20.4 V

  • permissible range, upper limit (DC)

 

60 V

28.8 V

28.8 V

28.8 V

Load voltage L1

 

 

 

 

 

  • Rated value (AC)

230 V; 120 / 230 VAC

230 V

 

 

 

  • permissible range, lower limit (AC)

79 V

2 V

 

 

20.4 V

  • permissible range, upper limit (AC)

264 V

264 V

 

 

28.8 V

Current consumption

 

 

 

 

 

from load voltage L+ (without load), max.

1.5 mA

 

30 mA

30 mA

120 mA

from load voltage L1 (without load), max.

6 mA

 

 

 

 

from backplane bus 5 V DC, max.

400 mA

1 A

160 mA

200 mA

200 mA

Power losses

 

 

 

 

 

Power loss, max.

16 W

25 W

7 W

4 W

8 W

Digital outputs

 

 

 

 

 

Number of digital outputs

16

16; Relay

16

32

32

Short-circuit protection

Yes; Fuse 8 A, 250 V; per group

 

Yes; Clocked electronically

Yes; Clocked electronically

Yes; Clocked electronically

Limitation of inductive shutdown voltage to

 

 

-30 V

-27 V

L+ (-45 V)

Lamp load, max.

50 W

60 W

10 W

5 W

5 W

Output voltage

 

 

 

 

 

  • for signal "1", min.

L1 (-18.1 V)

 

L+ (-0.5 V)

L+ (-0.3 V)

L+ (-0.8 V)

Output current

 

 

 

 

 

  • for signal "1" rated value

2 A

5 A

2 A

0.5 A

0.5 A

  • for signal "1" permissible range for 0 to 60 °C, min.

10 mA

 

5 mA

5 mA

5 mA

  • for signal "1" permissible range for 0 to 60 °C, max.

 

 

2.4 A

0.6 A

0.6 A

  • for signal "0" residual current, max.

2.6 mA

 

0.5 mA

0.3 mA

0.5 mA

Switching frequency

 

 

 

 

 

  • with resistive load, max.

10 Hz

10 Hz

100 Hz

100 Hz

100 Hz

  • with inductive load, max.

0.5 Hz

 

0.1 Hz

0.5 Hz

2 Hz

Aggregate current of outputs (per group)

 

 

 

 

 

  • up to 60 °C, max.

2 A; 5 A with fan subassembly; per 4 adjacent outputs

5 mA; 10 A with fan subassembly

2 A; 2 adjacent outputs each

2 A; 8 adjacent outputs each

2 A

Cable length

 

 

 

 

 

  • Cable length, shielded, max.

1 000 m

1 000 m

1 000 m

1 000 m

1 000 m

  • Cable length unshielded, max.

600 m

600 m

600 m

600 m

600 m

Relay outputs

 

 

 

 

 

Number of operating cycles

 

100 000; 100,000 (AC 15 / DC 13); 3,000,000 mechanical

 

 

 

Switching capacity of contacts

 

 

 

 

 

  • with inductive load, max.

 

5 A; 5 A (30 V DC); 5 A (230 V AC)

 

 

 

  • with resistive load, max.

 

5 A; 5 A (30 V DC); 5 A (230 V AC); 1.2 A (60 V DC); 0.2 A (125 V DC)

 

 

 

Interrupts/diagnostics/status information

 

 

 

 

 

Alarms

 

 

 

 

 

  • Diagnostic alarm

 

 

 

 

Yes; Parameterizable

Diagnoses

 

 

 

 

 

  • Diagnostics

 

 

 

 

Yes; internal/ external fault

Isolation

 

 

 

 

 

Isolation checked with

1500 VAC

1500 VAC

500 VDC

500 VDC

500 VDC

Galvanic isolation

 

 

 

 

 

Galvanic isolation digital outputs

 

 

 

 

 

  • between the channels, in groups of

4

2

8

32

8

  • between the channels and the backplane bus

Yes

Yes

Yes

Yes

Yes

Dimensions and weight

 

 

 

 

 

Dimensions

 

 

 

 

 

  • Width

25 mm

25 mm

25 mm

25 mm

25 mm

  • Height

290 mm

290 mm

290 mm

290 mm

290 mm

  • Depth

210 mm

210 mm

210 mm

210 mm

210 mm

Weight

 

 

 

 

 

  • Weight, approx.

800 g

700 g

600 g

600 g

600 g