6ES7 211-0AA23-0XB0

6ES7 211-0BA23-0XB0

Supply voltages

 

 

Rated value

 

 

  • 24 V DC

Yes

 

  • permissible range, lower limit (DC)

20.4 V

 

  • permissible range, upper limit (DC)

28.8 V

 

  • 120 V AC

 

Yes

  • 230 V AC

 

Yes

  • permissible range, lower limit (AC)

 

85 V

  • permissible range, upper limit (AC)

 

264 V

  • permissible frequency range, lower limit

 

47 Hz

  • permissible frequency range, upper limit

 

63 Hz

Load voltage L+

 

 

  • Rated value (DC)

24 V

24 V

  • permissible range, lower limit (DC)

20.4 V

5 V

  • permissible range, upper limit (DC)

28.8 V

30 V

Load voltage L1

 

 

  • Rated value (AC)

 

100 V; 100 to 230 V AC

  • permissible range, lower limit (AC)

 

5 V

  • permissible range, upper limit (AC)

 

250 V

  • permissible frequency range, lower limit

 

47 Hz

  • permissible frequency range, upper limit

 

63 Hz

Current consumption

 

 

Inrush current, max.

10 A; at 28.8 V

20 A; at 264 V

from supply voltage L+, max.

450 mA; 80 to 450 mA

 

from supply voltage L1, max.

 

120 mA; 15 to 60 mA (240 V); 30 to 120 mA (120 V); output current for expansion modules (5 V DC) 340 mA

Backup battery

 

 

Battery operation

 

 

  • Backup time, max.

50 h; (min. 8 h at 40 °C); 200 days (typ.) with optional battery module

50 h; (min. 8 h at 40 °C); 200 days (typ.) with optional battery module

Memory

 

 

Number of memory modules (optional)

1; pluggable memory module, content identical with integral EEPROM; can additionally store recipes, data logs and other files

1; pluggable memory module, content identical with integral EEPROM; can additionally store recipes, data logs and other files

Data and program memory

 

 

  • Data memory, max.

2 Kibyte

2 Kibyte

  • Program memory, max.

4 Kibyte

4 Kibyte

Backup

 

 

  • present

Yes; Program: Entire program maintenance-free on integral EEPROM, programmable via CPU; data: Entire DB 1 loaded from PG/PC maintenance-free on integral EEPROM, current values of DB 1 in RAM, retentive memory bits, timers, counters, etc. maintenance-free via high-performance capacitor; optional battery for long-term buffering

Yes; Program: Entire program maintenance-free on integral EEPROM, programmable via CPU; data: Entire DB 1 loaded from PG/PC maintenance-free on integral EEPROM, current values of DB 1 in RAM, retentive memory bits, timers, counters, etc. maintenance-free via high-performance capacitor; optional battery for long-term buffering

CPU processing times

 

 

for bit operations, max.

0.22 µs

0.22 µs

Counters, timers and their retentivity

 

 

S7 counter

 

 

  • Number

256

256

  • of which retentive with battery

 

 

    • can be set

Yes; via high-performance capacitor or battery

Yes; via high-performance capacitor or battery

    • lower limit

1

1

    • upper limit

256

256

  • Counting range

 

 

    • lower limit

0

0

    • upper limit

32 767

32 767

S7 times

 

 

  • Number

256

256

  • of which retentive with battery

 

 

    • can be set

Yes; via high-performance capacitor or battery

Yes; via high-performance capacitor or battery

    • upper limit

64

64

  • Time range

 

 

    • lower limit

1 ms

1 ms

    • upper limit

54 min; 4 timers: 1 ms to 30 s; 16 timers: 10 ms to 5 min; 236 timers: 100 ms to 54 min

54 min; 4 timers: 1 ms to 30 s; 16 timers: 10 ms to 5 min; 236 timers: 100 ms to 54 min

Data areas and their retentivity

 

 

Flag

 

 

  • Number, max.

32 byte

32 byte

  • Retentivity available

Yes; M 0.0 to M 31.7

Yes; M 0.0 to M 31.7

  • of which retentive with battery

0 to 255, via high-performance capacitor or battery, adjustable

0 to 255, via high-performance capacitor or battery, adjustable

  • of which retentive without battery

0 to 112 in EEPROM, adjustable

0 to 112 in EEPROM, adjustable

Hardware configuration

 

 

Connectable programming devices/PCs

SIMATIC PG/PC, standard PC

SIMATIC PG/PC, standard PC

Connection method

 

 

Plug-in I/O terminals

No

No

1st interface

 

 

Type of interface

Integrated RS 485 interface

Integrated RS 485 interface

Physics

RS 485

RS 485

Functionality

 

 

  • MPI

Yes; as MPI slave for data exchange with MPI masters (S7-300/S7-400 CPUs, OPs, TDs, Push Button Panels); S7-200-internal CPU/CPU communications is possible in the MPI network with restrictions; transmission rates: 19.2 / 187.5 kbit/s

Yes; as MPI slave for data exchange with MPI masters (S7-300/S7-400 CPUs, OPs, TDs, Push Button Panels); S7-200-internal CPU/CPU communications is possible in the MPI network with restrictions; transmission rates: 19.2 / 187.5 kbit/s

  • PPI

Yes; with PPI protocol for programming functions, HMI functions (TD 200, OP), S7-200-internal CPU/CPU communications; transmission rates 9.6 / 19.2 / 187.5 kbit/s

Yes; with PPI protocol for programming functions, HMI functions (TD 200, OP), S7-200-internal CPU/CPU communications; transmission rates 9.6 / 19.2 / 187.5 kbit/s

  • Serial data exchange

Yes; as freely programmable interface with interrupt facility for serial data exchange with third-party devices with ASCII protocol transfer rates: 1.2 / 2.4 / 4.8 / 9.6 / 19.2 / 38.4 / 57.6 / 115.2 kbit/s; the PC / PPI cable can also be used as RS232 / RS485 converter

Yes; as freely programmable interface with interrupt facility for serial data exchange with third-party devices with ASCII protocol transfer rates: 1.2 / 2.4 / 4.8 / 9.6 / 19.2 / 38.4 / 57.6 / 115.2 kbit/s; the PC / PPI cable can also be used as RS232 / RS485 converter

MPI

 

 

  • Transmission rate, max.

187.5 kbit/s

187.5 kbit/s

  • Transmission speeds, min.

19.2 kbit/s

19.2 kbit/s

CPU/ programming

 

 

Programming language

 

 

  • LAD

Yes

Yes

  • FBD

Yes

Yes

  • STL

Yes

Yes

Command set

Bit logic instructions, compare instructions, timer instructions, counter instructions, clock instructions, transmissions instructions, table instructions, logic instructions, shift and rotate instructions, conversion instructions, program control instructions, interrupt and communications instructions, logic stack instructions, integer maths, floating-point math instructions, numerical functions

Bit logic instructions, compare instructions, timer instructions, counter instructions, clock instructions, transmissions instructions, table instructions, logic instructions, shift and rotate instructions, conversion instructions, program control instructions, interrupt and communications instructions, logic stack instructions, integer maths, floating-point math instructions, numerical functions

Program processing

free cycle (OB 1), interrupt-controller, time-controlled (1 to 255 ms)

free cycle (OB 1), interrupt-controller, time-controlled (1 to 255 ms)

Program organization

1 OB, 1 DB, 1 SDB subroutines with/without parameter transfer

1 OB, 1 DB, 1 SDB subroutines with/without parameter transfer

Number of subroutines, max.

64

64

  • User program protection/password protection

Yes; 3-stage password protection

Yes; 3-stage password protection

Digital inputs

 

 

Number of digital inputs

6; Integrated

6; Integrated

m/p-reading

Yes; optionally, per group

Yes; optionally, per group

Input voltage

 

 

  • Rated value, DC

24 V

24 V

  • for signal "0"

0 to 5 V

0 to 5 V

  • for signal "1"

min. 15 V

min. 15 V

Input current

 

 

  • for signal "1", typ.

2.5 mA

2.5 mA

Input delay (for rated value of input voltage)

 

 

  • for standard inputs

 

 

    • parameterizable

Yes; all

Yes; all

    • at "0" to "1", min.

0.2 ms

0.2 ms

    • at "0" to "1", max.

12.8 ms

12.8 ms

  • for interrupt inputs

 

 

    • parameterizable

Yes; I 0.0 to I 0.3

Yes; I 0.0 to I 0.3

  • for counter/technological functions

 

 

    • parameterizable

Yes; (E0.0 to E0.5) 30 kHz

Yes; (E0.0 to E0.5) 30 kHz

Cable length

 

 

  • Cable length, shielded, max.

500 m; Standard input: 500 m, high-speed counters: 50 m

500 m; Standard input: 500 m, high-speed counters: 50 m

  • Cable length unshielded, max.

300 m; not for high-speed signals

300 m; not for high-speed signals

Digital outputs

 

 

Number of digital outputs

4; Transistor

4; Relay

Short-circuit protection

No; to be provided externally

No; to be provided externally

Limitation of inductive shutdown voltage to

1 W

 

Switching capacity of the outputs

 

 

  • with resistive load, max.

0.75 A

2 A

  • on lamp load, max.

5 W

30 W DC; 200 W AC

Output voltage

 

 

  • for signal "1", min.

20 VDC

L+/L1

Output current

 

 

  • for signal "1" rated value

750 mA

2 A

  • for signal "0" residual current, max.

0.1 mA

0 mA

Output delay with resistive load

 

 

  • 0 to "1", max.

15 µs; of the standard outputs, max. (Q0.2 to Q0.3) 15 µs; of the pulse outputs, max. (Q0.0 to Q0.1) 2 µs

10 ms; all outputs

  • 1 to "0", max.

130 µs; of the standard outputs, max. (Q0.2 to Q0.3) 100 µs; of the pulse outputs, max. (Q0.0 to Q0.1) 10 µs

10 ms; all outputs

Parallel switching of 2 outputs

 

 

  • for increased power

Yes

No

Switching frequency

 

 

  • of the pulse outputs, with resistive load, max.

20 kHz; Q 0.0 to Q 0.1

 

Aggregate current of outputs (per group)

 

 

  • horizontal installation

 

 

    • up to 55 °C, max.

3 A

6 A

  • up to 40 °C, max.

3 A

6 A

Cable length

 

 

  • Cable length, shielded, max.

500 m

500 m

  • Cable length unshielded, max.

150 m

150 m

Relay outputs

 

 

Number of operating cycles

 

10 000 000; mechanically 10 million, at rated load voltage 100,000

Analog inputs

 

 

Number of analog potentiometers

1; Analog potentiometer; resolution 8 bit

1; Analog potentiometer; resolution 8 bit

Encoder supply

 

 

24 V encoder supply

 

 

  • 24 V

Yes; permissible range: 15.4 to 28.8 V

Yes; permissible range: 20.4 bis 28.8 V

  • Short-circuit protection

Yes; electronic at  600 mA

Yes; electronic at  600 mA

  • Output current, max.

180 mA

180 mA

Encoder

 

 

Connectable encoders

 

 

  • 2-wire BEROS

Yes

Yes

    • permissible quiescent current (2-wire BEROS), max.

1 mA

1 mA

Integrated Functions

 

 

Number of counters

4; High-speed counters (30 kHz each), 32 bits (incl. sign), can be used as up/down counters or for connecting 2 incremental encoders with 2 pulse trains offset by 90° (max. 20 kHz (A/B counters)); parameterizable enable and reset input; interrupt facilities (incl. call of subroutine with any content) when the setpoint is reached; reversal in counting direction, etc.

4; High-speed counters (30 kHz each), 32 bits (incl. sign), can be used as up/down counters or for connecting 2 incremental encoders with 2 pulse trains offset by 90° (max. 20 kHz (A/B counters)); parameterizable enable and reset input; interrupt facilities (incl. call of subroutine with any content) when the setpoint is reached; reversal in counting direction, etc.

Counter frequency (counter) max.

30 kHz

30 kHz

Number of alarm inputs

4; 4 rising edges and/or 4 falling edges

4; 4 rising edges and/or 4 falling edges

Number of pulse outputs

2; high-speed outputs, 20 kHz, with interrupt option; pulse-width and frequency modulation option

 

Limit frequency (pulse)

20 kHz

 

Galvanic isolation

 

 

Galvanic isolation digital inputs

 

 

  • between the channels

Yes

Yes

  • between the channels, in groups of

2 and 4

2 and 4

Galvanic isolation digital outputs

 

 

  • between the channels

Yes; Optocoupler

Yes; Relay

  • between the channels, in groups of

4

1 and 3

Permissible potential difference

 

 

between different circuits

500 V DC between 24 V DC  and 5 V DC

500 V DC between 24 V DC and 5 V DC;  1500 V AC between 24 V DC and 230 V AC

Environmental requirements

 

 

Environmental conditions

For further environmental conditions, see "Automation System S7-200, System Manual"

For further environmental conditions, see "Automation System S7-200, System Manual"

Operating temperature

 

 

  • vertical installation, min.

0 °C

0 °C

  • vertical installation, max.

45 °C

45 °C

  • horizontal installation, min.

0 °C

0 °C

  • horizontal installation, max.

55 °C

55 °C

Air pressure

 

 

  • permissible range, min.

860 hPa

860 hPa

  • permissible range, max.

1 080 hPa

1 080 hPa

Relative humidity

 

 

  • Operation, min.

5 %

5 %

  • Operation, max.

95 %; RH class 2 in accordance with IEC 1131-2

95 %; RH class 2 in accordance with IEC 1131-2

Degree of protection

 

 

IP20

Yes

Yes

Dimensions and weight

 

 

Dimensions

 

 

  • Width

90 mm

90 mm

  • Height

80 mm

80 mm

  • Depth

62 mm

62 mm

Weight

 

 

  • Weight, approx.

270 g

310 g