6ES7 214-1AD23-0XB0 |
6ES7 214-1BD23-0XB0 |
Supply voltages |
|
|
Rated value |
|
|
|
Yes |
|
|
20.4 V |
|
|
28.8 V |
|
|
|
Yes |
|
|
Yes |
|
|
85 V |
|
|
264 V |
|
|
47 Hz |
|
|
63 Hz |
Load voltage L+ |
|
|
|
24 V |
24 V |
|
20.4 V |
5 V |
|
28.8 V |
30 V |
Load voltage L1 |
|
|
|
|
100 V; 100 to 230 V AC |
|
|
5 V |
|
|
250 V |
|
|
47 Hz |
|
|
63 Hz |
Current consumption |
|
|
Inrush current, max. |
12 A; at 28.8 V |
20 A; at 264 V |
from supply voltage L+, max. |
700 mA; 110 to 700 mA, output current for expansion modules (DC 5 V) 660 mA |
|
from supply voltage L1, max. |
|
200 mA; 30 to 100 mA (240 V); 60 to 200 mA (120 V); output current for expansion modules (5 V DC) 600 mA |
Backup battery |
|
|
Battery operation |
|
|
|
100 h; (min. 70 h at 40 °C); 200 days (typ.) with optional battery module |
100 h; (min. 70 h at 40 °C); 200 days (typ.) with optional battery module |
Memory |
|
|
Number of memory modules (optional) |
1; pluggable memory module, content identical with integral EEPROM; can additionally store recipes, data logs and other files |
1; pluggable memory module, content identical with integral EEPROM; can additionally store recipes, data logs and other files |
Data and program memory |
|
|
|
8 Kibyte |
8 Kibyte |
|
12 Kibyte; 8 KB with active run-time edit |
12 Kibyte; 8 KB with active run-time edit |
Backup |
|
|
|
Yes; Program: Entire program maintenance-free on integral EEPROM, programmable via CPU; data: Entire DB 1 loaded from PG/PC maintenance-free on integral EEPROM, current values of DB 1 in RAM, retentive memory bits, timers, counters, etc. maintenance-free via high-performance capacitor; optional battery for long-term buffering |
Yes; Program: Entire program maintenance-free on integral EEPROM, programmable via CPU; data: Entire DB 1 loaded from PG/PC maintenance-free on integral EEPROM, current values of DB 1 in RAM, retentive memory bits, timers, counters, etc. maintenance-free via high-performance capacitor; optional battery for long-term buffering |
CPU processing times |
|
|
for bit operations, max. |
0.22 µs |
0.22 µs |
Counters, timers and their retentivity |
|
|
S7 counter |
|
|
|
256 |
256 |
|
|
|
|
Yes; via high-performance capacitor or battery |
Yes; via high-performance capacitor or battery |
|
1 |
1 |
|
256 |
256 |
|
|
|
|
0 |
0 |
|
32 767 |
32 767 |
S7 times |
|
|
|
256 |
256 |
|
|
|
|
Yes; via high-performance capacitor or battery |
Yes; via high-performance capacitor or battery |
|
64 |
64 |
|
|
|
|
1 ms |
1 ms |
|
54 min; 4 timers: 1 ms to 30 s; 16 timers: 10 ms to 5 min; 236 timers: 100 ms to 54 min |
54 min; 4 timers: 1 ms to 30 s; 16 timers: 10 ms to 5 min; 236 timers: 100 ms to 54 min |
Data areas and their retentivity |
|
|
Flag |
|
|
|
32 byte |
32 byte |
|
Yes; M 0.0 to M 31.7 |
Yes; M 0.0 to M 31.7 |
|
0 to 255, via high-performance capacitor or battery, adjustable |
0 to 255, via high-performance capacitor or battery, adjustable |
|
0 to 112 in EEPROM, adjustable |
0 to 112 in EEPROM, adjustable |
Hardware configuration |
|
|
Connectable programming devices/PCs |
SIMATIC PG/PC, standard PC |
SIMATIC PG/PC, standard PC |
Expansion devices, max. |
7; Only expansion modules of the S7-22x series can be used. Due to the limited output current, the use of expansion modules may be limited. |
7; Only expansion modules of the S7-22x series can be used. Due to the limited output current, the use of expansion modules may be limited. |
Extension of distributed I/O |
|
|
|
35; max. 28 inputs and 7 outputs (EM) or max. 0 inputs and 14 outputs (EM) |
35; max. 28 inputs and 7 outputs (EM) or max. 0 inputs and 14 outputs (EM) |
|
168; max. 94 inputs and 74 outputs (CPU + EM) |
168; max. 94 inputs and 74 outputs (CPU + EM) |
|
62; AS-Interface A/B slaves (CP 243-2) |
62; AS-Interface A/B slaves (CP 243-2) |
Connection method |
|
|
Plug-in I/O terminals |
Yes |
Yes |
1st interface |
|
|
Type of interface |
Integrated RS 485 interface |
Integrated RS 485 interface |
Physics |
RS 485 |
RS 485 |
Functionality |
|
|
|
Yes; as MPI slave for data exchange with MPI masters (S7-300/S7-400 CPUs, OPs, TDs, Push Button Panels); S7-200-internal CPU/CPU communications is possible in the MPI network with restrictions; transmission rates: 19.2 / 187.5 kbit/s |
Yes; as MPI slave for data exchange with MPI masters (S7-300/S7-400 CPUs, OPs, TDs, Push Button Panels); S7-200-internal CPU/CPU communications is possible in the MPI network with restrictions; transmission rates: 19.2 / 187.5 kbit/s |
|
Yes; with PPI protocol for programming functions, HMI functions (TD 200, OP), S7-200-internal CPU/CPU communications; transmission rates 9.6 / 19.2 / 187.5 kbit/s |
Yes; with PPI protocol for programming functions, HMI functions (TD 200, OP), S7-200-internal CPU/CPU communications; transmission rates 9.6 / 19.2 / 187.5 kbit/s |
|
Yes; as freely programmable interface with interrupt facility for serial data exchange with third-party devices with ASCII protocol transfer rates: 1.2 / 2.4 / 4.8 / 9.6 / 19.2 / 38.4 / 57.6 / 115.2 kbit/s; the PC / PPI cable can also be used as RS232 / RS485 converter |
Yes; as freely programmable interface with interrupt facility for serial data exchange with third-party devices with ASCII protocol transfer rates: 1.2 / 2.4 / 4.8 / 9.6 / 19.2 / 38.4 / 57.6 / 115.2 kbit/s; the PC / PPI cable can also be used as RS232 / RS485 converter |
MPI |
|
|
|
187.5 kbit/s |
187.5 kbit/s |
|
19.2 kbit/s |
19.2 kbit/s |
CPU/ programming |
|
|
Programming language |
|
|
|
Yes |
Yes |
|
Yes |
Yes |
|
Yes |
Yes |
Command set |
Bit logic instructions, compare instructions, timer instructions, counter instructions, clock instructions, transmissions instructions, table instructions, logic instructions, shift and rotate instructions, conversion instructions, program control instructions, interrupt and communications instructions, logic stack instructions, integer maths, floating-point math instructions, numerical functions |
Bit logic instructions, compare instructions, timer instructions, counter instructions, clock instructions, transmissions instructions, table instructions, logic instructions, shift and rotate instructions, conversion instructions, program control instructions, interrupt and communications instructions, logic stack instructions, integer maths, floating-point math instructions, numerical functions |
Program processing |
free cycle (OB 1), interrupt-controller, time-controlled (1 to 255 ms) |
free cycle (OB 1), interrupt-controller, time-controlled (1 to 255 ms) |
Program organization |
1 OB, 1 DB, 1 SDB subroutines with/without parameter transfer |
1 OB, 1 DB, 1 SDB subroutines with/without parameter transfer |
Number of subroutines, max. |
64 |
64 |
|
Yes; 3-stage password protection |
Yes; 3-stage password protection |
Digital inputs |
|
|
Number of digital inputs |
14 |
14 |
m/p-reading |
Yes; optionally, per group |
Yes; optionally, per group |
Input voltage |
|
|
|
24 V |
24 V |
|
0 to 5 V |
0 to 5 V |
|
min. 15 V |
min. 15 V |
Input current |
|
|
|
2.5 mA |
2.5 mA |
Input delay (for rated value of input voltage) |
|
|
|
|
|
|
Yes; all |
Yes; all |
|
0.2 ms |
0.2 ms |
|
12.8 ms |
12.8 ms |
|
|
|
|
Yes; I 0.0 to I 0.3 |
Yes; I 0.0 to I 0.3 |
|
|
|
|
Yes; (E0.0 to E1.5) 30 kHz |
Yes; (E0.0 to E1.5) 30 kHz |
Cable length |
|
|
|
500 m; Standard input: 500 m, high-speed counters: 50 m |
500 m; Standard input: 500 m, high-speed counters: 50 m |
|
300 m; not for high-speed signals |
300 m; not for high-speed signals |
Digital outputs |
|
|
Number of digital outputs |
10; Transistor |
10; Relay |
Short-circuit protection |
No; to be provided externally |
No; to be provided externally |
Limitation of inductive shutdown voltage to |
1 W |
|
Switching capacity of the outputs |
|
|
|
0.75 A |
2 A |
|
5 W |
200 W; 30 W DC; 200 W AC |
Output voltage |
|
|
|
20 VDC |
L+/L1 |
Output current |
|
|
|
750 mA |
2 A |
|
10 µA |
0 mA |
Output delay with resistive load |
|
|
|
15 µs; of the standard outputs, max. (Q0.2 to Q1.1) 2 µs; of the pulse outputs, max. (Q0.0 to Q0.1) 2 µs |
10 ms; all outputs |
|
130 µs; of the standard outputs, max. (Q0.2 to Q1.1) 10 µs; of the pulse outputs, max. (Q0.0 to Q0.1) 10 µs |
10 ms; all outputs |
Parallel switching of 2 outputs |
|
|
|
Yes |
No |
Switching frequency |
|
|
|
20 kHz; Q 0.0 to Q 0.1 |
1 Hz |
Aggregate current of outputs (per group) |
|
|
|
|
|
|
6 A |
10 A |
|
6 A |
10 A |
Cable length |
|
|
|
500 m |
500 m |
|
150 m |
150 m |
Relay outputs |
|
|
Number of operating cycles |
|
10 000 000; mechanically 10 million, at rated load voltage 100,000 |
Analog inputs |
|
|
Number of analog potentiometers |
2; Analog potentiometer; resolution 8 bit |
2; Analog potentiometer; resolution 8 bit |
Encoder supply |
|
|
24 V encoder supply |
|
|
|
Yes; permissible range: 15.4 to 28.8 V |
Yes; permissible range: 20.4 bis 28.8 V |
|
Yes; electronic at 280 mA |
Yes; electronic at 280 mA |
|
280 mA |
280 mA |
Encoder |
|
|
Connectable encoders |
|
|
|
Yes |
Yes |
|
1 mA |
1 mA |
Integrated Functions |
|
|
Number of counters |
6; High-speed counters (30 kHz each), 32 bits (incl. sign), can be used as up/down counters or for connecting 2 incremental encoders with 2 pulse trains offset by 90° (max. 20 kHz (A/B counters)); parameterizable enable and reset input; interrupt facilities (incl. call of subroutine with any content) when the setpoint is reached; reversal in counting direction, etc. |
6; High-speed counters (30 kHz each), 32 bits (incl. sign), can be used as up/down counters or for connecting 2 incremental encoders with 2 pulse trains offset by 90° (max. 20 kHz (A/B counters)); parameterizable enable and reset input; interrupt facilities (incl. call of subroutine with any content) when the setpoint is reached; reversal in counting direction, etc. |
Counter frequency (counter) max. |
30 kHz |
30 kHz |
Number of alarm inputs |
4; 4 rising edges and/or 4 falling edges |
4; 4 rising edges and/or 4 falling edges |
Number of pulse outputs |
2; high-speed outputs, 20 kHz, with interrupt option; pulse-width and frequency modulation option |
|
Limit frequency (pulse) |
20 kHz |
|
Galvanic isolation |
|
|
Galvanic isolation digital inputs |
|
|
|
Yes |
Yes |
|
6 and 8 |
6 and 8 |
Galvanic isolation digital outputs |
|
|
|
Yes; Optocoupler |
Yes; Relay |
|
5 |
3 and 4 |
Permissible potential difference |
|
|
between different circuits |
500 V DC between 24 V DC and 5 V DC |
500 V DC between 24 V DC and 5 V DC; 1500 V AC between 24 V DC and 230 V AC |
Environmental requirements |
|
|
Environmental conditions |
For further environmental conditions, see "Automation System S7-200, System Manual" |
For further environmental conditions, see "Automation System S7-200, System Manual" |
Operating temperature |
|
|
|
0 °C |
0 °C |
|
45 °C |
45 °C |
|
0 °C |
0 °C |
|
55 °C |
55 °C |
Air pressure |
|
|
|
860 hPa |
860 hPa |
|
1 080 hPa |
1 080 hPa |
Relative humidity |
|
|
|
5 % |
5 % |
|
95 %; RH class 2 in accordance with IEC 1131-2 |
95 %; RH class 2 in accordance with IEC 1131-2 |
Degree of protection |
|
|
IP20 |
Yes |
Yes |
Dimensions and weight |
|
|
Dimensions |
|
|
|
120.5 mm |
120.5 mm |
|
80 mm |
80 mm |
|
62 mm |
62 mm |
Weight |
|
|
|
360 g |