6ES7 222-1BD22-0XA0

6ES7 222-1BF22-0XA0

Supply voltages

 

 

Load voltage L+

 

 

  • Rated value (DC)

24 V

24 V

  • permissible range, lower limit (DC)

20.4 V

20.4 V

  • permissible range, upper limit (DC)

28.8 V

28.8 V

Current consumption

 

 

from backplane bus 5 V DC, max.

40 mA

50 mA

Power losses

 

 

Power loss, typ.

3 W

2 W

Connection method

 

 

Plug-in I/O terminals

Yes

Yes

Digital outputs

 

 

Number of digital outputs

4

8

Short-circuit protection

No

No; to be provided externally (see manual package "Setting up an S7-200")

Limitation of inductive shutdown voltage to

L+ (-48 V)

L+ (-48 V)

Output voltage

 

 

  • for signal "1", min.

20 VDC

20 V

Output current

 

 

  • for signal "1" permissible range for 0 to 55 °C, max.

5 A

750 mA

  • for signal "0" residual current, max.

30 µA

10 µA

Parallel switching of 2 outputs

 

 

  • for increased power

 

Yes

Aggregate current of outputs (per group)

 

 

  • horizontal installation

 

 

    • up to 55 °C, max.

20 A

3 A

  • up to 40 °C, max.

20 A

3 A

  • maximum current per conductor/group

5 A

3 A

Cable length

 

 

  • Cable length, shielded, max.

500 m

500 m

  • Cable length unshielded, max.

150 m

150 m

Relay outputs

 

 

Switching capacity of contacts

 

 

  • with inductive load, max.

5 A

0.75 A

  • on lamp load, max.

50 W

5 W

  • with resistive load, max.

5 A

0.75 A

Galvanic isolation

 

 

Galvanic isolation digital outputs

 

 

  • Galvanic isolation digital outputs

Yes

Yes; Optocoupler

  • between the channels, in groups of

1

4

Dimensions and weight

 

 

Dimensions

 

 

  • Width

45 mm

45 mm

  • Height

80 mm

80 mm

  • Depth

62 mm

62 mm

Weight

 

 

  • Weight, approx.

120 g

150 g


 

6ES7 222-1HD22-0XA0

6ES7 222-1HF22-0XA0

6ES7 222-1EF22-0XA0

Supply voltages

 

 

 

Load voltage L+

 

 

 

  • Rated value (DC)

24 V

24 V

 

  • permissible range, lower limit (DC)

12 V

5 V

 

  • permissible range, upper limit (DC)

30 V

30 V

 

Load voltage L1

 

 

 

  • Rated value (AC)

24 V; 24 to 230 V AC

24 V; 24 to 230 V AC

230 V; 220/230 V AC

  • permissible range, lower limit (AC)

12 V

5 V

65 V

  • permissible range, upper limit (AC)

250 V

250 V

264 V

  • permissible frequency range, lower limit

 

47 Hz

47 Hz

  • permissible frequency range, upper limit

 

63 Hz

63 Hz

Current consumption

 

 

 

from backplane bus 5 V DC, max.

30 mA

40 mA

110 mA

Digital outputs

 

 

 

  • from load voltage L+, max.

80 mA; 20 mA per switched output

72 mA; 9 mA per switched output

 

Power losses

 

 

 

Power loss, typ.

4 W

2 W

4 W

Connection method

 

 

 

Plug-in I/O terminals

Yes

Yes

Yes

Digital outputs

 

 

 

Number of digital outputs

4; Relay

8; Relay

8

Short-circuit protection

No; to be provided externally (see manual package "Setting up an S7-200")

No; to be provided externally (see manual package "Setting up an S7-200")

No; to be provided externally (see manual package "Setting up an S7-200")

Limitation of inductive shutdown voltage to

to be provided externally (see manual package "Setting up an S7-200")

to be provided externally (see manual package "Setting up an S7-200")

to be provided externally (see manual package "Setting up an S7-200")

Output voltage

 

 

 

  • for signal "1", min.

 

 

L1 (-0.9 V)

Output current

 

 

 

  • for signal "1" permissible range for 0 to 55 °C, max.

10 A

2 A

500 mA; AC

  • for signal "1" minimum load current

 

 

50 mA

  • for signal "0" residual current, max.

0 mA

0 mA

1.8 mA; at 264 V AC

Aggregate current of outputs (per group)

 

 

 

  • horizontal installation

 

 

 

    • up to 55 °C, max.

20 A

8 A

0.5 A

  • up to 40 °C, max.

40 A

8 A

0.5 A

  • maximum current per conductor/group

10 A

8 A

0.5 A

Cable length

 

 

 

  • Cable length, shielded, max.

500 m

500 m

500 m

  • Cable length unshielded, max.

150 m

150 m

150 m

Relay outputs

 

 

 

Number of operating cycles

30 000 000; mechanically 30 million, at rated load voltage 30,000

10 000 000; mechanically 10 million, at rated load voltage 100,000

 

Switching capacity of contacts

 

 

 

  • with inductive load, max.

3 A; 2 A (DC), 3 A (AC)

2 A

0.5 A

  • on lamp load, max.

1 000 W; 100/1000 W (DC/AC)

200 W; 30 W DC; 200 W AC

60 W

  • with resistive load, max.

10 A

2 A

0.5 A

Galvanic isolation

 

 

 

Galvanic isolation digital outputs

 

 

 

  • Galvanic isolation digital outputs

Yes; Relay

Yes; Relay

Yes; Optocoupler

  • between the channels, in groups of

1; 4 groups

4

1; 8 groups

Dimensions and weight

 

 

 

Dimensions

 

 

 

  • Width

45 mm

45 mm

71.2 mm

  • Height

80 mm

80 mm

80 mm

  • Depth

62 mm

62 mm

62 mm

Weight

 

 

 

  • Weight, approx.

150 g

170 g

170 g