6ES7 223-1BF22-0XA0 |
6ES7 223-1BH22-0XA0 |
6ES7 223-1BL22-0XA0 |
6ES7 223-1BM22-0XA0 |
Supply voltages |
|
|
|
|
Load voltage L+ |
|
|
|
|
|
24 V |
24 V |
24 V |
24 V |
|
20.4 V |
20.4 V |
20.4 V |
20.4 V |
|
28.8 V |
28.8 V |
28.8 V |
28.8 V |
Current consumption |
|
|
|
|
from backplane bus 5 V DC, max. |
40 mA |
80 mA |
160 mA |
240 mA |
from sensor current supply or external current supply (24 V DC), max. |
|
|
|
128 mA; ON: 4ma/Input |
Power losses |
|
|
|
|
Power loss, typ. |
2 W |
3 W |
6 W |
9 W |
Connection method |
|
|
|
|
Plug-in I/O terminals |
Yes |
Yes |
Yes |
Yes |
Digital inputs |
|
|
|
|
Number of digital inputs |
4 |
8 |
16 |
32 |
Input voltage |
|
|
|
|
|
24 V |
24 V |
24 V |
24 V |
|
0 to 5 V |
0 to 5 V |
0 to 5 V |
0 to 5 V |
|
15 to 30 VDC |
15 to 30 VDC |
15 to 30 VDC |
15 to 30 VDC |
Input current |
|
|
|
|
|
4 mA |
4 mA |
4 mA |
4 mA |
Input delay (for rated value of input voltage) |
|
|
|
|
|
|
|
|
|
|
4.5 ms |
4.5 ms |
4.5 ms |
4.5 ms |
Digital outputs |
|
|
|
|
Number of digital outputs |
4 |
8 |
16 |
32 |
Short-circuit protection |
No; to be provided externally |
No; to be provided externally |
No; to be provided externally |
No; to be provided externally |
Limitation of inductive shutdown voltage to |
L+ (-48 V) |
L+ (-48 V) |
L+ (-48 V) |
L+ (-48 V) |
Output voltage |
|
|
|
|
|
0.1 V |
0.1 V |
0.1 V |
0.1 V |
|
20 V |
20 V |
20 V |
20 V |
Output current |
|
|
|
|
|
750 mA |
750 mA |
750 mA |
750 mA |
Aggregate current of outputs (per group) |
|
|
|
|
|
3 A |
3 A |
3 A; 3 / 3 / 6 |
0.75 A; 10 A per group |
Cable length |
|
|
|
|
|
500 m |
500 m |
500 m |
500 m |
|
150 m |
150 m |
150 m |
150 m |
Relay outputs |
|
|
|
|
Switching capacity of contacts |
|
|
|
|
|
0.75 A; each output |
0.75 A; each output |
0.75 A; each output |
0.75 A; each output |
|
5 W |
5 W |
5 W |
5 W |
|
0.75 A; each output |
0.75 A; each output |
0.75 A; each output |
0.75 A; each output |
Encoder |
|
|
|
|
Connectable encoders |
|
|
|
|
|
Yes |
Yes |
Yes |
Yes |
|
1 mA |
1 mA |
1 mA |
1 mA |
Isolation |
|
|
|
|
Isolation checked with |
500 V AC |
500 V AC |
500 V AC |
500 V AC |
Galvanic isolation |
|
|
|
|
Galvanic isolation digital inputs |
|
|
|
|
|
Yes; Optocoupler |
Yes; Optocoupler |
Yes; Optocoupler |
Yes; Optocoupler |
|
4 |
4 |
4 |
16; 2 groups with 16 inputs each |
Galvanic isolation digital outputs |
|
|
|
|
|
Yes; Optocoupler |
Yes; Optocoupler |
Yes; Optocoupler |
Yes; Optocoupler |
|
4 |
4 |
4; 4 / 4 / 8 |
16; 2 groups with 16 outputs each |
Dimensions and weight |
|
|
|
|
Dimensions |
|
|
|
|
|
46 mm |
71.2 mm |
137.5 mm |
196 mm |
|
80 mm |
80 mm |
80 mm |
80 mm |
|
62 mm |
62 mm |
62 mm |
62 mm |
Weight |
|
|
|
|
|
160 g |
200 g |
360 g |
500 g |
|
6ES7 223-1HF22-0XA0 |
6ES7 223-1PH22-0XA0 |
6ES7 223-1PL22-0XA0 |
6ES7 223-1PM22-0XA0 |
Supply voltages |
|
|
|
|
Load voltage L+ |
|
|
|
|
|
24 V |
24 V |
24 V |
24 V |
|
5 V |
5 V |
5 V |
5 V |
|
30 V |
30 V |
30 V |
30 V |
Load voltage L1 |
|
|
|
|
|
230 V; 24 to 230 V AC |
230 V; 24 to 230 V AC |
230 V; 24 to 230 V AC |
230 V; 24 to 230 V AC |
|
5 V |
5 V |
5 V |
5 V |
|
250 V |
250 V |
250 V |
250 V |
Current consumption |
|
|
|
|
from backplane bus 5 V DC, max. |
40 mA |
80 mA |
150 mA |
205 mA |
from coil current, max. |
9 mA; for each output on signal "1" |
9 mA; for each output on signal "1" |
9 mA; for each output on signal "1" |
9 mA; for each output on signal "1" |
from sensor current supply or external current supply (24 V DC), max. |
72 mA |
72 mA |
72 mA |
128 mA |
Power losses |
|
|
|
|
Power loss, typ. |
2 W |
3 W |
6 W |
13 W |
Connection method |
|
|
|
|
Plug-in I/O terminals |
Yes |
Yes |
Yes |
Yes |
Digital inputs |
|
|
|
|
Number of digital inputs |
4 |
8 |
16 |
32 |
Input voltage |
|
|
|
|
|
24 V |
24 V |
24 V |
24 V |
|
0 to 5 V |
0 to 5 V |
0 to 5 V |
0 to 5 V |
|
15 to 30 VDC |
15 to 30 VDC |
15 to 30 VDC |
15 to 30 VDC |
Input current |
|
|
|
|
|
4 mA |
4 mA |
4 mA |
4 mA |
Input delay (for rated value of input voltage) |
|
|
|
|
|
|
|
|
|
|
4.5 ms |
4.5 ms |
4.5 ms |
4.5 ms |
Digital outputs |
|
|
|
|
Number of digital outputs |
4; Relay |
8; Relay |
16; Relay |
32; Relay |
Short-circuit protection |
No; to be provided externally |
No; to be provided externally |
No; to be provided externally |
No; to be provided externally |
Output voltage |
|
|
|
|
|
0.1 V; with 10 kOhm load |
0.1 V; with 10 kOhm load |
0.1 V; with 10 kOhm load |
0.1 V; with 10 kOhm load |
|
L+/L1 |
L+/L1 |
L+/L1 |
L+/L1 |
Output current |
|
|
|
|
|
2 000 mA |
2 000 mA |
2 000 mA |
2 000 mA |
Aggregate current of outputs (per group) |
|
|
|
|
|
8 A |
8 A |
8 A |
2 A; 10 A per group |
Cable length |
|
|
|
|
|
500 m |
500 m |
500 m |
500 m |
|
150 m |
150 m |
150 m |
150 m |
Relay outputs |
|
|
|
|
Number of operating cycles |
10 000 000; mechanically 10 million, at rated load voltage 100,000 |
10 000 000; mechanically 10 million, at rated load voltage 100,000 |
10 000 000; mechanically 10 million, at rated load voltage 100,000 |
10 000 000; mechanically 10 million, at rated load voltage 100,000 |
Switching capacity of contacts |
|
|
|
|
|
0.75 A; each output |
0.75 A; each output |
0.75 A; each output |
0.75 A; each output |
|
200 W; 30 W DC; 200 W AC |
200 W; 30 W DC; 200 W AC |
200 W; 30 W DC; 200 W AC |
200 W; 30 W DC; 200 W AC |
|
0.75 A; each output |
0.75 A; each output |
0.75 A; each output |
2 A; each output |
Encoder |
|
|
|
|
Connectable encoders |
|
|
|
|
|
Yes |
Yes |
Yes |
Yes |
|
1 mA |
1 mA |
1 mA |
1 mA |
Isolation |
|
|
|
|
Isolation checked with |
500 V AC |
500 V AC |
500 V AC |
500 V AC |
Galvanic isolation |
|
|
|
|
Galvanic isolation digital inputs |
|
|
|
|
|
Yes; Optocoupler |
Yes; Optocoupler |
Yes; Optocoupler |
Yes; Optocoupler |
|
4 |
4 |
8 |
16 |
Galvanic isolation digital outputs |
|
|
|
|
|
Yes; Relay |
Yes; Relay |
Yes; Relay |
Yes; Relay |
|
4 |
4 |
4 |
11; 11/11/10 |
Dimensions and weight |
|
|
|
|
Dimensions |
|
|
|
|
|
46 mm |
71.2 mm |
137.5 mm |
196 mm |
|
80 mm |
80 mm |
80 mm |
80 mm |
|
62 mm |
62 mm |
62 mm |
62 mm |
Weight |
|
|
|
|
|
160 g |
300 g |
400 g |
580 g |