6ES7 223-1BF22-0XA0

6ES7 223-1BH22-0XA0

6ES7 223-1BL22-0XA0

6ES7 223-1BM22-0XA0

Supply voltages

 

 

 

 

Load voltage L+

 

 

 

 

  • Rated value (DC)

24 V

24 V

24 V

24 V

  • permissible range, lower limit (DC)

20.4 V

20.4 V

20.4 V

20.4 V

  • permissible range, upper limit (DC)

28.8 V

28.8 V

28.8 V

28.8 V

Current consumption

 

 

 

 

from backplane bus 5 V DC, max.

40 mA

80 mA

160 mA

240 mA

from sensor current supply or external current supply (24 V DC), max.

 

 

 

128 mA; ON: 4ma/Input

Power losses

 

 

 

 

Power loss, typ.

2 W

3 W

6 W

9 W

Connection method

 

 

 

 

Plug-in I/O terminals

Yes

Yes

Yes

Yes

Digital inputs

 

 

 

 

Number of digital inputs

4

8

16

32

Input voltage

 

 

 

 

  • Rated value, DC

24 V

24 V

24 V

24 V

  • for signal "0"

0 to 5 V

0 to 5 V

0 to 5 V

0 to 5 V

  • for signal "1"

15 to 30 VDC

15 to 30 VDC

15 to 30 VDC

15 to 30 VDC

Input current

 

 

 

 

  • for signal "1", typ.

4 mA

4 mA

4 mA

4 mA

Input delay (for rated value of input voltage)

 

 

 

 

  • for standard inputs

 

 

 

 

    • at "0" to "1", max.

4.5 ms

4.5 ms

4.5 ms

4.5 ms

Digital outputs

 

 

 

 

Number of digital outputs

4

8

16

32

Short-circuit protection

No; to be provided externally

No; to be provided externally

No; to be provided externally

No; to be provided externally

Limitation of inductive shutdown voltage to

L+ (-48 V)

L+ (-48 V)

L+ (-48 V)

L+ (-48 V)

Output voltage

 

 

 

 

  • for signal "0" (DC), max.

0.1 V

0.1 V

0.1 V

0.1 V

  • for signal "1", min.

20 V

20 V

20 V

20 V

Output current

 

 

 

 

  • for signal "1" rated value

750 mA

750 mA

750 mA

750 mA

Aggregate current of outputs (per group)

 

 

 

 

  • maximum current per conductor/group

3 A

3 A

3 A; 3 / 3 / 6

0.75 A; 10 A per group

Cable length

 

 

 

 

  • Cable length, shielded, max.

500 m

500 m

500 m

500 m

  • Cable length unshielded, max.

150 m

150 m

150 m

150 m

Relay outputs

 

 

 

 

Switching capacity of contacts

 

 

 

 

  • with inductive load, max.

0.75 A; each output

0.75 A; each output

0.75 A; each output

0.75 A; each output

  • on lamp load, max.

5 W

5 W

5 W

5 W

  • with resistive load, max.

0.75 A; each output

0.75 A; each output

0.75 A; each output

0.75 A; each output

Encoder

 

 

 

 

Connectable encoders

 

 

 

 

  • 2-wire BEROS

Yes

Yes

Yes

Yes

    • permissible quiescent current (2-wire BEROS), max.

1 mA

1 mA

1 mA

1 mA

Isolation

 

 

 

 

Isolation checked with

500 V AC

500 V AC

500 V AC

500 V AC

Galvanic isolation

 

 

 

 

Galvanic isolation digital inputs

 

 

 

 

  • Galvanic isolation digital inputs

Yes; Optocoupler

Yes; Optocoupler

Yes; Optocoupler

Yes; Optocoupler

  • between the channels, in groups of

4

4

4

16; 2 groups with 16 inputs each

Galvanic isolation digital outputs

 

 

 

 

  • Galvanic isolation digital outputs

Yes; Optocoupler

Yes; Optocoupler

Yes; Optocoupler

Yes; Optocoupler

  • between the channels, in groups of

4

4

4; 4 / 4 / 8

16; 2 groups with 16 outputs each

Dimensions and weight

 

 

 

 

Dimensions

 

 

 

 

  • Width

46 mm

71.2 mm

137.5 mm

196 mm

  • Height

80 mm

80 mm

80 mm

80 mm

  • Depth

62 mm

62 mm

62 mm

62 mm

Weight

 

 

 

 

  • Weight, approx.

160 g

200 g

360 g

500 g


 

6ES7 223-1HF22-0XA0

6ES7 223-1PH22-0XA0

6ES7 223-1PL22-0XA0

6ES7 223-1PM22-0XA0

Supply voltages

 

 

 

 

Load voltage L+

 

 

 

 

  • Rated value (DC)

24 V

24 V

24 V

24 V

  • permissible range, lower limit (DC)

5 V

5 V

5 V

5 V

  • permissible range, upper limit (DC)

30 V

30 V

30 V

30 V

Load voltage L1

 

 

 

 

  • Rated value (AC)

230 V; 24 to 230 V AC

230 V; 24 to 230 V AC

230 V; 24 to 230 V AC

230 V; 24 to 230 V AC

  • permissible range, lower limit (AC)

5 V

5 V

5 V

5 V

  • permissible range, upper limit (AC)

250 V

250 V

250 V

250 V

Current consumption

 

 

 

 

from backplane bus 5 V DC, max.

40 mA

80 mA

150 mA

205 mA

from coil current, max.

9 mA; for each output on signal "1"

9 mA; for each output on signal "1"

9 mA; for each output on signal "1"

9 mA; for each output on signal "1"

from sensor current supply or external current supply (24 V DC), max.

72 mA

72 mA

72 mA

128 mA

Power losses

 

 

 

 

Power loss, typ.

2 W

3 W

6 W

13 W

Connection method

 

 

 

 

Plug-in I/O terminals

Yes

Yes

Yes

Yes

Digital inputs

 

 

 

 

Number of digital inputs

4

8

16

32

Input voltage

 

 

 

 

  • Rated value, DC

24 V

24 V

24 V

24 V

  • for signal "0"

0 to 5 V

0 to 5 V

0 to 5 V

0 to 5 V

  • for signal "1"

15 to 30 VDC

15 to 30 VDC

15 to 30 VDC

15 to 30 VDC

Input current

 

 

 

 

  • for signal "1", typ.

4 mA

4 mA

4 mA

4 mA

Input delay (for rated value of input voltage)

 

 

 

 

  • for standard inputs

 

 

 

 

    • at "0" to "1", max.

4.5 ms

4.5 ms

4.5 ms

4.5 ms

Digital outputs

 

 

 

 

Number of digital outputs

4; Relay

8; Relay

16; Relay

32; Relay

Short-circuit protection

No; to be provided externally

No; to be provided externally

No; to be provided externally

No; to be provided externally

Output voltage

 

 

 

 

  • for signal "0" (DC), max.

0.1 V; with 10 kOhm load

0.1 V; with 10 kOhm load

0.1 V; with 10 kOhm load

0.1 V; with 10 kOhm load

  • for signal "1", min.

L+/L1

L+/L1

L+/L1

L+/L1

Output current

 

 

 

 

  • for signal "1" rated value

2 000 mA

2 000 mA

2 000 mA

2 000 mA

Aggregate current of outputs (per group)

 

 

 

 

  • maximum current per conductor/group

8 A

8 A

8 A

2 A; 10 A per group

Cable length

 

 

 

 

  • Cable length, shielded, max.

500 m

500 m

500 m

500 m

  • Cable length unshielded, max.

150 m

150 m

150 m

150 m

Relay outputs

 

 

 

 

Number of operating cycles

10 000 000; mechanically 10 million, at rated load voltage 100,000

10 000 000; mechanically 10 million, at rated load voltage 100,000

10 000 000; mechanically 10 million, at rated load voltage 100,000

10 000 000; mechanically 10 million, at rated load voltage 100,000

Switching capacity of contacts

 

 

 

 

  • with inductive load, max.

0.75 A; each output

0.75 A; each output

0.75 A; each output

0.75 A; each output

  • on lamp load, max.

200 W; 30 W DC; 200 W AC

200 W; 30 W DC; 200 W AC

200 W; 30 W DC; 200 W AC

200 W; 30 W DC; 200 W AC

  • with resistive load, max.

0.75 A; each output

0.75 A; each output

0.75 A; each output

2 A; each output

Encoder

 

 

 

 

Connectable encoders

 

 

 

 

  • 2-wire BEROS

Yes

Yes

Yes

Yes

    • permissible quiescent current (2-wire BEROS), max.

1 mA

1 mA

1 mA

1 mA

Isolation

 

 

 

 

Isolation checked with

500 V AC

500 V AC

500 V AC

500 V AC

Galvanic isolation

 

 

 

 

Galvanic isolation digital inputs

 

 

 

 

  • Galvanic isolation digital inputs

Yes; Optocoupler

Yes; Optocoupler

Yes; Optocoupler

Yes; Optocoupler

  • between the channels, in groups of

4

4

8

16

Galvanic isolation digital outputs

 

 

 

 

  • Galvanic isolation digital outputs

Yes; Relay

Yes; Relay

Yes; Relay

Yes; Relay

  • between the channels, in groups of

4

4

4

11; 11/11/10

Dimensions and weight

 

 

 

 

Dimensions

 

 

 

 

  • Width

46 mm

71.2 mm

137.5 mm

196 mm

  • Height

80 mm

80 mm

80 mm

80 mm

  • Depth

62 mm

62 mm

62 mm

62 mm

Weight

 

 

 

 

  • Weight, approx.

160 g

300 g

400 g

580 g