6ES7 231-0HC22-0XA0

6ES7 231-0HF22-0XA0

Current consumption

 

 

from load voltage L+ (without load), max.

60 mA

60 mA

from backplane bus 5 V DC, max.

20 mA

20 mA

Power losses

 

 

Power loss, typ.

2 W

2 W

Connection method

 

 

Plug-in I/O terminals

No

No

Analog inputs

 

 

Number of analog inputs

4; Difference

8; Difference

Cable length, shielded, max.

100 m; to the sensor

100 m; to the sensor

Input ranges (rated values), voltages

 

 

  • 0 to +5 V

Yes

Yes

  • 0 to +10 V

Yes

Yes

  • -2.5 V to +2.5 V

Yes

Yes

  • -5 V to +5 V

Yes

Yes

  • -80 mV to +80 mV

 

No

Input ranges (rated values), currents

 

 

  • 0 to 20 mA

Yes

Yes; for channels 6 and 7 only

Input ranges (rated values), thermoelements

 

 

  • Type E

 

No

  • Type J

 

No

  • Type K

 

No

  • Type N

 

No

  • Type R

 

No

  • Type S

 

No

  • Type T

 

No

Input ranges (rated values), resistance thermometers

 

 

  • Cu 10

 

No

  • Ni 10

 

No

  • Ni 1000

 

No

  • Ni 120

 

No

  • Pt 100

 

No

  • Pt 1000

 

No

  • Pt 10000

 

No

  • Pt 200

 

No

  • Pt 500

 

No

Input ranges (rated values), resistors

 

 

  • 0 to 150 ohms

 

No

  • 0 to 300 ohms

 

No

  • 0 to 600 ohms

 

No

Voltage input

 

 

  • permissible input voltage for voltage input (destruction limit), max.

30 V

30 V

Current input

 

 

  • permissible input current for current input (destruction limit), max.

32 mA

40 mA

Characteristic linearization

 

 

  • for voltage measurement

No

No

  • for current measurement

No

No

Temperature compensation

 

 

  • Temperature compensation parameterizable

No

No

Analog value creation

 

 

Integrations and conversion time/ resolution per channel

 

 

  • Resolution with overrange (bit including sign), max.

12 bit

12 bit

  • Interference voltage suppression for interference frequency f1 in Hz

40 dB, DC to 60 V for interference frequency 50 / 60 Hz

40 dB, DC up to 60 V for interference frequency

  • Conversion time (per channel)

250 µs

250 µs

Displayable conversion value range

 

 

  • bipolar signals

-32000 to +32000

-32000 to +32000

  • unipolar signals

0 to 32000

0 to 32000

Errors/accuracies

 

 

Interference voltage suppression for f = n x (fl +/- 1%), fl = interference frequency

 

 

  • common mode voltage, max.

12 V

12 V

Galvanic isolation

 

 

Galvanic isolation analog inputs

 

 

  • Galvanic isolation analog inputs

No

No

Dimensions and weight

 

 

Dimensions

 

 

  • Width

71.2 mm

71.2 mm

  • Height

80 mm

80 mm

  • Depth

62 mm

62 mm

Weight

 

 

  • Weight, approx.

183 g

190 g