6ES7 231-7PB22-0XA0 |
6ES7 231-7PC22-0XA0 |
Current consumption |
|
|
from load voltage L+ (without load), max. |
60 mA |
60 mA |
from backplane bus 5 V DC, max. |
87 mA |
87 mA |
Power losses |
|
|
Power loss, typ. |
1.8 W; Sensor: 1 mW |
1.8 W; Sensor: 1 mW |
Connection method |
|
|
Plug-in I/O terminals |
No |
No |
Analog inputs |
|
|
Number of analog inputs |
2 |
4 |
Cable length, shielded, max. |
100 m; to the sensor |
100 m; to the sensor |
Loop resistance cable |
20 Ω; max. 2.7 Ohm for Cu |
20 Ω; max. 2.7 Ohm for Cu |
Updating time (all channels) |
405 ms; 700 ms with Pt10000 |
810 ms; 1400 ms with Pt10000 |
Input ranges (rated values), resistance thermometers |
|
|
|
Yes |
Yes |
|
Yes |
Yes |
|
Yes |
Yes |
|
Yes |
Yes |
|
Yes |
Yes |
|
Yes |
Yes |
|
Yes |
Yes |
|
Yes |
Yes |
|
Yes |
Yes |
Input ranges (rated values), resistors |
|
|
|
Yes |
Yes |
|
Yes |
Yes |
|
Yes |
Yes |
Voltage input |
|
|
|
30 V; 30 V DC (probe), 5 V DC (source) |
30 V; 30 V DC (probe), 5 V DC (source) |
Analog value creation |
|
|
Measurement principle |
Sigma Delta |
Sigma Delta |
Integrations and conversion time/ resolution per channel |
|
|
|
16 bit; Temperature 0.1 °C / 0.1 °F |
16 bit; Temperature 0.1 °C / 0.1 °F |
|
85 dB at 50 / 60 / 400 Hz |
85 dB at 50 / 60 / 400 Hz |
Displayable conversion value range |
|
|
|
-27,648 to +27,648 |
-27,648 to +27,648 |
Errors/accuracies |
|
|
Repeat accuracy in settled status at 25 °C (relative to input area) |
+/- 0,05 % |
+/- 0,05 % |
Operational limit in overall temperature range |
|
|
|
+/- 0,1 % |
+/- 0,1 % |
Interference voltage suppression for f = n x (fl +/- 1%), fl = interference frequency |
|
|
|
0 V |
0 V |
|
120 dB; at 120 V AC |
120 dB; at 120 V AC |
Galvanic isolation |
|
|
Galvanic isolation analog inputs |
|
|
|
Yes |
Yes |
Dimensions and weight |
|
|
Dimensions |
|
|
|
71.2 mm |
71.2 mm |
|
80 mm |
80 mm |
|
62 mm |
62 mm |
Weight |
|
|
|
210 g |
210 g |