6ES7 331-7RD00-0AB0 |
6ES7 331-7SF00-0AB0 |
Supply voltages |
|
|
Load voltage L+ |
|
|
|
24 V |
24 V |
Power supply to the transmitters |
|
|
|
Yes |
|
|
13 V; at 22 mA |
|
|
25.2 V |
|
Current consumption |
|
|
from backplane bus 5 V DC, max. |
60 mA |
120 mA |
from supply voltage L+, max. |
150 mA |
|
Power losses |
|
|
Power loss, typ. |
3 W |
0.6 W |
Connection method |
|
|
required front connector |
20-pin |
20-pin |
Analog inputs |
|
|
Number of analog inputs |
4 |
8; 8x thermocouples; 4x RTD thermal sensors |
Cable length, shielded, max. |
200 m |
200 m; TC: 50m |
Input ranges (rated values), currents |
|
|
|
Yes |
|
|
Yes |
|
Input ranges (rated values), thermoelements |
|
|
|
|
Yes |
|
|
Yes |
|
|
Yes |
|
|
Yes |
|
|
Yes |
|
|
Yes |
|
|
Yes |
|
|
Yes |
|
|
Yes |
|
|
Yes |
Input ranges (rated values), resistance thermometers |
|
|
|
|
Yes |
|
|
Yes |
|
|
Yes |
Current input |
|
|
|
40 mA |
|
Analog value creation |
|
|
Measurement principle |
Sigma Delta |
Sigma Delta |
Integrations and conversion time/ resolution per channel |
|
|
|
16 bit; 10 to 15 bits + sign |
16 bit; 10 to 15 bits + sign |
|
Yes; 2.5 to 100 ms |
Yes; 2.5 to 100 ms |
|
10 to 400 Hz |
10 to 400 Hz |
Encoder |
|
|
Connection of signal encoders |
|
|
|
Yes |
Yes |
|
Yes |
Yes |
Ex(i) characteristics |
|
|
Max. values of input circuits (per channel) |
|
|
|
90 nF |
43 µF |
|
68.5 mA |
28.8 mA |
|
7.5 mH |
40 mH |
|
431 mW |
41.4 mW |
|
50 Ω |
|
|
25.2 V |
5.9 V |
Errors/accuracies |
|
|
Temperature error (relative to input area) |
|
Temperature error: 0.001 to 0.002%/K |
Operational limit in overall temperature range |
|
|
|
+/- 0,45 % |
|
|
|
0.09 to 0.04% |
Basic error limit (operational limit at 25 °C) |
|
|
|
+/- 0,1 % |
|
|
|
+/- 0,1 % |
Interference voltage suppression for f = n x (fl +/- 1%), fl = interference frequency |
|
|
|
60 dB |
60 dB |
|
130 dB |
130 dB |
Interrupts/diagnostics/status information |
|
|
Diagnoses |
|
|
|
Yes |
Yes |
|
Yes |
Yes |
|
Yes |
Yes |
|
Yes |
Yes |
Galvanic isolation |
|
|
Galvanic isolation analog inputs |
|
|
|
Yes |
Yes |
Permissible potential difference |
|
|
between the inputs (UCM) |
60 V DC/30 V AC when used in the hazardous area; 400 V DC/250 V AC when used in the NON-hazardous area |
60 V DC/30 V AC when used in the hazardous area; 400 V DC/250 V AC when used in the NON-hazardous area |
between inputs and MANA (UCM) |
60 V DC/30 V AC when used in the hazardous area; 400 V DC/250 V AC when used in the NON-hazardous area |
60 V DC/30 V AC when used in the hazardous area; 400 V DC/250 V AC when used in the NON-hazardous area |
Standards, approvals, certificates |
|
|
Type of protection acc. to EN 50020 (CENELEC) |
[EEx ib] IIC |
[EEx ib] IIC |
Type of protection acc. to FM |
Class I, Division 2, Group A, B, C, D T4 |
Class I, Division 2, Group A, B, C, D T4 |
Test number PTB |
Ex-96.D.2092X |
Ex-96.D.2108X |
Dimensions and weight |
|
|
Weight |
|
|
|
290 g |
210 g |