6ES7 153-2BA02-0XB0 |
Power supply |
|
Input current |
|
|
650 mA |
Output voltage |
|
|
Yes |
Output current |
|
|
1.5 A |
Supply voltages |
|
Rated value |
|
|
Yes |
|
20.4 V |
|
28.8 V |
external protection for supply cables (recommendation) |
2.5 A |
Mains buffering |
|
|
5 ms |
Current consumption |
|
Current consumption, max. |
600 mA |
Inrush current, typ. |
3 A |
I²t |
0.1 A²·s |
Power losses |
|
Power loss, typ. |
5.5 W |
Address area |
|
Addressing volume |
|
|
244 byte |
|
244 byte |
Hardware configuration |
|
Number of modules per DP slave interface, max. |
12 |
Communication functions |
|
Bus protocol/transmission protocol |
PROFIBUS DP to EN 50170 |
Interfaces |
|
PROFIBUS DP, output current, max. |
70 mA |
Interface physics, RS 485 |
Yes |
Interface physics, FOC |
No |
Connection method |
|
PROFIBUS DP |
9-pin sub D |
PROFIBUS DP |
|
Transmission procedure |
RS 485 |
Transmission rate, max. |
12 Mbit/s |
Node addresses |
1 to 125 permitted |
Automatic detection of transmission speed |
Yes |
SYNC capability |
Yes |
FREECE capability |
Yes |
Direct data exchange (slave-to-slave communication) |
Yes; Sender |
1st interface |
|
DP slave |
|
|
SI04801.GSG |
|
Yes |
CPU/ programming |
|
Configuration software |
|
|
Yes; STEP 7 / COM PROFIBUS / non-Siemens tools via GSD file |
Time stamping |
|
Accuracy |
1 ms; 1ms at up to 8 modules; 10ms at up to 12 modules |
Number of message buffers |
15 |
Messages per message buffer |
20 |
Number of stampable digital inputs, max. |
128; Max. 128 signals/station; max. 32 signals/slot |
Time format |
RFC 1119 |
Time resolution |
0.466 ns |
Time interval for transmitting the message buffer if a message is present |
1 000 ms |
Time stamp on signal change |
rising / falling edge as signal entering or exiting |
Isolation |
|
Isolation checked with |
Isolation voltage 500 V |
Environmental requirements |
|
Operating temperature |
|
|
0 °C |
|
60 °C |
Air pressure |
|
|
3 000 m |
Degree of protection |
|
IP20 |
Yes |
General information |
|
Vendor identification (VendorID) |
801Eh |
Dimensions and weight |
|
Dimensions |
|
|
40 mm |
|
125 mm |
|
117 mm |
Weight |
|
|
360 g |
|
6ES7 197-1LB00-0XA0 |
System |
|
Requirements for DP master system |
|
|
244 byte |
Supply voltages |
|
Description |
via bus module |
Rated value |
|
|
20.4 V |
|
28.8 V |
Protocols |
|
PROFIBUS DP protocol |
Yes |
PROFIBUS DP |
|
Properties of the lower-level DP master systems |
|
|
12 Mbit/s; 45.45 Kbit/s to 12 Mbit/s |
|
Active terminating resistor (Bus Terminator) |
|
Yes |
|
9 |
|
31; 64 when using RS 485 repeaters or OLM/OBT |
Interrupts/diagnostics/status information |
|
Status indicator |
No |
Alarms |
|
|
No |
Diagnoses |
|
|
Yes |
Galvanic isolation |
|
to lower-level DP master system |
Yes |
Dimensions and weight |
|
Dimensions |
|
|
40 mm |
|
125 mm |
|
130 mm |
Weight |
|
|
200 g |