6ES7 151-7AB00-0AB0 |
6ES7 151-7AA20-0AB0 |
Product version |
|
|
associated programming package |
|
STEP 7 V5.2 + SP1 or higher with HW update |
Supply voltages |
|
|
Rated value |
|
|
|
20.4 V |
|
Load voltage L+ |
|
|
|
|
24 V |
|
|
20.4 V |
|
|
28.8 V |
|
|
Yes |
|
|
Yes |
Current consumption |
|
|
Inrush current, max. |
3.5 A |
|
Current output to backplane bus (DC 5 V), max. |
|
700 mA |
from supply voltage 1L+, max. |
|
250 mA; 280 mA with DP master module |
Power losses |
|
|
Power loss, typ. |
|
3.3 W |
Memory |
|
|
Work memory |
|
|
|
48 Kibyte; as of FW V1.13 48 KB; previously 24 KB |
96 Kibyte; For program and data |
|
|
No |
Load memory |
|
|
|
|
Yes |
|
|
8 Mbyte |
CPU/ blocks |
|
|
Number of blocks (total) |
|
1 024; (DBs, FCs, FBs); the maximum number of loadable blocks can be reduced by the MMC used. |
DB |
|
|
|
127 |
511; Number range: 1 to 511 |
|
|
16 Kibyte |
FB |
|
|
|
128 |
1 024; Number range: 0 to 2047 |
|
|
16 Kibyte |
FC |
|
|
|
128 |
1 024; Number range: 0 to 2047 |
|
|
16 Kibyte |
OB |
|
|
|
|
16 Kibyte |
Nesting depth |
|
|
|
8 |
8 |
|
|
4 |
CPU processing times |
|
|
for bit operations, min. |
0.1 µs |
0.1 µs |
for word operations, min. |
1 µs |
0.2 µs |
for fixed point arithmetic, min. |
2 µs |
2 µs |
for floating point arithmetic, min. |
20 µs |
3 µs |
Counters, timers and their retentivity |
|
|
S7 counter |
|
|
|
256 |
256 |
|
|
|
|
|
Yes |
|
|
0 |
|
|
255 |
|
|
Z 0 to Z 7 |
|
|
|
|
Yes |
Yes |
|
1 |
0 |
|
999 |
999 |
IEC counter |
|
|
|
|
SFB |
|
|
Unlimited (limited only by RAM capacity) |
S7 times |
|
|
|
256 |
256 |
|
|
|
|
|
Yes |
|
|
0 |
|
|
255 |
|
|
No retentivity |
|
|
|
|
10 ms |
10 ms |
|
9 990 s |
9 990 s |
IEC timer |
|
|
|
|
SFB |
|
|
Unlimited (limited only by RAM capacity) |
Data areas and their retentivity |
|
|
retentive data area in total (incl. times, counters, flags), max. |
4 Kibyte |
64 Kibyte |
Flag |
|
|
|
256 byte |
256 byte |
|
|
Yes |
|
|
MB 0 to MB 15 |
|
|
8; 1 memory byte |
Data blocks |
|
|
|
|
511; Number range: 1 to 511 |
|
|
16 Kibyte |
Local data |
|
|
|
|
510 byte |
Address area |
|
|
I/O address area |
|
|
|
|
2 048 byte |
|
|
2 048 byte |
Process image |
|
|
|
|
128 byte; Not adjustable |
|
|
128 byte; Not adjustable |
Digital channels |
|
|
|
|
16 336 |
|
|
16 336 |
|
|
248 |
|
|
248 |
Analog channels |
|
|
|
|
1 021 |
|
|
1 021 |
|
|
124 |
|
|
124 |
Addressing volume |
|
|
|
244 byte |
|
|
244 byte |
|
Hardware configuration |
|
|
Number of modules per system, max. |
63 |
63; Centralized |
Connectable programming devices/PCs |
PGs/OPs with STEP 7 connectable via PROFIBUS interface |
|
Time of day |
|
|
Clock |
|
|
|
|
Yes |
|
|
Yes |
|
|
6 wk; At 40 °C ambient temperature, typically |
|
|
10 s |
Runtime meter |
|
|
|
|
1 |
|
|
0 |
|
|
0 to 2^31 hours (when using SFC 101) |
|
|
1 hour |
|
|
Yes; Must be restarted at each restart |
Clock synchronization |
|
|
|
|
Yes |
|
|
Yes |
|
|
Yes |
|
|
Yes |
|
|
Yes |
|
|
No |
|
|
No |
S7 message functions |
|
|
Number of login stations for message functions, max. |
|
12; Depending on the configured connections for PG/OP and S7 basic communication |
Process diagnostic messages |
|
Yes; ALARM_S, ALARM_SC, ALARM_SQ, ALARM_D, ALARM_DQ |
simultaneously active Alarm-S blocks, max. |
|
40 |
Test commissioning functions |
|
|
Status/control |
|
|
|
|
Yes |
|
|
Inputs, outputs, memory bits, DB, times, counters |
|
|
30 |
|
|
30 |
|
|
14 |
Forcing |
|
|
|
|
Yes |
Status block |
|
Yes |
Single step |
|
Yes |
Number of breakpoints |
|
2 |
Diagnostic buffer |
|
|
|
Yes |
Yes |
|
100 |
100 |
|
|
No |
Communication functions |
|
|
PG/OP communication |
|
Yes |
Global data communication |
|
|
|
|
Yes |
|
|
4 |
|
|
4 |
|
|
4 |
|
|
22 byte |
|
|
22 byte |
S7 basic communication |
|
|
|
|
Yes |
|
|
76 byte |
|
|
76 byte; 76 bytes (with X_SEND or X_RCV); 64 bytes (with X_PUT or X_GET as server) |
S7 communication |
|
|
|
|
Yes |
|
|
Yes |
|
|
No |
|
|
180 byte |
|
|
64 byte |
S5-compatible communication |
|
|
|
|
No |
Standard communication (FMS) |
|
|
|
|
No |
Number of connections |
|
|
|
|
12 |
|
|
11 |
|
|
1 |
|
|
11 |
|
|
1 |
|
|
10 |
|
|
0 |
|
|
4; As slave only with active interface, with IM 151-7 CPU as DP master |
1st interface |
|
|
Type of interface |
|
Integrated RS 485 interface |
Physics |
|
RS 485 |
Isolated |
|
Yes |
Power supply to interface (15 to 30 V DC), max. |
|
80 mA |
Functionality |
|
|
|
|
Yes |
|
|
No |
|
Yes |
Yes; active / passive |
|
|
No |
MPI |
|
|
|
|
12; Notice: 12 connections per CPU, not per interface |
|
|
|
|
|
Yes |
|
|
Yes; With master module |
|
|
Yes |
|
|
Yes |
|
|
Yes |
|
|
No |
|
|
Yes |
|
|
12 Mbit/s |
DP slave |
|
|
|
11 |
12; Notice: 12 connections per CPU, not per interface |
|
|
|
|
|
Yes; Only when interface active and in master mode |
|
Yes |
Yes |
|
|
No |
|
http://www.siemens.de/profibus-gsd |
http://www.siemens.de/profibus-gsd |
|
12 Mbit/s |
12 Mbit/s |
|
|
Yes; only with passive interface |
|
|
|
|
|
244 byte |
|
|
244 byte |
|
|
32 |
|
|
32 byte; Up to max. size of the transfer memory |
2nd interface |
|
|
Type of interface |
|
External interface via master module 6ES7138-4HA00-0AB0 |
Physics |
|
RS 485 |
Isolated |
|
Yes |
Power supply to interface (15 to 30 V DC), max. |
|
No |
Functionality |
|
|
|
|
No |
|
|
Yes |
|
|
No |
DP master |
|
|
|
|
12; Notice: 12 connections per CPU, not per interface |
|
|
|
|
|
Yes |
|
|
Yes |
|
|
No |
|
|
Yes; I blocks only |
|
|
Yes |
|
|
No |
|
|
Yes |
|
|
Yes |
|
|
Yes |
|
|
Yes |
|
|
Yes |
|
|
Yes |
|
|
12 Mbit/s |
|
|
32; Per station |
|
|
|
|
|
2 Kibyte |
|
|
2 Kibyte |
|
|
|
|
|
244 byte |
|
|
244 byte |
Isochronous mode |
|
|
Isochronous mode |
|
No |
CPU/ programming |
|
|
Configuration rules |
|
max. 63 peripheral modules per station; station width < 1 m or < 2 m; max. 10 A per load group (power module); master interface module on right next to IM 151-7 CPU (X2 interface) |
Programming language |
|
|
|
|
Yes |
|
|
Yes |
|
|
Yes |
|
|
Yes |
|
Yes |
Yes; Optional |
|
|
Yes; Optional |
Command set |
Binary logic operations, bracketed operations, result allocation, saving, counting, loading, transferring, comparing, shifting, rotating, complementation, calling blocks, fixed point arithmetic, floating point arithmetic, jump functions |
See instruction list |
Nesting levels |
8 |
8 |
Know-how protection |
|
|
|
Yes |
Yes |
System functions (SFC) |
Interrupt and error processing, copy data, clock functions, diagnostic functions, module parameterization, operating mode transitions |
See instruction list |
System function blocks (SFB) |
|
See instruction list |
Isolation |
|
|
Isolation checked with |
|
500 VDC |
Galvanic isolation |
|
|
between load voltage and all other switching components |
|
Yes |
between PROFIBUS DP and all other circuit components |
|
Yes |
Permissible potential difference |
|
|
between different circuits |
|
75 VDC / 60 VAC |
Environmental requirements |
|
|
Operating temperature |
|
|
|
0 °C |
|
Dimensions and weight |
|
|
Dimensions |
|
|
|
60 mm |
60 mm; DP master module: 35 mm |
|
119.5 mm |
119.5 mm |
|
75 mm |
75 mm |
Weight |
|
|
|
200 g |
200 g; DP master module: Approx. 100 g |